lgpPwrThresholdTable
LIEBERT-GP-POWER-MIB ·
.1.3.6.1.4.1.476.1.42.3.5.4.7
Object
table
A list of power thresholds for a given power measurement at a
point/location in the system.
The lgpPwrThresholdType in this table corresponds to the
type of measurement the high and low thresholds applies to.
This table contains zero, one, or many rows, depending upon the number
of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the
table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
Context
- MIB
- LIEBERT-GP-POWER-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.5.4.7- Type
- table
- Status
- current
- Parent
- lgpPwrSettings
- Siblings
- 20
- Children
- 1
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpPwrPreferredSource The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
input source of the system. | scalar | ObjectIdentifier | .1.3.6.1.4.1.476.1.42.3.5.4.1 |
| lgpPwrAutoRestartBatteryChargeThreshold The battery charge percentage required before the device can
automatically restart. | scalar | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.10 |
| lgpPwrParallelModuleCount The number of modules in the parallel system. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.11 |
| lgpPwrParallelRedundancyCount The number of redundant modules in the parallel system. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.12 |
| lgpPwrLoadBusSyncMode The configuration of Load Bus Synchronization (LBS) between
independent systems. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.13 |
| lgpPwrEconomicOperationMode The configuration of the economic operation mode of the system. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.14 |
| lgpPwrAutomaticBatteryTest Automatic battery test option. If enabled, the battery will be tested
on a fixed interval. If disabled, the battery test must be initiated
by a battery test command. The interv… | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.15 |
| lgpPwrMinimumRedundantPowerModule The minimum number of redundant power modules that must be present
before sending a loss of power redundancy alarm. If 0, there is no
redundant power functionality. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.16 |
| lgpPwrMinimumRedundantBatteryModule The minimum number of redundant battery modules that must be present
before sending an alarm. If 0, the redundant battery module alarm is
disabled. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.17 |
| lgpPwrOutputToLoadUserOverloadLimit This is the user specified maximum load the device can support
without sending an alarm. | scalar | Volt-Amp SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.18 |
| lgpPwrNoLoadWarningLimit The minimum current draw on the output in which the device considers
there to be a load present on the output. The condition
lgpConditionWarningNoLoadDetected will be triggered i… | scalar | Amp SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.19 |
| lgpPwrLoadOnSource The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is currently
powering the output (load). | scalar | ObjectIdentifier | .1.3.6.1.4.1.476.1.42.3.5.4.2 |
| lgpPwrNoLoadWarningDelay The amount of time to delay before annunciation of the condition
lgpConditionNoLoadDetectedWarning after the output current load
falls below the threshold lgpPwrOutputNoLoadWarnin… | scalar | minutes Integer32 | .1.3.6.1.4.1.476.1.42.3.5.4.20 |
| lgpPwrEconomicOperationModeControl The configuration of the economic operation mode of the system.
Note that this supersedes lgpPwrEconomicOperationMode in newer devices. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.21 |
| lgpPwrNominalVoltageDeviation The nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input. | scalar | Volt SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.3 |
| lgpPwrNominalVoltageDeviationPercent The percentage of the nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input. | scalar | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.4 |
| lgpPwrPhaseDifferenceLimit The maximum phase difference (between the well known
input sources ) in which a transfer to an available input source is
permitted. | scalar | 0.1 Degrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.5 |
| lgpPwrFrequencyDeviationLimit The maximum frequency deviation (between the well known
input sources ) in which a transfer to an available input source is
permitted. | scalar | 0.1 Hertz SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.6 |
| lgpPwrUpsAutoRestart The device will automatically restart when utility power is restored
following a battery discharge. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.8 |
| lgpPwrUpsAutoRestartDelay The device will automatically delay a certain number of seconds and
then restart after utility power is restored following a battery
discharge. The number of seconds to delay is… | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.9 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpPwrThresholdEntry This entry defines the contents of the columns for the table
'lgpPwrThresholdTable'. | row | - | .1.3.6.1.4.1.476.1.42.3.5.4.7.1 |