LIEBERT-GP-POWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
59
.1.3.6.1.4.1.476.1.42.3.5.2.2 · 1 row entry · 18 columns
This table contains a list of AC power measurement point entries.
The table contains zero, one, or many rows, depending upon the number
of power related measurement points available.  The NMS cannot
create or delete rows from the table. The rows are created by the
agent based upon the capabilities of the managed device.  Each row
in the table represents a series of measurements on a given point
or location within the system.  Measurement points/locations are
identified by the object identifier 'lgpPwrMeasurementPointId' in the
'LgpPwrMeasurementPointEntry' object.  The actual measurement being
taken at that identified point is identified by the other
corresponding columns in the LgpPwrMeasurementPointEntry for the
particular row of the table.
lgpPwrMeasurementPointEntry entry .1.3.6.1.4.1.476.1.42.3.5.2.2.1
This entry defines the measurements to be populated in the
various columns of the 'lgpPwrMeasurementPointTable'.
Indexes
lgpPwrMeasurementPointIndex
Column Syntax OID
lgpPwrMeasurementPointIndex
This is the index that indicates the row of the
'lgpPwrMeasurementPointTable' for a power measurement point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.1
lgpPwrMeasurementPointId
An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such …
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.2.2.1.2
lgpPwrMeasurementPointNumLines
The number of lines on the indicated power measurement point.
(i.e. the number of phases on the power source being measured.)
CountSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.3
lgpPwrMeasurementPointNomVolts
The magnitude of the nominal voltage on the power source being
measured.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.4
lgpPwrMeasurementPointNomFrequency
The nominal or configured/expected frequency for the power
source indicated by 'lgpPwrMeasurementPointId' in the
corresponding row in the lgpPwrMeasurementPointTable.
HertzSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.5
lgpPwrMeasurementPointFrequency
The present (actual) frequency for the power source indicated
by 'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
HertzSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.6
lgpPwrMeasurementPointApparentPower
The present apparent AC power for the power source
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable.
Volt-AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.7
lgpPwrMeasurementPointTruePower
The present AC power for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
WattSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.8
lgpPwrMeasurementPointPowerFactor
The present Power Factor for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
.01 Power FactorSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.9
lgpPwrMeasurementPointWattHours
The present number of Watt Hours for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
Watt-HourSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.10
lgpPwrMeasurementPointVAPercent
The percentage of the rated apparent AC power of the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable.
0.1 PercentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.11
lgpPwrMeasurementPointNeutralCurrent
The present neutral current of the power point indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.12
lgpPwrMeasurementPointGroundCurrent
The present ground current of the power point indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable.
0.1 AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.13
lgpPwrMeasurementPointNomCurrent
The nominal or configured/expected current of the power point
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable.
0.1 AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.14
lgpPwrMeasurementPointNomPowerFactor
The nominal or configured/expected power factor of the power point
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable.
.01 Power FactorSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.15
lgpPwrMeasurementPointNomVA
The nominal or configured/expected apparent AC power for the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable.
Volt-AmpSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.16
lgpPwrMeasurementPointNomW
The nominal or configured/expected true AC power for the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable.
WattSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.17
lgpPwrMeasurementPointPowerFactorTag
The present description of the Power Factor for the power source
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable. If Leading, the load is said
to be capacitive and th…
Enumeration
Enumerated Values:
1leading
2lagging
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.19
.1.3.6.1.4.1.476.1.42.3.5.2.3 · 1 row entry · 21 columns
A list of power measurements for each phase/line for a given
power measurement point/location in the 'lgpPwrMeasurementPointTable'.
The lgpPwrMeasurementPointIndex in this table corresponds to the
index in the lgpPwrMeasurementPointTable.
          
This table contains zero, one, or
many rows, depending upon the number of power line source objects
available.  The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
lgpPwrLineMeasurementEntry entry .1.3.6.1.4.1.476.1.42.3.5.2.3.1
This entry defines the contents of the columns for the table
'lgpPwrLineMeasurementTable'.
Indexes
lgpPwrMeasurementPtIndex lgpPwrLineMeasurementIndex
Column Syntax OID
lgpPwrMeasurementPtIndex
This is the index indicating the row of the table
'lgpPwrMeasurementPointTable' for a power measurement point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.1
lgpPwrLineMeasurementIndex
This is the index indicating the row of the table
'lgpPwrLineMeasurementTable' for a power measurement point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.2
lgpPwrMeasurementPoint
An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID name usually
implies a location of the measurement point such as…
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.2.3.1.3
lgpPwrLineMeasurementVoltsLL
The present Line-to-Line voltage measurement for the indicated
source. The line being measured is given by the
lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA].
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.4
lgpPwrLineMeasurementVoltsLN
The present Line-to-neutral voltage measurement for the indicated
source. The line being measured is given by the
lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.5
lgpPwrLineMeasurementCurrent
The present current measurement for the indicated source. The line
being measured is given by the 'lgpPwrLineMeasurementIndex' where
[1 = A, 2 = B, 3 = C].
AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.6
lgpPwrLineMeasurementCapacity
The percentage of the power capacity presently being used on this
line.
percentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.7
lgpPwrLineMeasurementVA
The present apparent AC line power.
Volt-AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.8
lgpPwrLineMeasurementTruePower
The present AC line power measured in watts.
WattSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.9
lgpPwrLineMeasurementVoltageTHD
The present total harmonic distortion on the AC line voltage.
0.1 PercentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.10
lgpPwrLineMeasurementCurrentTHD
The present total harmonic distortion on the AC line current.
0.1 PercentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.11
lgpPwrLineMeasurementKFactorCurrent
The present line K Factor.
0.1 K FactorSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.12
lgpPwrLineMeasurementCrestFactorCurrent
The present crest factor of the line current.
0.1 Crest FactorSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.13
lgpPwrLineMeasurementPowerFactor
The present Power Factor for the line.
0.01 Power FactorSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.14
lgpPwrLineMeasurementPowerFactorTag
The present description of the Power Factor for the line. If
Leading, the load is said to be capacitive and the phase of the
current leads the voltage. If Lagging, the load is said to be
inductive and the phase of the…
Enumeration
Enumerated Values:
1leading
2lagging
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.15
lgpPwrLineMeasurementMaxVolts
The maximum voltage measurement recorded for the indicated source
since the command 'lgpPwrStatisticsReset' was executed.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.16
lgpPwrLineMeasurementMinVolts
The minimum voltage measurement recorded for the
indicated source since the command 'lgpPwrStatisticsReset' was
executed.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.17
lgpPwrLineMeasurementVAR
The present reactive AC line power of the power source indicated by
'lgpPwrMeasurementPoint'.
Volt-Amp-ReactiveSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.18
lgpPwrLineMeasurementPercentLoad
The present percent load of the AC line power.
percentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.19
lgpPwrLineMeasurementVolts
The present voltage measurement for the indicated source.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.20
lgpPwrLineMeasurementVACapacity
The percentage of the apparent power capacity presently being
used on this line.
percentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.3.1.21
.1.3.6.1.4.1.476.1.42.3.5.2.4 · 1 row entry · 7 columns
This table contains a list of DC power measurement point entries.
The table contains zero, one, or many rows, depending upon the number
of power related measurement points available.  The NMS cannot
create or delete rows from the table. The rows are created by the
agent based upon the capabilities of the managed device.  Each row
in the table represents a series of measurements on a given point
or location within the system.  Measurement points/locations are
identified by the object identifier 'lgpPwrDcMeasurementPointId' in the
'LgpPwrDcMeasurementPointEntry' object.  The actual measurement being
taken at that identified point is identified by the other
corresponding columns in the LgpPwrDcMeasurementPointEntry for the
particular row of the table.
lgpPwrDcMeasurementPointEntry entry .1.3.6.1.4.1.476.1.42.3.5.2.4.1
This entry defines the measurements to be populated in the
various columns of the 'lgpPwrDcMeasurementPointTable'.
Indexes
lgpPwrDcMeasurementPointIndex
Column Syntax OID
lgpPwrDcMeasurementPointIndex
This is the index that indicates the row of the
'lgpPwrMeasurementPointTable' for a power measurement point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.1
lgpPwrDcMeasurementPointId
An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such …
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.2.4.1.2
lgpPwrDcMeasurementPointSubID
The identifier used to differentiate between identical thresholds
for a given point index and point ID in the DC measurements table.
CountSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.3
lgpPwrDcMeasurementPointVolts
The present DC voltage for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.4
lgpPwrDcMeasurementPointCurrent
The present DC current for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable.
AmpSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.5
lgpPwrDcMeasurementPointNomVolts
The nominal(configured/expected) DC voltage for the power source
indicated by 'lgpPwrDcMeasurementPointId' in the
corresponding row in the lgpPwrDcMeasurementPointTable.
VoltSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.6
lgpPwrDcMeasurementPointTruePower
The present DC power for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable.
WattSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.2.4.1.7
.1.3.6.1.4.1.476.1.42.3.5.4.7 · 1 row entry · 8 columns
A list of power thresholds for a given power measurement at a
point/location in the system.
The lgpPwrThresholdType in this table corresponds to the
type of measurement the high and low thresholds applies to.
          
This table contains zero, one, or many rows, depending upon the number
of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the
table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
lgpPwrThresholdEntry entry .1.3.6.1.4.1.476.1.42.3.5.4.7.1
This entry defines the contents of the columns for the table
'lgpPwrThresholdTable'.
Indexes
lgpPwrThresholdIndex
Column Syntax OID
lgpPwrThresholdIndex
This is the index indicating the row of the table
'lgpPwrLineMeasurementTable' for a power measurement point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.1
lgpPwrThresholdPoint
An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such …
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.4.7.1.2
lgpPwrThresholdSubID
This is a sub identifier for the 'lgpPwrThresholdPoint'.
It indicates the instance number of the well known threshold point.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.3
lgpPwrThresholdType
An OID representing a well known measurement type.
These object identifiers indicate the type of measurement referenced
by the row of the table. These object identifiers can encompass
units of measure, lines of referen…
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.4.7.1.4
lgpPwrThresholdHighWarning
The high warning threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint…
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.5
lgpPwrThresholdHighFailure
The high failure threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint…
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.6
lgpPwrThresholdLowWarning
The low warning threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint'…
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.7
lgpPwrThresholdLowFailure
The low failure threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint'…
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.5.4.7.1.8
.1.3.6.1.4.1.476.1.42.3.5.6.2 · 1 row entry · 5 columns
A list of load circuits that can be controlled(opened or closed).
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
lgpPwrLoadCircuitEntry entry .1.3.6.1.4.1.476.1.42.3.5.6.2.1
This entry defines the contents of the columns for the table
'lgpPwrLoadCircuitTable'.
Indexes
lgpPwrLoadCircuitIndex
Column Syntax OID
lgpPwrLoadCircuitIndex
This is the index indicating the row of the table
'lgpPwrLoadCircuitTable'.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.1
lgpPwrLoadCircuitId
An OID representing a well known load circuit identifier.
These load circuit identifiers indicate the name or type of load
circuit reference in the table.
ObjectIdentifier .1.3.6.1.4.1.476.1.42.3.5.6.2.1.2
lgpPwrLoadCircuitSubID
This is a sub identifier for the 'lgpPwrLoadCircuitId'.
It indicates the hardware identifier of the load control circuit.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.3
lgpPwrLoadCircuitState
This identifier indicates the state of the load circuit.
When read, only a closed or open response will be returned.
When written to, the state of the circuit will transition to
desired state.
Enumerationr/w
Enumerated Values:
1on
2off
3default
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.4
lgpPwrLoadCircuitStateAndControl
This identifier indicates the state of the load circuit.
When read, only a closed or open response will be returned.
When written to, the state of the circuit will transition to
desired state.
Enumerationr/w
Enumerated Values:
0off
1on
2reboot
.1.3.6.1.4.1.476.1.42.3.5.6.2.1.5