lgpPwrParallelModuleCount
LIEBERT-GP-POWER-MIB ·
.1.3.6.1.4.1.476.1.42.3.5.4.11
Object
The number of modules in the parallel system.
Context
- MIB
- LIEBERT-GP-POWER-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.5.4.11- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- Count
- Parent
- lgpPwrSettings
- Siblings
- 20
Syntax
Count SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpPwrPreferredSource The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
input source of the system. | scalar | ObjectIdentifier | .1.3.6.1.4.1.476.1.42.3.5.4.1 |
| lgpPwrAutoRestartBatteryChargeThreshold The battery charge percentage required before the device can
automatically restart. | scalar | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.10 |
| lgpPwrParallelRedundancyCount The number of redundant modules in the parallel system. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.12 |
| lgpPwrLoadBusSyncMode The configuration of Load Bus Synchronization (LBS) between
independent systems. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.13 |
| lgpPwrEconomicOperationMode The configuration of the economic operation mode of the system. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.14 |
| lgpPwrAutomaticBatteryTest Automatic battery test option. If enabled, the battery will be tested
on a fixed interval. If disabled, the battery test must be initiated
by a battery test command. The interv… | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.15 |
| lgpPwrMinimumRedundantPowerModule The minimum number of redundant power modules that must be present
before sending a loss of power redundancy alarm. If 0, there is no
redundant power functionality. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.16 |
| lgpPwrMinimumRedundantBatteryModule The minimum number of redundant battery modules that must be present
before sending an alarm. If 0, the redundant battery module alarm is
disabled. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.17 |
| lgpPwrOutputToLoadUserOverloadLimit This is the user specified maximum load the device can support
without sending an alarm. | scalar | Volt-Amp SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.18 |
| lgpPwrNoLoadWarningLimit The minimum current draw on the output in which the device considers
there to be a load present on the output. The condition
lgpConditionWarningNoLoadDetected will be triggered i… | scalar | Amp SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.19 |
| lgpPwrLoadOnSource The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is currently
powering the output (load). | scalar | ObjectIdentifier | .1.3.6.1.4.1.476.1.42.3.5.4.2 |
| lgpPwrNoLoadWarningDelay The amount of time to delay before annunciation of the condition
lgpConditionNoLoadDetectedWarning after the output current load
falls below the threshold lgpPwrOutputNoLoadWarnin… | scalar | minutes Integer32 | .1.3.6.1.4.1.476.1.42.3.5.4.20 |
| lgpPwrEconomicOperationModeControl The configuration of the economic operation mode of the system.
Note that this supersedes lgpPwrEconomicOperationMode in newer devices. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.21 |
| lgpPwrNominalVoltageDeviation The nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input. | scalar | Volt SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.3 |
| lgpPwrNominalVoltageDeviationPercent The percentage of the nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input. | scalar | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.4 |
| lgpPwrPhaseDifferenceLimit The maximum phase difference (between the well known
input sources ) in which a transfer to an available input source is
permitted. | scalar | 0.1 Degrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.5 |
| lgpPwrFrequencyDeviationLimit The maximum frequency deviation (between the well known
input sources ) in which a transfer to an available input source is
permitted. | scalar | 0.1 Hertz SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.6 |
| lgpPwrThresholdTable A list of power thresholds for a given power measurement at a
point/location in the system.
The lgpPwrThresholdType in this table corresponds to the
type of measurement the high a… | table | - | .1.3.6.1.4.1.476.1.42.3.5.4.7 |
| lgpPwrUpsAutoRestart The device will automatically restart when utility power is restored
following a battery discharge. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.4.8 |
| lgpPwrUpsAutoRestartDelay The device will automatically delay a certain number of seconds and
then restart after utility power is restored following a battery
discharge. The number of seconds to delay is… | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.4.9 |