lgpPwrStateUpsOutputSource
LIEBERT-GP-POWER-MIB ·
.1.3.6.1.4.1.476.1.42.3.5.3.55
Object
scalar
Enumeration
The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.
NOTE: In a single-module system, this point is intended to have the same
behavior as the RFC1628 point upsOutputSource.
Context
- MIB
- LIEBERT-GP-POWER-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.5.3.55- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- lgpPwrStatus
- Siblings
- 57
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | other |
2 | none |
3 | normal |
4 | bypass |
5 | battery |
6 | booster |
7 | reducer |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpPwrTransferCount Number of times that the output load has been transferred between the
available input sources. | scalar | Count SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.1 |
| lgpPwrOutputToLoadOnBypass The present source of output power is the Bypass. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.10 |
| lgpPwrBoost The present state of the boost circuitry | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.11 |
| lgpPwrBuck The present state of the buck circuitry | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.12 |
| lgpPwrShutdownOverTemperature The system has previously shutdown due to an over temperature
condition. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.13 |
| lgpPwrShutdownOverload The system has previously shutdown due to an over load condition. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.14 |
| lgpPwrShutdownDcBusOverload The system has previously shutdown due to a DC bus over load
condition. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.15 |
| lgpPwrShutdownOutputShort The system has previously shutdown due to an output short condition. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.16 |
| lgpPwrShutdownLineSwap The system has previously shutdown due to a condition where the line
and neutral were reversed. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.17 |
| lgpPwrShutdownLowBattery The system has previously shutdown due to a low battery condition. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.18 |
| lgpPwrShutdownRemote The system has previously shutdown due to a remote shutdown command. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.19 |
| lgpPwrAutoTransferTimer The required wait time between output load auto transfer attempts
between available input sources. | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.2 |
| lgpPwrShutdownInputUnderVoltage The system has previously shutdown due to an under voltage condition
during startup. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.20 |
| lgpPwrShutdownPowerFactorCorrectionFailure The system has previously shutdown due to a power factor correction
startup failure. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.21 |
| lgpPwrShutdownHardware The system has previously shutdown due external shutdown signal. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.22 |
| lgpPwrRedundantSubModule The system has a redundant battery module installed. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.23 |
| lgpPwrBypassReady The ability of the bypass to support the output load of the system.
If Yes, the bypass is available to transfer to. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.24 |
| lgpPwrGeneratorStatus The state of the system generator. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.25 |
| lgpPwrRotaryBreakerStatus The state of the system rotary breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.26 |
| lgpPwrPowerFactorCorrection The state of the power factor correction circuitry of the system. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.27 |
| lgpPwrBypassSyncDiff The phase angle difference between the inverter output and bypass
source. A positive value means the inverter leads the bypass source.
A negative value means the inverter lags the… | scalar | 0.1 Degrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.28 |
| lgpPwrBypassOverloadShutdownTime The calculated time remaining before bypass static switch shutdown due
to the present overload condition. If the bypass is not in an overload
condition, this object returns -1. | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.29 |
| lgpPwrAutoReTransferEnabled The ability to retransfer the output load automatically to the well
known measurement source from the 'lgpPwrWellKnownMeasurements'
sub-tree that is the preferred input source of … | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.3 |
| lgpPwrInverterOverloadShutdownTime The calculated time remaining before inverter shutdown. The calculated
time of inverter operation remaining for the present overload event.
Note: If the inverter is not… | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.30 |
| lgpPwrStateOutputSource The UPS's output power source (inverter, bypass, or none).
NOTE: It is possible that the load still has power from the
Maintenance Bypass. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.31 |
| lgpPwrStateInputSource The system input power source (none, utility, generator). | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.32 |
| lgpPwrStateInputQualification The current state of the system input. The unit may or may not operate
normally under 'marginalLow' and 'marginalHigh' states. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.33 |
| lgpPwrStateBypassStaticSwitchState The current state of the bypass static switch. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.34 |
| lgpPwrStateBypassQualification The current operational state of the bypass static switch. The unit may
or may not operate normally under 'marginalLow' and 'marginalHigh'
states. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.35 |
| lgpPwrStateDCBusQualification The current operational state of the DC bus. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.36 |
| lgpPwrStateOutQualification The current operational state of the output. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.37 |
| lgpPwrStateInverterQualification The current operational state of the inverter. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.38 |
| lgpPwrStateInverterState The current state of the inverter. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.39 |
| lgpPwrSyncPhaseAngle The phase angle difference of source 1 in relation to source 2. | scalar | 0.1 Degrees Integer32 | .1.3.6.1.4.1.476.1.42.3.5.3.4 |
| lgpPwrStateRectifierState The current state of the rectifier. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.40 |
| lgpPwrStateModuleGroup This group contains UPS module information. | node | - | .1.3.6.1.4.1.476.1.42.3.5.3.41 |
| lgpPwrStateBackfeedBrkrState The state of the Static Bypass Switch Line Disconnect Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.42 |
| lgpPwrStateLoadDisconnectState The state of the Static Bypass Switch Load Disconnect Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.43 |
| lgpPwrStateInputBrkrState The state of the Input Disconnect Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.44 |
| lgpPwrStateTrapFilterBrkrState The state of the Trap Filter Disconnect Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.45 |
| lgpPwrStateInvOutputBrkrState The state of the Inverter Output Disconnect Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.46 |
| lgpPwrStateIntBypassBrkrState The state of the Internal Bypass Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.47 |
| lgpPwrStateBypassIsolBrkrState The state of the Bypass Isolation Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.48 |
| lgpPwrStateRectifierIsolBrkrState The state of the Rectifier Isolation Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.49 |
| lgpPwrParallelSystemOutputToLoadSource The source supporting the parallel system's load. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.5 |
| lgpPwrStateMaintBypassBrkrState The state of the Maintenance Bypass Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.50 |
| lgpPwrStateMaintIsolBrkrState The state of the Maintenance Isolation Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.51 |
| lgpPwrStateOutStaticSwState The state of the Output Series Static Switch. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.52 |
| lgpPwrStateModuleOutBrkrState The state of the Module Output Breaker. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.53 |
| lgpPwrBypassReXfrRemainTime The time remaining before an inverter overload or inverter fault can
be cleared and auto retransfer from the bypass to the inverter can take
place.
Note: If an inver… | scalar | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.476.1.42.3.5.3.54 |
| lgpPwrStateLoadBusSynchronization The state of the Load Bus Synchronizer (LBS). | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.56 |
| lgpPwrStateCircuitBrkrStateGroup This group contains Static Switch circuit breaker state information. | node | - | .1.3.6.1.4.1.476.1.42.3.5.3.57 |
| lgpPwrEconomicOperation The present state of ECO mode operation,
on(1) if system is on bypass due to ECO mode operation,
off(0) any other time. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.58 |
| lgpPwrDcToDcConverter The state of the DC to DC converter. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.6 |
| lgpPwrOutputToLoadOnInverter The present source of output power is the Inverter. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.7 |
| lgpPwrBatteryChargeCompensating The system is adjusting the battery charging algorithm to accommodate
for the battery temperature. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.8 |
| lgpPwrInverterReady The ability of the inverter to support the output load of the system. | scalar | Enumeration | .1.3.6.1.4.1.476.1.42.3.5.3.9 |