lgpEnvConfigBmsResetTimer

LIEBERT-GP-ENVIRONMENTAL-MIB · .1.3.6.1.4.1.476.1.42.3.4.4.36

Object

scalar r/w minutes SNMPv2-SMIUnsigned32
The current count-down time for a BMS to continue controlling the fan
speed.  If this value reaches 0, then the condition
lgpConditionBmsResetTimerExpired will be generated.  If a BMS wants to
continue controlling the fan speed, it must reset this timer.  Typical
values range from 0 to 120 minutes (actual valid ranges may differ from
unit to unit).

Context

MIB
LIEBERT-GP-ENVIRONMENTAL-MIB
OID
.1.3.6.1.4.1.476.1.42.3.4.4.36
Type
scalar
Access
readwrite
Status
current
Units
minutes
Parent
lgpEnvConfig
Siblings
41

Syntax

minutes SNMPv2-SMIUnsigned32
Source
SNMPv2-SMIUnsigned32
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295

Related Objects