WebGraph-AnalogIO-57762-US-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
10
Rows
10
Columns
100
.1.3.6.1.4.1.5040.1.2.29.1.2 · 1 row entry · 1 columns
List of sensors.
wtWebGraphAnalog57762SensorEntry entry .1.3.6.1.4.1.5040.1.2.29.1.2.1
List of sensor numbers.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762SensorNo mandatory
Sensor number.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.5040.1.2.29.1.2.1.1
.1.3.6.1.4.1.5040.1.2.29.1.3 · 1 row entry · 1 columns
List of measurement values corresponding to the channel numbers.
wtWebGraphAnalog57762ValuesEntry entry .1.3.6.1.4.1.5040.1.2.29.1.3.1
Measurement values of the sensors.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762Values mandatory
Measurement value of the sensor, ASCII.
This value will be translated according to the ports settings
for the read and write operations.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.29.1.3.1.1
.1.3.6.1.4.1.5040.1.2.29.1.4 · 1 row entry · 1 columns
List of binary measurement values corresponding to the channel numbers.
wtWebGraphAnalog57762BinaryValuesEntry entry .1.3.6.1.4.1.5040.1.2.29.1.4.1
Binary measurement values of the sensors.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762BinaryValues mandatory
Binary measurement value of the sensor in 1/1000,
signed number, 0x7FFFFFFF indicates an invalid value.
This value will be translated according to the ports settings
for the read and write operations.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.29.1.4.1.1
.1.3.6.1.4.1.5040.1.2.29.1.8 · 1 row entry · 1 columns
List of measurement values corresponding to the channel numbers.
wtWebGraphAnalog57762ValuesPointEntry entry .1.3.6.1.4.1.5040.1.2.29.1.8.1
Measurement values of the sensors.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762ValuesPoint mandatory
Measurement value of the sensor, ASCII.
This value will be translated according to the ports settings
for the read and write operations.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.29.1.8.1.1
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.2 · 1 row entry · 1 columns
Table of indices.
wtWebGraphAnalog57762BinaryIfEntry entry .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.2.1
Indices of the binary channels.
Indexes
wtWebGraphAnalog57762BinaryModeNo
Column Syntax OID
wtWebGraphAnalog57762BinaryModeNo mandatory
Number of the binary channel.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.2.1.1
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3 · 1 row entry · 29 columns
Table of properties of the binary mode.
wtWebGraphAnalog57762BinaryEntry entry .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1
Binary properties.
Indexes
wtWebGraphAnalog57762BinaryModeNo
Column Syntax OID
wtWebGraphAnalog57762BinaryOperationMode mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : UDP Peer
Bit 1 : TCP Client
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.1
wtWebGraphAnalog57762BinaryTcpServerLocalPort mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual).
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.2
wtWebGraphAnalog57762BinaryTcpServerInputTrigger mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input …
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.3
wtWebGraphAnalog57762BinaryTcpServerApplicationMode mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 4-7: unused
Bit 3 : OPC Device
Bit 2 : Box2Box S…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.4
wtWebGraphAnalog57762BinaryTcpClientLocalPort mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual).
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.5
wtWebGraphAnalog57762BinaryTcpClientServerPort mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the server port to zero.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.6
wtWebGraphAnalog57762BinaryTcpClientServerIpAddr mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the server IP address to 0.0.0.0.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.7
wtWebGraphAnalog57762BinaryTcpClientServerPassword mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password
to establish the connection, if a server administrator password
exists.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.8
wtWebGraphAnalog57762BinaryTcpClientInactivity mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server.
The value 0 deactivates the timer. Using the Box2Box mode this function is
disabled.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.9
wtWebGraphAnalog57762BinaryTcpClientInputTrigger mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input …
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.10
wtWebGraphAnalog57762BinaryTcpClientInterval mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the
periodical sending.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.11
wtWebGraphAnalog57762BinaryTcpClientApplicationMode mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : Box2Box Slave
Bit 1 : Compat…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.12
wtWebGraphAnalog57762BinaryUdpPeerLocalPort mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual).
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.13
wtWebGraphAnalog57762BinaryUdpPeerRemotePort mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the remote port to zero.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.14
wtWebGraphAnalog57762BinaryUdpPeerRemoteIpAddr mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the remote device IP address to 0.0.0.0.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.15
wtWebGraphAnalog57762BinaryUdpPeerInputTrigger mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input …
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.16
wtWebGraphAnalog57762BinaryUdpPeerInterval mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the
periodical sending.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.17
wtWebGraphAnalog57762BinaryUdpPeerApplicationMode mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.18
wtWebGraphAnalog57762BinaryConnectedPort mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.19
wtWebGraphAnalog57762BinaryConnectedIpAddr mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read.
RFC1155-SMIIpAddress
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.20
wtWebGraphAnalog57762BinaryTcpServerClientHttpPort mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port.
Not used at mode Compatible 50xxx.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.21
wtWebGraphAnalog57762BinaryTcpClientServerHttpPort mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.22
wtWebGraphAnalog57762BinaryTcpServerHysteresis1 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57762BinaryTcpServerInputTrigger.
With a hysteresis of zero any change will be t…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.23
wtWebGraphAnalog57762BinaryTcpServerHysteresis2 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57762BinaryTcpServerInputTrigger.
With a hysteresis of zero any change will be t…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.24
wtWebGraphAnalog57762BinaryTcpClientHysteresis1 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57762BinaryTcpClientInputTrigger.
With a hysteresis of zero any change will be t…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.25
wtWebGraphAnalog57762BinaryTcpClientHysteresis2 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57762BinaryTcpClientInputTrigger.
With a hysteresis of zero any change will be t…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.26
wtWebGraphAnalog57762BinaryUdpPeerHysteresis1 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57762BinaryUdpPeerInputTrigger.
With a hysteresis of zero any change will be tra…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.27
wtWebGraphAnalog57762BinaryUdpPeerHysteresis2 mandatory
A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57762BinaryUdpPeerInputTrigger.
With a hysteresis of zero any change will be tra…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.28
wtWebGraphAnalog57762BinaryTcpClientServerUserName mandatory
Building a connection may be protected by a specific
user name within the server. Enter the user name
to establish the connection, if a user name entry
exists.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.3.9.3.1.29
.1.3.6.1.4.1.5040.1.2.29.3.1.5.2 · 1 row entry · 1 columns
List of alarm indices.
wtWebGraphAnalog57762AlarmIfEntry entry .1.3.6.1.4.1.5040.1.2.29.3.1.5.2.1
Numbers of the alarms.
Indexes
wtWebGraphAnalog57762AlarmNo
Column Syntax OID
wtWebGraphAnalog57762AlarmNo mandatory
Alarm number.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5040.1.2.29.3.1.5.2.1.1
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3 · 1 row entry · 49 columns
List of settings depending on the alarm number.
wtWebGraphAnalog57762AlarmEntry entry .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1
Alarm parameters of the individual alarms.
Indexes
wtWebGraphAnalog57762AlarmNo
Column Syntax OID
wtWebGraphAnalog57762AlarmTrigger mandatory
Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart

Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.1
wtWebGraphAnalog57762AlarmMin1 mandatory
Minimum sensor 1 with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.2
wtWebGraphAnalog57762AlarmMax1 mandatory
Maximum sensor 1 with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.3
wtWebGraphAnalog57762AlarmHysteresis1 mandatory
Reading changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.4
wtWebGraphAnalog57762AlarmDelay mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes).
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.5
wtWebGraphAnalog57762AlarmInterval mandatory
Send interval for alarm messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.6
wtWebGraphAnalog57762AlarmEnable mandatory
Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.7
wtWebGraphAnalog57762AlarmEMailAddr mandatory
E-Mail address for sending the alarm mail to.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.8
wtWebGraphAnalog57762AlarmMailSubject mandatory
Subject line for alarm mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.9
wtWebGraphAnalog57762AlarmMailText mandatory
Alarm mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.10
wtWebGraphAnalog57762AlarmManagerIP mandatory
Name or IP address of the SNMP Manager which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.11
wtWebGraphAnalog57762AlarmTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.12
wtWebGraphAnalog57762AlarmMailOptions mandatory
Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.13
wtWebGraphAnalog57762AlarmTcpIpAddr mandatory
Name or IP address of the TCP server which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.14
wtWebGraphAnalog57762AlarmTcpPort mandatory
Port number of the TCP server which accepts the trap.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.15
wtWebGraphAnalog57762AlarmTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.16
wtWebGraphAnalog57762AlarmClearMailSubject mandatory
Subject line for alarm clear mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.17
wtWebGraphAnalog57762AlarmClearMailText mandatory
Alarm clear mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.18
wtWebGraphAnalog57762AlarmClearTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.19
wtWebGraphAnalog57762AlarmClearTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.20
wtWebGraphAnalog57762AlarmMin2 mandatory
Minimum sensor 2 with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.21
wtWebGraphAnalog57762AlarmMax2 mandatory
Maximum sensor 2 with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.22
wtWebGraphAnalog57762AlarmHysteresis2 mandatory
Hysterese rel. sensor 2 with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.23
wtWebGraphAnalog57762AlarmSyslogIpAddr mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.24
wtWebGraphAnalog57762AlarmSyslogPort mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.25
wtWebGraphAnalog57762AlarmSyslogText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.26
wtWebGraphAnalog57762AlarmSyslogClearText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body of a alarm clear message.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.27
wtWebGraphAnalog57762AlarmFtpDataPort mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.28
wtWebGraphAnalog57762AlarmFtpFileName mandatory
Name of the file including path informations.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.29
wtWebGraphAnalog57762AlarmFtpText mandatory
Message text to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.30
wtWebGraphAnalog57762AlarmFtpClearText mandatory
Alarm clear message to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.31
wtWebGraphAnalog57762AlarmFtpOption mandatory
Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file

Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STOR…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.32
wtWebGraphAnalog57762AlarmTimerCron mandatory
This entry defines a time window for alarm 1-8 and a activation time for the report.
A time window is definied by start and stop time stamp, seperated by a space or tab.
The activation time of the report is defined by a…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.33
wtWebGraphAnalog57762AlarmName mandatory
Alert name
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.39
wtWebGraphAnalog57762AlarmActive mandatory
Alert active
1 = ON
0 = OFF
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.40
wtWebGraphAnalog57762AlarmHttpReqAuthEnable mandatory
Binary coded options, select only one option at the same time:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : HHTP Request Authentication enable
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.61
wtWebGraphAnalog57762AlarmHttpReqAuthUser mandatory
HTTP Request: User
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.62
wtWebGraphAnalog57762AlarmHttpReqAuthPassword mandatory
HTTP Request: Password
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.63
wtWebGraphAnalog57762AlarmHttpReqSetUrl mandatory
HTTP Request: Set URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.64
wtWebGraphAnalog57762AlarmHttpReqClearUrl mandatory
HTTP Request: Clear URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.65
wtWebGraphAnalog57762AlarmHttpReqServerPort mandatory
HTTP Request: Server Port
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.66
wtWebGraphAnalog57762AlarmMqttTopicPath mandatory
MQTT Publish: Topic path
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.67
wtWebGraphAnalog57762AlarmMqttTopicSetTopic mandatory
MQTT Publish: Topic SET message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.68
wtWebGraphAnalog57762AlarmMqttTopicClear mandatory
MQTT Publish: Topic CLEAR message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.69
wtWebGraphAnalog57762AlarmSensorLostSelection mandatory
Binary coded options:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : Sensor 0
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.70
wtWebGraphAnalog57762AlarmLimitWindow mandatory
If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE
the alarm is generated when the measured value is lower than the mini…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.71
wtWebGraphAnalog57762AlarmSnmpManagerPort mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.76
wtWebGraphAnalog57762AlarmMqttQoS mandatory
Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: QoS 0
Bit 1: QoS 1
Bit 2: QoS 2
Bit 3-7:unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.77
wtWebGraphAnalog57762AlarmMqttRetain mandatory
Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : retain enable
Bit 1-7 : unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.1.5.3.1.78
.1.3.6.1.4.1.5040.1.2.29.3.1.6.2.3 · 1 row entry · 2 columns
List of sensor colors for the praphical presentation.
wtWebGraphAnalog57762SensorColor2Entry entry .1.3.6.1.4.1.5040.1.2.29.3.1.6.2.3.1
Numbers of the sensors.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762GraphicsSensorColor mandatory
Color of the sensors at the praphical presention.
OctetStringr/w
Constraints:
range: 3-3
.1.3.6.1.4.1.5040.1.2.29.3.1.6.2.3.1.1
wtWebGraphAnalog57762GraphicsSelectScale mandatory
Assignes one of 4 scales to a sensor:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Use Scale 1
Bit 1 : Use Scale 2
Bit 2-7: unused
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.1.6.2.3.1.2
.1.3.6.1.4.1.5040.1.2.29.3.2.1 · 1 row entry · 14 columns
List of settings depending on the sensor number.
wtWebGraphAnalog57762PortEntry entry .1.3.6.1.4.1.5040.1.2.29.3.2.1.1
Sensor parameters for the individual sensors.
Indexes
wtWebGraphAnalog57762SensorNo
Column Syntax OID
wtWebGraphAnalog57762PortName mandatory
Name of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.1
wtWebGraphAnalog57762PortText mandatory
Description of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.2
wtWebGraphAnalog57762PortOffset1 mandatory
Offset calibration: Offset in degrees with maximum 3 decimal places at set point 1.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.3
wtWebGraphAnalog57762SetPoint1 mandatory
Offset calibration: Reference set point 1 in degrees with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.4
wtWebGraphAnalog57762PortOffset2 mandatory
Offset calibration: Offset in degrees with maximum 3 decimal places at set point 2.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.5
wtWebGraphAnalog57762SetPoint2 mandatory
Offset calibration: Reference set point 2 in degrees with maximum 3 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.6
wtWebGraphAnalog57762PortComment mandatory
Offset calibration: informations of date, name of operator, reference devices.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.7
wtWebGraphAnalog57762PortSensorSelect mandatory
Binary coded options for sensor 1:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : 0-20mA (default)
Bit 1 : 4-20mA
Bit 2 : Disconnect
Bit 3-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.2.1.1.8
wtWebGraphAnalog57762PortUnit mandatory
User scale: displayed unit.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.9
wtWebGraphAnalog57762PortScale0 mandatory
User scale: displayed value in 1/1000 at 0% full scale range.
Range: -999999.999 to 999999.999
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.10
wtWebGraphAnalog57762PortScale100 mandatory
User scale: displayed value in 1/1000 at 100% full scale range.
Range: -999999.999 to 999999.999
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.11
wtWebGraphAnalog57762PortOutputMode mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. If an output mode is selected,
Bit 2 in wtWebGraphAnalog57762PortInputMode will be set automat…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.2.1.1.12
wtWebGraphAnalog57762PortInputMode mandatory
This binary coded input mode defines the individual operation mode for any
input. More than one mode must not be selected. If an input mode is selected,
Bit 5 in wtWebGraphAnalog57762PortOutputMode will be set automatic…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.29.3.2.1.1.13
wtWebGraphAnalog57762PortPresetValue mandatory
This value will be set after reset or initialisation.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.29.3.2.1.1.16