EATON-EPDU-MA-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
33
.1.3.6.1.4.1.534.6.6.6.1.2.2 · 1 row entry · 11 columns
A list of outlet entries. The number of
entries is given by the value of outletCount.
outletEntry entry .1.3.6.1.4.1.534.6.6.6.1.2.2.1
An outlet entry containing objects at the
for a particular outlet.
Indexes
outletIndex
Column Syntax OID
outletIndex
A unique value for each outlet. Its value
ranges between 1 and the value of outletCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.1
outletLabel
A textual string containing information
about the outlet.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.2
outletOperationalState
A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet
Enumerationr/w
Enumerated Values:
-1error
0off
1on
2cycling
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.3
outletCurrent
A unique value for the current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmps
Textual Convention: MilliAmps Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.4
outletMaxCurrent
A unique value for the max. current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmps
Textual Convention: MilliAmps Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.5
outletVoltage
A unique value for the voltage sensor
attached to the outlet.This value is
reported in millivolts (1/1000th of a volt)
MilliVolts
Textual Convention: MilliVolts Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.6
outletActivePower
A unique value for the active power sensor
attached to the outlet. This value is
reported in Watts.
Watts
Textual Convention: Watts Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.7
outletApparentPower
A unique value for the apparent power sensor
attached to the outlet. This value is
reported in Volt-Amps
VoltAmps
Textual Convention: VoltAmps Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.8
outletPowerFactor
A unique value for the power factor
of the outlet. The reading represents a
percentage in the range of 0% to 100%.
PowerFactorPercentage
Textual Convention: PowerFactorPercentage Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.9
outletCurrentUpperWarning
The value of the upper warning (non-critical)
current threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmpsr/w
Textual Convention: MilliAmps Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.21
outletCurrentUpperCritical
The value of the upper critical current
threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmpsr/w
Textual Convention: MilliAmps Unsigned32
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.23
.1.3.6.1.4.1.534.6.6.6.2.2 · 1 row entry · 11 columns
A list of temperature sensor entries. The number of
entries is given by the value of tempSensorCount.
tempSensorEntry entry .1.3.6.1.4.1.534.6.6.6.2.2.1
An entry containing sensor reading and threshold
settings for a particular temperature sensor.
Indexes
tempSensorIndex
Column Syntax OID
tempSensorIndex
A unique value for each temperature sensor. Its value
ranges between 1 and tempSensorCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.2.2.1.1
tempSensorLabel
A settable human-readable label for the external temperature
sensor. One possible use for this label is to convey sensor
location.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.534.6.6.6.2.2.1.2
temperature
The value of the external temperature sensor reported
in degrees celsius.
DegreesCelsius
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.3
tempLowerWarning
The value of the lower warning (non-critical) threshold.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.4
tempUpperWarning
The value of the upper warning (non-critical) threshold.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.5
tempLowerCritical
The value of the lower critical threshold.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.6
tempUpperCritical
The value of the upper critical threshold.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.7
tempLowerWarningReset
The value of the lower warning (non-critical) reset/hysteresis value.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.8
tempUpperWarningReset
The value of the upper warning (non-critical) reset/hysteresis value.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.9
tempLowerCriticalReset
The value of the lower critical reset/hysteresis value.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.10
tempUpperCriticalReset
The value of the upper critical reset/hysteresis value.
DegreesCelsiusr/w
Textual Convention: DegreesCelsius Unsigned32
.1.3.6.1.4.1.534.6.6.6.2.2.1.11
.1.3.6.1.4.1.534.6.6.6.2.4 · 1 row entry · 11 columns
A list of humidity sensor entries. The number of
entries is given by the value of humiditySensorCount.
humiditySensorEntry entry .1.3.6.1.4.1.534.6.6.6.2.4.1
An entry containing sensor reading and threshold
settings for a particular humidity sensor.
Indexes
humiditySensorIndex
Column Syntax OID
humiditySensorIndex
A unique value for each humidity sensor. Its value
ranges between 1 and humiditySensorCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.2.4.1.1
humiditySensorLabel
A settable human-readable label for the external humidity
sensor. One possible use for this label is to convey sensor
location.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.534.6.6.6.2.4.1.2
humidity
The value of the external humidity sensor reported
as relative humidity (a percentage).
RelativeHumidity
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.3
humidityLowerWarning
The value of the lower warning (non-critical) threshold.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.4
humidityUpperWarning
The value of the upper warning (non-critical) threshold.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.5
humidityLowerCritical
The value of the lower critical threshold.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.6
humidityUpperCritical
The value of the upper critical threshold.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.7
humidityLowerWarningReset
The value of the lower warning (non-critical) reset/hysteresis value.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.8
humidityUpperWarningReset
The value of the upper warning (non-critical) reset/hysteresis value.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.9
humidityLowerCriticalReset
The value of the lower critical reset/hysteresis value.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.10
humidityUpperCriticalReset
The value of the upper critical reset/hysteresis value.
RelativeHumidityr/w
Textual Convention: RelativeHumidity Unsigned32
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.11