outletActivePower
EATON-EPDU-MA-MIB ·
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.7
Object
column
Watts
A unique value for the active power sensor attached to the outlet. This value is reported in Watts.
Context
- MIB
- EATON-EPDU-MA-MIB
- OID
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.7- Type
- column
- Access
- readonly
- Status
- current
- Parent
- outletEntry
- Table
- outletTable
- Siblings
- 10
Syntax
Watts
- Source
- Watts
- Base type
Unsigned32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| outletIndex A unique value for each outlet. Its value
ranges between 1 and the value of outletCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.1 |
| outletLabel A textual string containing information
about the outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.2 |
| outletCurrentUpperWarning The value of the upper warning (non-critical)
current threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp) | column | MilliAmps | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.21 |
| outletCurrentUpperCritical The value of the upper critical current
threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp) | column | MilliAmps | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.23 |
| outletOperationalState A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet | column | Enumeration | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.3 |
| outletCurrent A unique value for the current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp) | column | MilliAmps | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.4 |
| outletMaxCurrent A unique value for the max. current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp) | column | MilliAmps | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.5 |
| outletVoltage A unique value for the voltage sensor
attached to the outlet.This value is
reported in millivolts (1/1000th of a volt) | column | MilliVolts | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.6 |
| outletApparentPower A unique value for the apparent power sensor
attached to the outlet. This value is
reported in Volt-Amps | column | VoltAmps | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.8 |
| outletPowerFactor A unique value for the power factor
of the outlet. The reading represents a
percentage in the range of 0% to 100%. | column | PowerFactorPercentage | .1.3.6.1.4.1.534.6.6.6.1.2.2.1.9 |