overrideHeatSP

THERMOSTAT-MIB · .1.3.6.1.4.1.57702.1.3.19

Object

scalar r/w degreesInteger32
Heat setpoint value during an override. It must be at least 2 F or 1 C lower
than the cool setpoint counterpart overrideCoolSP, and also within the allowed
min max limits hvacHeatSPLowLimit, and hvacHeatSPHighLimit. Writing this value
will attempt to start an override if allowed (see hvacOverrideTime) or modifies
the setpoint of an already running override. If starting an override, this will
do it whether operating in manual mode or not, and also it will use the current
cool setpoint as the initial override cool setpoint counterpart.

Context

MIB
THERMOSTAT-MIB
OID
.1.3.6.1.4.1.57702.1.3.19
Type
scalar
Access
readwrite
Status
current
Units
degrees
Parent
control
Groups
1

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::overrideHeatSP.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'THERMOSTAT-MIB::overrideHeatSP'

Syntax

degreesInteger32

Values & Constraints

Object Constraints
range: 3-88

Conformance