THERMOSTAT-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
2
Rows
2
Columns
14
ipv4TrapTable
table.1.3.6.1.4.1.57702.1.2.1
·
1 row entry
·
4 columns
Uses the nthermo variant from
Command help
/opt/observium/mibs/nthermo.
Walk ipv4TrapTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::ipv4TrapTable'
Trap table for IPv4 Destination address configuration
Single trap entry containing trap receiver info.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Index of trap receiver
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.57702.1.2.1.1.1 |
||||
|
Indicates if this trap entry is enabled or not.
|
TrapEnabledTyper/w Type Values:
Description: Enabled status for IPv4 traps |
.1.3.6.1.4.1.57702.1.2.1.1.2 |
||||
|
Trap receiver IP address
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.57702.1.2.1.1.3 |
||||
|
Trap community to be used by agent to send trap
|
SNMPv2-TCDisplayStringr/w Constraints: range: 0-32Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.57702.1.2.1.1.4 |
scheduleTable
table.1.3.6.1.4.1.57702.1.3.120
·
1 row entry
·
10 columns
Uses the nthermo variant from
Command help
/opt/observium/mibs/nthermo.
Walk scheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::scheduleTable'
Table of thermostat schedule entries.
An entry in the thermostat schedule table.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index of the schedule accounting for weekday and period
|
ScheduleIndexType Type Constraints: range: 0..28Description: A combined index representing weekday and period. Calculated as: (weekday * 4) + period Where weekday is 0-6 (Monday-Sunday) and period is 0-3. |
.1.3.6.1.4.1.57702.1.3.120.1.1 |
||||||||||||||
|
Day of the week from monday(1) though sunday(7)
|
ScheduleWeekdayType Type Values:
Description: Day of the week from monday though sunday |
.1.3.6.1.4.1.57702.1.3.120.1.2 |
||||||||||||||
|
Period within the day, from 1 to 4
|
SchedulePeriodType Type Values:
Description: Period within each day, 1 through 4, typically maps as morning(1), day(2), evening(3), and night(4), but there is no restriction in how they are used. |
.1.3.6.1.4.1.57702.1.3.120.1.3 |
||||||||||||||
|
Indicates whether this schedule entry is enabled or disabled.
Note schedules will not run regardless if the thermostat is in Manual Operation (see manualOperation). |
EnabledTyper/w Type Values:
Description: Indicates whether something is enabled or not |
.1.3.6.1.4.1.57702.1.3.120.1.4 |
||||||||||||||
|
The time of day for this schedule entry, in minutes since midnight.
|
minutesInteger32r/w Constraints: range: 0-1439 |
.1.3.6.1.4.1.57702.1.3.120.1.5 |
||||||||||||||
|
The cool temperature setpoint for this schedule entry. it must be at
least 2 F or 1 C higher than the heat setpoint counterpart scheduleHeatSetpoint, and also within the allowed min max limits hvacCoolSPLowLimit, and hv… |
degreesInteger32r/w Constraints: range: 16-108 |
.1.3.6.1.4.1.57702.1.3.120.1.6 |
||||||||||||||
|
The heat temperature setpoint for this schedule entry. it must be at
least 2 F or 1 C lower than the cool setpoint counterpart scheduleCoolSetpoint, and also within the allowed min max limits hvacHeatSPLowLimit, and hva… |
degreesInteger32r/w Constraints: range: 3-88 |
.1.3.6.1.4.1.57702.1.3.120.1.7 |
||||||||||||||
|
Whether to consider the space occupied or not when this particular
schedule entry is active. |
OccupiedTyper/w Type Values:
Description: Indicates the occupancy state |
.1.3.6.1.4.1.57702.1.3.120.1.8 |
||||||||||||||
|
The system mode to set active for this schedule entry. Only valid modes depending
on the HVAC configuration of the system will be allowed. |
ModeTyper/w Type Values:
Description: Thermostat system mode |
.1.3.6.1.4.1.57702.1.3.120.1.9 |
||||||||||||||
|
Only auto and on values are supported for schedules, even on multi-speed
fan systems. |
FanTyper/w Type Values:
Description: Fan operation mode, on and fan1 are the same, recirc is intermitent fan. Not all modes are writable in all circumstances except for auto and on. |
.1.3.6.1.4.1.57702.1.3.120.1.10 |