overrideCoolSP

THERMOSTAT-MIB · .1.3.6.1.4.1.57702.1.3.18

Object

scalar r/w degreesInteger32
Cool setpoint value during an override. It must be at least 2 F or 1 C higher
than the heat setpoint counterpart overrideHeatSP, and also within the allowed
min max limits hvacCoolSPLowLimit, and hvacCoolSPHighLimit. Writing this value
will attempt to start an override if allowed (see hvacOverrideTime) or modifies
the setpoint of an already running override. If starting an override, this will
do it whether operating in manual mode or not, and also it will use the current
heat setpoint as the initial override heat setpoint counterpart.

Context

MIB
THERMOSTAT-MIB
OID
.1.3.6.1.4.1.57702.1.3.18
Type
scalar
Access
readwrite
Status
current
Units
degrees
Parent
control
Groups
1

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::overrideCoolSP.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'THERMOSTAT-MIB::overrideCoolSP'

Syntax

degreesInteger32

Values & Constraints

Object Constraints
range: 16-108

Conformance