basOutdoorTemp
THERMOSTAT-MIB ·
.1.3.6.1.4.1.57702.1.3.78
Object
scalar r/w
degreesInteger32
Writable version of outdoorTemp in F or C depending on SNMP scale configuration. If data is written periodically within a 30 minute window, it will be taken as the source for outdoor temperature, as long as no external outdoor temperature sensor is enabled. The origin priority for the data is, external sensor if enabled, BAS data point basOutdoorTemp when kept updated periodically, and finally outdoor weather service from the cloud if enabled. A value of 2147483647 indicates an invalid reading.
Context
- MIB
- THERMOSTAT-MIB
- OID
.1.3.6.1.4.1.57702.1.3.78- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- degrees
- Parent
- control
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::basOutdoorTemp.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'THERMOSTAT-MIB::basOutdoorTemp'
Syntax
degreesInteger32
Values & Constraints
Object Constraints
range: -54-118
Conformance
Member of