basOutdoorTemp

THERMOSTAT-MIB · .1.3.6.1.4.1.57702.1.3.78

Object

scalar r/w degreesInteger32
Writable version of outdoorTemp in F or C depending
on SNMP scale configuration. If data is written
periodically within a 30 minute window, it will be
taken as the source for outdoor temperature, as long
as no external outdoor temperature sensor is enabled.
The origin priority for the data is, external sensor
if enabled, BAS data point basOutdoorTemp when kept
updated periodically, and finally outdoor weather
service from the cloud if enabled. A value of
2147483647 indicates an invalid reading.

Context

MIB
THERMOSTAT-MIB
OID
.1.3.6.1.4.1.57702.1.3.78
Type
scalar
Access
readwrite
Status
current
Units
degrees
Parent
control
Groups
1

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'THERMOSTAT-MIB::basOutdoorTemp.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'THERMOSTAT-MIB' -M '/opt/observium/mibs/nthermo:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'THERMOSTAT-MIB::basOutdoorTemp'

Syntax

degreesInteger32

Values & Constraints

Object Constraints
range: -54-118

Conformance