infeedCapacity

OBS ✓
Sentry3-MIB · .1.3.6.1.4.1.1718.3.2.2.1.10

Object

column AmpsInteger32
The load capacity of the input feed line.  A non-negative
value indicates the maximum load in Amps.  A negative
value indicates that the capacity was not available.
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in: Sensors
Explore Observium network monitoring

Context

MIB
Sentry3-MIB
OID
.1.3.6.1.4.1.1718.3.2.2.1.10
Type
column
Access
readonly
Status
current
Units
Amps
Parent
infeedEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::infeedCapacity'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::infeedCapacity.<towerIndex>.<infeedIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'Sentry3-MIB::infeedCapacity'

Syntax

AmpsInteger32

Values & Constraints

Object Constraints
range: -1-600 range: 4-4