Sentry3-MIB
Monitored by Observium This is the MIB module for the third generation of the
Sentry product family. This includes the Sentry Remote
Power Manager (RPM), Sentry Power Distribution Unit (PDU),
Sentry Environmental Monitor (EM), Sentry Smart and
Switched Cabinet Distribution Unit (CDU), and Sentry
Switched -48 VDC.
Observium actively monitors this MIB
Observium uses this MIB in discovery or polling workflows on applicable devices.
Device identity
Sensors
Explore Observium network monitoring
- Source file
Sentry3-MIB- Last revised
- Identity
sentry3- Base OID
1.3.6.1.4.1.1718.3
Imported Objects
| SNMPv2-SMI | enterprises MODULE-IDENTITY (no object page) NOTIFICATION-TYPE (no object page) OBJECT-TYPE (no object page) |
| SNMPv2-TC | DisplayString |
Net-SNMP examples using the sentry MIB directory Show commands
These commands use the standard Observium installation path and load the selected MIB variant before the RFC and Net-SNMP directories.
Translate the module identity
/usr/bin/snmptranslate -Pud -Ir -On -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'Sentry3-MIB::sentry3'
Walk the MIB subtree
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::sentry3'
Objects (139)
23 directly used by Observium
Showing 139 of 139 objects
Object legend
Object type
Icons distinguish tables, entry rows, columns, scalars, and structural nodes.
SNMPv2-TCTruthValue
Syntax
Blue badges identify the value syntax. Connected badges read as defining module and convention.
IF-MIBifIndex
Table index
Green identifies an index object; yellow names its module when the index is defined elsewhere.
r/w
deprecated
obsolete
Access and status
r/w means read-write. Grey labels mark definitions retained for compatibility.
OBS ✓
Observium use
The indicator appears only when Observium directly references that object.
ifOperStatus
.1.3.6.1.2.1…
Names and OIDs
Object names link to their detail pages. Hover or focus a linked name or badge for available definition details.
.1.3.6.1.4.1.1718 |
||
|
|
.1.3.6.1.4.1.1718.3 |
|
.1.3.6.1.4.1.1718.3.1 |
||
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.1.1 |
|
hundredthsInteger32
|
.1.3.6.1.4.1.1718.3.1.10 |
|
|
Bits
|
.1.3.6.1.4.1.1718.3.1.11 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.1.12 |
.1.3.6.1.4.1.1718.3.1.13 |
||
|
secondsInteger32
|
.1.3.6.1.4.1.1718.3.1.14 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.1.15 |
|
|
OctetStringAPOLLO-MIBapolloShelfIndex
|
.1.3.6.1.4.1.1718.3.1.2 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.1.3 |
|
Integer32
|
.1.3.6.1.4.1.1718.3.1.4 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.1.5 |
|
|
WattsInteger32
|
.1.3.6.1.4.1.1718.3.1.6 |
|
|
|
tenth area unitsInteger32
|
.1.3.6.1.4.1.1718.3.1.7 |
|
Watts per area unitInteger32
|
.1.3.6.1.4.1.1718.3.1.8 |
|
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.1.9 |
.1.3.6.1.4.1.1718.3.100 |
||
.1.3.6.1.4.1.1718.3.100.0 |
||
.1.3.6.1.4.1.1718.3.2 |
||
.1.3.6.1.4.1.1718.3.2.1 |
||
.1.3.6.1.4.1.1718.3.2.1.1 |
||
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.1.1.1 |
|
|
tenth percentageInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.10 |
|
|
WattsInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.11 |
|
|
Volt-AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.12 |
|
|
hundredthsInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.13 |
|
|
Kilowatt-HoursInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.14 |
|
|
HertzInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.15 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.1.1.2 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.1.1.3 |
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.1.1.4 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.1.1.5 |
|
|
OctetStringAPOLLO-MIBapolloIfIndex
|
.1.3.6.1.4.1.1718.3.2.1.1.6 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.1.1.7 |
|
|
Bits
|
.1.3.6.1.4.1.1718.3.2.1.1.8 |
|
|
Volt-AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.1.1.9 |
|
.1.3.6.1.4.1.1718.3.2.2 |
||
|
|
.1.3.6.1.4.1.1718.3.2.2.1 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.2.1.1 |
|
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.10 |
|
|
tenth VoltsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.11 |
|
|
WattsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.12 |
|
Volt-AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.13 |
|
|
hundredthsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.14 |
|
|
tenthsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.15 |
|
|
tenth Kilowatt-HoursInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.16 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.2.1.17 |
|
|
tenth VoltsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.18 |
|
|
hundredth AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.19 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.2.1.2 |
|
|
tenth percentageInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.20 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.2.1.21 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.2.1.22 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.2.1.23 |
|
|
Volt-AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.24 |
|
|
tenth percentageInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.25 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.2.1.3 |
|
Bits
|
.1.3.6.1.4.1.1718.3.2.2.1.4 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.2.1.5 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.2.1.6 |
|
|
|
hundredth AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.7 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.2.1.8 |
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.2.1.9 |
|
.1.3.6.1.4.1.1718.3.2.3 |
||
|
|
.1.3.6.1.4.1.1718.3.2.3.1 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.3.1.1 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.3.1.10 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.3.1.11 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.12 |
|
|
tenth VoltsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.13 |
|
|
WattsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.14 |
|
|
Volt-AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.15 |
|
|
hundredthsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.16 |
|
|
tenthsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.17 |
|
|
Watt-HoursInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.18 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.3.1.19 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.3.1.2 |
|
|
secondsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.20 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.3.1.3 |
|
Bits
|
.1.3.6.1.4.1.1718.3.2.3.1.4 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.3.1.5 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.3.1.6 |
|
|
|
hundredth AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.7 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.8 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.3.1.9 |
.1.3.6.1.4.1.1718.3.2.4 |
||
.1.3.6.1.4.1.1718.3.2.4.1 |
||
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.1 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.10 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.11 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.12 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.13 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.4.1.2 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.4.1.3 |
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.4.1.4 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.4.1.5 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.4.1.6 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.4.1.7 |
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.4.1.8 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.4.1.9 |
|
.1.3.6.1.4.1.1718.3.2.5 |
||
|
|
.1.3.6.1.4.1.1718.3.2.5.1 |
|
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.5.1.1 |
|
|
percentage relative humidityInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.10 |
|
|
|
percentage relative humidityInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.11 |
|
|
percentage relative humidityInteger32APOLLO-MIBapolloEtherStatsEgPerPortCosIfIndexAPOLLO-MIBapolloEtherStatsEgPerPortCosCosNum
|
.1.3.6.1.4.1.1718.3.2.5.1.12 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.5.1.13 |
|
degreesInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.14 |
|
|
percentage relative humidityInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.15 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.5.1.2 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.5.1.3 |
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.5.1.4 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.5.1.5 |
|
|
|
tenth degreesInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.6 |
|
|
degreesInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.7 |
|
|
degreesInteger32
|
.1.3.6.1.4.1.1718.3.2.5.1.8 |
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.5.1.9 |
|
.1.3.6.1.4.1.1718.3.2.6 |
||
.1.3.6.1.4.1.1718.3.2.6.1 |
||
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.6.1.1 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.6.1.2 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.6.1.3 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.6.1.4 |
|
.1.3.6.1.4.1.1718.3.2.7 |
||
.1.3.6.1.4.1.1718.3.2.7.1 |
||
|
Integer32
|
.1.3.6.1.4.1.1718.3.2.7.1.1 |
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.7.1.2 |
|
|
|
OctetString
|
.1.3.6.1.4.1.1718.3.2.7.1.3 |
|
Bits
|
.1.3.6.1.4.1.1718.3.2.7.1.4 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.7.1.5 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.2.7.1.6 |
|
|
hundredth AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.7.1.7 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.7.1.8 |
|
|
AmpsInteger32
|
.1.3.6.1.4.1.1718.3.2.7.1.9 |
|
.1.3.6.1.4.1.1718.3.99 |
||
|
OctetString
|
.1.3.6.1.4.1.1718.3.99.1 |
|
|
Enumeration
|
.1.3.6.1.4.1.1718.3.99.2 |
Dependencies (2) 2 direct Show tree and compile order Hide dependency details
Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.
Dependency tree
Dependency-first compile order
- SNMPv2-SMIrfc
- SNMPv2-TCrfc
- Sentry3-MIBsentryselected
Notifications / Traps (15)
| Name | OID | Description |
|---|---|---|
.1.3.6.1.4.1.1718.3.100.0.1 |
Tower status event. If enabled, this trap is sent when the
towerStatus indicates an error state ('noComm', 'fanFail', 'overTemp', 'nvmFail', or 'outOfBalance'). This trap is repeated periodically while the towerStatus remains in an error state. If the towerStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error towerStatus, and then stops being repeated. While the towerStatus indicates a 'noComm' error state, all status and load traps are suppressed for input feeds and outlets on the tower. |
|
.1.3.6.1.4.1.1718.3.100.0.10 |
Temperature/humidity sensor status event. If enabled, this
trap is sent when the tempHumidSensorStatus indicates an error state ('lost'). This trap is repeated periodically while the tempHumidSensorStatus remains in an error state. If the tempHumidSensorStatus returns to a non-error state ('found'), this trap is sent once more with the non-error tempHumidSensorStatus, and then stops being repeated. While the tempHumidSensorStatus indicates an error state, all temperature and humidity status traps are suppressed for the temperature/humidity sensor. |
|
.1.3.6.1.4.1.1718.3.100.0.11 |
Temperature/humidity sensor temperature event. If enabled,
this trap is sent when the tempHumidSensorTempStatus indicates an error state ('tempLow' or 'tempHigh'). This trap is repeated periodically while the tempHumidSensorTempStatus remains in an error state. If the tempHumidSensorTempStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorTempStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.12 |
Temperature/humidity sensor humidity event. If enabled,
this trap is sent when the tempHumidSensorHumidStatus indicates an error state ('humidLow' or 'humidHigh'). This trap is repeated periodically while the tempHumidSensorHumidStatus remains in an error state. If the tempHumidSensorHumidStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error tempHumidSensorHumidStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.13 |
Contact closure event. If enabled, this trap is sent when
the contactClosureStatus indicates an error state ('alarm'). This trap is repeated periodically while the contactClosureStatus remains in an error state. If the contactClosureStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error contactClosureStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.14 |
Branch status event. If enabled, this trap is sent when
the branchStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the branchStatus remains in an error state. If the branchStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error branchStatus, and then stops being repeated. While the branchStatus indicates an error state, load traps are suppressed for the branch. |
|
.1.3.6.1.4.1.1718.3.100.0.15 |
Branch load event. If enabled, this trap is sent when
the branchLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the branchLoadStatus remains in an error state. If the branchLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error branchLoadStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.2 |
Input feed status event. If enabled, this trap is sent when
the infeedStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the infeedStatus remains in an error state. If the infeedStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error infeedStatus, and then stops being repeated. While the infeedStatus indicates an error state, load traps are suppressed for the input feed, and, if the infeedCapabilities 'failSafe' bit is FALSE, all status and load traps are suppressed for outlets on the input feed. |
|
.1.3.6.1.4.1.1718.3.100.0.3 |
Input feed load event. If enabled, this trap is sent when
the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the infeedLoadStatus remains in an error state. If the infeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error infeedLoadStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.4 |
Outlet status event. If enabled, this trap is sent when the
outletStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is repeated periodically while the outletStatus remains in an error state. If the outletStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error outletStatus, and then stops being repeated. While the outletStatus indicates an error state, load traps are suppressed for the outlet. |
|
.1.3.6.1.4.1.1718.3.100.0.5 |
Outlet load event. If enabled, this trap is sent when the
outletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the outletLoadStatus remains in an error state. If the outletLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error outletLoadStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.6 |
Outlet on/off change event. If enabled, this trap is sent
when the outletStatus changes from any 'on' state ('on', 'onWait', 'onError', or 'onFuse') to any 'off' state ('off', 'offWait', 'offError', or 'offFuse'), and vice-versa. |
|
.1.3.6.1.4.1.1718.3.100.0.7 |
Environmental monitor status event. If enabled, this trap
is sent when the envMonStatus indicates an error state ('noComm'). This trap is repeated periodically while the envMonStatus remains in an error state. If the envMonStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonStatus, and then stops being repeated. While the envMonStatus indicates an error state, all status traps are suppressed for the water sensor, ADC, temperature/ humidity sensors, and contact closures on the environmental monitor. |
|
.1.3.6.1.4.1.1718.3.100.0.8 |
Environmental monitor water sensor event. If enabled, this
trap is sent when the envMonWaterSensorStatus indicates an error state ('alarm'). This trap is repeated periodically while the envMonWaterSensorStatus remains in an error state. If the envMonWaterSensorStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonWaterSensorStatus, and then stops being repeated. |
|
.1.3.6.1.4.1.1718.3.100.0.9 |
Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the envMonADCStatus remains in an error state. If the envMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error envMonADCStatus, and then stops being repeated. |