Sentry3-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
101
towerTable
table.1.3.6.1.4.1.1718.3.2.1
·
1 row entry
·
15 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk towerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::towerTable'
A table of towers.
Row definition for the tower table.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the tower table.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.1.1.1 |
||||||||||||
|
The ID of the tower.
|
OctetString Constraints: range: 1-1 |
.1.3.6.1.4.1.1718.3.2.1.1.2 |
||||||||||||
|
The name of the tower.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.1.1.3 |
||||||||||||
|
The operational status of the tower.
|
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.1.1.4 |
||||||||||||
|
The number of input feeds on the tower.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.1.1.5 |
||||||||||||
|
The product serial number of the tower.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.1718.3.2.1.1.6 |
||||||||||||
|
The model number of the tower.
|
OctetString Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.1.1.7 |
||||||||||||
|
The capabilities of the tower.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.1.1.8 |
||||||||||||
|
The total apparent power capacity of the tower circuit.
A non-negative value indicates the maximum total apparent power in Volt-Amps. A negative value indicates that the total apparent power capacity was not available. |
Volt-AmpsInteger32 Constraints: range: -1-50000 |
.1.3.6.1.4.1.1718.3.2.1.1.9 |
||||||||||||
|
The used percentage of the tower circuit total apparent power
capacity (towerApparentPower / towerVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates… |
tenth percentageInteger32 Constraints: range: -1-1500 |
.1.3.6.1.4.1.1718.3.2.1.1.10 |
||||||||||||
|
The total active power consumption of the tower circuit.
A non-negative value indicates the total active power consumption in Watts. A negative value indicates that the total active power consumption was not available. |
WattsInteger32 Constraints: range: -1-50000 |
.1.3.6.1.4.1.1718.3.2.1.1.11 |
||||||||||||
|
The total apparent power consumption of the tower circuit.
A non-negative value indicates the total apparent power consumption in Volt-Amps. A negative value indicates that the total apparent power consumption was not … |
Volt-AmpsInteger32 Constraints: range: -1-50000range: 0-255 |
.1.3.6.1.4.1.1718.3.2.1.1.12 |
||||||||||||
|
The overall power factor of the tower circuit. A non-
negative value indicates the overall power factor in hundredths. A negative value indicates that the overall power factor was not able to be measured. |
hundredthsInteger32 Constraints: range: -1-100range: 0-255 |
.1.3.6.1.4.1.1718.3.2.1.1.13 |
||||||||||||
|
The total energy consumption of the tower circuit. A non-
negative value indicates the total energy consumption in Kilowatt-Hours. A negative value indicates that the total energy consumption was not available. |
Kilowatt-HoursInteger32 Constraints: range: -1-2147483647 |
.1.3.6.1.4.1.1718.3.2.1.1.14 |
||||||||||||
|
The frequency of the input feed line voltage. A non-
negative value indicates the frequency in Hertz. A negative value indicates that the frequency was not available. |
HertzInteger32 Constraints: range: -1-60 |
.1.3.6.1.4.1.1718.3.2.1.1.15 |
infeedTable
table.1.3.6.1.4.1.1718.3.2.2
·
1 row entry
·
25 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk infeedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::infeedTable'
A table of input feeds.
Row definition for the input feed table.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the input feed table.
|
Integer32 Constraints: range: 0-4range: 0-16777215 |
.1.3.6.1.4.1.1718.3.2.2.1.1 |
||||||||||||||||||||
|
The ID of the input feed.
|
OctetString Constraints: range: 2-2range: 0-255 |
.1.3.6.1.4.1.1718.3.2.2.1.2 |
||||||||||||||||||||
|
The name of the input feed.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.2.1.3 |
||||||||||||||||||||
|
The capabilities of the input feed.
|
Bits Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.4 |
||||||||||||||||||||
|
The status of the input feed line. If the infeedCapabilities
'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the input feed. If the infeedCapabilities 'onSense' bit is FALS… |
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.5 |
||||||||||||||||||||
|
The status of the load measured on the input feed line. If
the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the infeedCapabilities 'loadSense' bit is FALSE, then only the 'norma… |
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.6 |
||||||||||||||||||||
|
The load measured on the input feed line. A non-negative
value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. |
hundredth AmpsInteger32 Constraints: range: -1-60000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.7 |
||||||||||||||||||||
|
The load high threshold value of the input feed line in Amps.
|
AmpsInteger32r/w Constraints: range: 0-600range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.8 |
||||||||||||||||||||
|
The number of controlled and/or monitored outlets on the
input feed. |
Integer32 Constraints: range: 0-64range: 0-16777215 |
.1.3.6.1.4.1.1718.3.2.2.1.9 |
||||||||||||||||||||
|
The load capacity of the input feed line. A non-negative
value indicates the maximum load in Amps. A negative value indicates that the capacity was not available. |
AmpsInteger32 Constraints: range: -1-600range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.10 |
||||||||||||||||||||
|
The line-to-line voltage of the input feed. A non-negative
value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available. |
tenth VoltsInteger32 Constraints: range: -1-4800range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.11 |
||||||||||||||||||||
|
The active power consumption of the input feed phase. A non-
negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available. |
WattsInteger32 Constraints: range: -1-25000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.12 |
||||||||||||||||||||
|
The apparent power consumption of the input feed phase. A
non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available. |
Volt-AmpsInteger32 Constraints: range: -1-25000range: 0-16777215 |
.1.3.6.1.4.1.1718.3.2.2.1.13 |
||||||||||||||||||||
|
The power factor of the input feed phase. A non-negative
value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured. |
hundredthsInteger32 Constraints: range: -1-100range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.14 |
||||||||||||||||||||
|
The crest factor for the load of the input feed phase. A
non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured. |
tenthsInteger32 Constraints: range: -1-1000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.15 |
||||||||||||||||||||
|
The energy consumption of the input feed phase. A non-
negative value indicates the energy consumption in tenths of Kilowatt-Hours. A negative value indicates that the energy consumption was not available. |
tenth Kilowatt-HoursInteger32 Constraints: range: -1-2147483647range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.16 |
||||||||||||||||||||
|
The characterization of the phase relation between the
voltage and current of the input feed phase. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.2.1.17 |
||||||||||||||||||||
|
The voltage measured for the input feed phase. A non-
negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available. |
tenth VoltsInteger32 Constraints: range: -1-2640range: 0-255 |
.1.3.6.1.4.1.1718.3.2.2.1.18 |
||||||||||||||||||||
|
The current measured for the input feed phase. A non-
negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. |
hundredth AmpsInteger32 Constraints: range: -1-25500range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.19 |
||||||||||||||||||||
|
The used percentage of the input feed line load capacity
(infeedLoadValue / infeedCapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentag… |
tenth percentageInteger32 Constraints: range: -1-1500range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.20 |
||||||||||||||||||||
|
The ID of the input feed line.
|
OctetString Constraints: range: 0-4range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.21 |
||||||||||||||||||||
|
The line-to-line ID of the input feed.
|
OctetString Constraints: range: 0-7range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.22 |
||||||||||||||||||||
|
The ID of the input feed phase.
|
OctetString Constraints: range: 0-6range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.23 |
||||||||||||||||||||
|
The apparent power capacity of the input feed circuit. A
non-negative value indicates the maximum apparent power in Volt-Amps. A negative value indicates that the apparent power capacity was not available. |
Volt-AmpsInteger32 Constraints: range: -1-25000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.24 |
||||||||||||||||||||
|
The used percentage of the input feed circuit apparent power
capacity (infeedApparentPower / infeedVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicate… |
tenth percentageInteger32 Constraints: range: -1-1500range: 4-4 |
.1.3.6.1.4.1.1718.3.2.2.1.25 |
outletTable
table.1.3.6.1.4.1.1718.3.2.3
·
1 row entry
·
20 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::outletTable'
A table of outlets.
Row definition for the outlet table.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the outlet table.
|
Integer32 Constraints: range: 0-64range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.1 |
||||||||||||||||||||||||||||||||||||
|
The ID of the outlet.
|
OctetString Constraints: range: 2-4range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.2 |
||||||||||||||||||||||||||||||||||||
|
The name of the outlet.
|
OctetStringr/w Constraints: range: 0-24range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.3 |
||||||||||||||||||||||||||||||||||||
|
The capabilities of the outlet.
|
Bits Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.4 |
||||||||||||||||||||||||||||||||||||
|
The status of the outlet. If the outletCapabilities
'onSense' bit is TRUE, then the state indicates the sensed state of the outlet, not a derived state, and 'offError' and 'onError' are supported to indicate a mismatch… |
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.5 |
||||||||||||||||||||||||||||||||||||
|
The status of the load measured on the outlet. If the
outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and '… |
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.6 |
||||||||||||||||||||||||||||||||||||
|
The load measured on the outlet. A non-negative value
indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. |
hundredth AmpsInteger32 Constraints: range: -1-25500range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.7 |
||||||||||||||||||||||||||||||||||||
|
The load low threshold value of the outlet in Amps.
|
AmpsInteger32r/w Constraints: range: 0-255range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.8 |
||||||||||||||||||||||||||||||||||||
|
The load high threshold value of the outlet in Amps.
|
AmpsInteger32r/w Constraints: range: 0-255range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.9 |
||||||||||||||||||||||||||||||||||||
|
The control state of the outlet. The supported states are
dependent upon the outletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported features of the firmware version. |
Enumeration Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.10 |
||||||||||||||||||||||||||||||||||||
|
An action to change the control state of the outlet. If
the outletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be used to change the control state of the outlet. If the outle… |
Enumerationr/w Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.11 |
||||||||||||||||||||||||||||||||||||
|
The load capacity of the outlet. A non-negative value
indicates the maximum load in Amps. A negative value indicates that the capacity was not available. |
AmpsInteger32 Constraints: range: -1-255range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.12 |
||||||||||||||||||||||||||||||||||||
|
The voltage of the outlet. A non-negative value indicates
the voltage in tenths of Volts. A negative value indicates that the voltage was not available. |
tenth VoltsInteger32 Constraints: range: -1-2640range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.13 |
||||||||||||||||||||||||||||||||||||
|
The active power consumption of the device plugged into the
outlet. A non-negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available. |
WattsInteger32 Constraints: range: -1-10000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.14 |
||||||||||||||||||||||||||||||||||||
|
The apparent power consumption of the device plugged into
the outlet. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not … |
Volt-AmpsInteger32 Constraints: range: -1-10000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.15 |
||||||||||||||||||||||||||||||||||||
|
The power factor of the device plugged into the outlet. A
non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured. |
hundredthsInteger32 Constraints: range: -1-100range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.16 |
||||||||||||||||||||||||||||||||||||
|
The crest factor for the load of the device plugged into the
outlet. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured. |
tenthsInteger32 Constraints: range: -1-1000range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.17 |
||||||||||||||||||||||||||||||||||||
|
The energy consumption of the device plugged into the outlet.
A non-negative value indicates the energy consumption in Watt-Hours. A negative value indicates that the energy consumption was not available. |
Watt-HoursInteger32 Constraints: range: -1-2147483647range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.18 |
||||||||||||||||||||||||||||||||||||
|
The wakeup state of the outlet.
|
Enumerationr/w Enumerated Values:
Constraints: range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.19 |
||||||||||||||||||||||||||||||||||||
|
The post-on delay of the outlet.
|
secondsInteger32r/w Constraints: range: 0-900range: 4-4 |
.1.3.6.1.4.1.1718.3.2.3.1.20 |
envMonTable
table.1.3.6.1.4.1.1718.3.2.4
·
1 row entry
·
13 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk envMonTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::envMonTable'
A table of environmental monitors.
Row definition for the environmental monitor table.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the environmental monitor table.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.4.1.1 |
||||||||||||
|
The ID of the environmental monitor.
|
OctetString Constraints: range: 1-1 |
.1.3.6.1.4.1.1718.3.2.4.1.2 |
||||||||||||
|
The name of the environmental monitor.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.4.1.3 |
||||||||||||
|
The operational status of the environmental monitor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.4.1.4 |
||||||||||||
|
The name of the water sensor.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.4.1.5 |
||||||||||||
|
The status of the water sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.4.1.6 |
||||||||||||
|
The name of the analog-to-digital converter.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.4.1.7 |
||||||||||||
|
The status of the analog-to-digital converter.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.4.1.8 |
||||||||||||
|
The 8-bit count value from the analog-to-digital converter.
A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates that a digital value was not able to be retrieved. |
Integer32 Constraints: range: -1-255 |
.1.3.6.1.4.1.1718.3.2.4.1.9 |
||||||||||||
|
The 8-bit count low threshold value of the analog-to-digital
converter. |
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.1718.3.2.4.1.10 |
||||||||||||
|
The 8-bit count high threshold value of the analog-to-digital
converter. |
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.1718.3.2.4.1.11 |
||||||||||||
|
The number of temperature/humidity sensors on the
environmental monitor. |
Integer32 Constraints: range: 0-2 |
.1.3.6.1.4.1.1718.3.2.4.1.12 |
||||||||||||
|
The number of contact closures on the environmental
monitor. |
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.4.1.13 |
tempHumidSensorTable
table.1.3.6.1.4.1.1718.3.2.5
·
1 row entry
·
15 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk tempHumidSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::tempHumidSensorTable'
A table of temperature/humidity sensors.
Row definition for the temperature/humidity sensor table.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the temperature/humidity sensor table.
|
Integer32 Constraints: range: 0-2 |
.1.3.6.1.4.1.1718.3.2.5.1.1 |
||||||||||||||||
|
The ID of the temperature/humidity sensor.
|
OctetString Constraints: range: 2-2 |
.1.3.6.1.4.1.1718.3.2.5.1.2 |
||||||||||||||||
|
The name of the temperature/humidity sensor.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.5.1.3 |
||||||||||||||||
|
The operational status of the temperature/humidity sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.5.1.4 |
||||||||||||||||
|
The status of the temperature sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.5.1.5 |
||||||||||||||||
|
The temperature measured by the sensor. A non-negative value
indicates the measured temperature in tenths of degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSe… |
tenth degreesInteger32 Constraints: range: -1-2540 |
.1.3.6.1.4.1.1718.3.2.5.1.6 |
||||||||||||||||
|
The temperature low threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is … |
degreesInteger32r/w Constraints: range: 0-254 |
.1.3.6.1.4.1.1718.3.2.5.1.7 |
||||||||||||||||
|
The temperature high threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is… |
degreesInteger32r/w Constraints: range: 0-254 |
.1.3.6.1.4.1.1718.3.2.5.1.8 |
||||||||||||||||
|
The status of the humidity sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.5.1.9 |
||||||||||||||||
|
The humidity measured by the sensor. A non-negative value
indicates the measured humidity in percentage relative humidity. A negative value indicates that a humidity value was not able to be measured. |
percentage relative humidityInteger32 Constraints: range: -1-100 |
.1.3.6.1.4.1.1718.3.2.5.1.10 |
||||||||||||||||
|
The humidity low threshold value of the sensor in percentage
relative humidity. |
percentage relative humidityInteger32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.1718.3.2.5.1.11 |
||||||||||||||||
|
The humidity low threshold value of the sensor in percentage
relative humidity. |
percentage relative humidityInteger32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.1718.3.2.5.1.12 |
||||||||||||||||
|
The scale used for temperature values. This is a global
setting for all temperature values in the system. If the agent does not support this object, then the temperature scale used is Celsius. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.5.1.13 |
||||||||||||||||
|
The temperature recovery delta (hysteresis) value of the
sensor in degrees, using the scale selected by tempHumidSensorTempScale. |
degreesInteger32r/w Constraints: range: 0-54range: 1-8 |
.1.3.6.1.4.1.1718.3.2.5.1.14 |
||||||||||||||||
|
The humidity recovery delta (hysteresis) value of the
sensor in percentage relative humidity. |
percentage relative humidityInteger32r/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1718.3.2.5.1.15 |
contactClosureTable
table.1.3.6.1.4.1.1718.3.2.6
·
1 row entry
·
4 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk contactClosureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::contactClosureTable'
A table of contact closures.
Row definition for the contact closure table.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Index for the contact closure table.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.6.1.1 |
||||||
|
The ID of the contact closure.
|
OctetString Constraints: range: 2-2 |
.1.3.6.1.4.1.1718.3.2.6.1.2 |
||||||
|
The name of the contact closure.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.6.1.3 |
||||||
|
The status of the contact closure.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.6.1.4 |
branchTable
table.1.3.6.1.4.1.1718.3.2.7
·
1 row entry
·
9 columns
Uses the sentry variant from
Command help
/opt/observium/mibs/sentry.
Walk branchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry3-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry3-MIB::branchTable'
A table of branches.
Row definition for the branch table.
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index for the branch table.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.1718.3.2.7.1.1 |
||||||||||||||||||||
|
The ID of the branch.
|
OctetString Constraints: range: 3-3 |
.1.3.6.1.4.1.1718.3.2.7.1.2 |
||||||||||||||||||||
|
The name of the branch.
|
OctetStringr/w Constraints: range: 0-24 |
.1.3.6.1.4.1.1718.3.2.7.1.3 |
||||||||||||||||||||
|
The capabilities of the branch.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.7.1.4 |
||||||||||||||||||||
|
The status of the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.7.1.5 |
||||||||||||||||||||
|
The status of the load measured on the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.1718.3.2.7.1.6 |
||||||||||||||||||||
|
The load measured on the branch. A non-negative
value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured. |
hundredth AmpsInteger32 Constraints: range: -1-4000 |
.1.3.6.1.4.1.1718.3.2.7.1.7 |
||||||||||||||||||||
|
The load high threshold value of the branch in Amps.
|
AmpsInteger32r/w Constraints: range: 0-40 |
.1.3.6.1.4.1.1718.3.2.7.1.8 |
||||||||||||||||||||
|
The load capacity of the branch. A non-negative value
indicates the maximum load in Amps. A negative value indicates that the capacity was not available. |
AmpsInteger32 Constraints: range: -1-40 |
.1.3.6.1.4.1.1718.3.2.7.1.9 |