VERTIV-V5-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
34
Rows
34
Columns
355

pduMainTable

table
.1.3.6.1.4.1.21239.5.2.3.1 · 1 row entry · 12 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduMainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduMainTable'
PDU general information
pduMainEntry row .1.3.6.1.4.1.21239.5.2.3.1.1
Entry in the pduMainTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.1.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.3.1.1.2
PDU name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.3
PDU label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.4
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.3.1.1.5
Current meter type:
0 = Wye
1 = Delta
Enumeration
Enumerated Values:
0wye
1delta
.1.3.6.1.4.1.21239.5.2.3.1.1.6
Total name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.7
Total label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.8
PDU total real power
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.9
PDU total apparent power
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.10
PDU total power factor
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.1.1.11
PDU total accumulated energy in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.1.1.12
.1.3.6.1.4.1.21239.5.2.3.2 · 1 row entry · 12 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduPhaseTable'
PDU phases information
pduPhaseEntry row .1.3.6.1.4.1.21239.5.2.3.2.1
Entry in the pduPhaseTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.2.1.1
PDU phase name (factory-assigned)
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.2.1.2
PDU phase label (user-defined)
OctetStringr/w
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.2.1.3
PDU phase voltage in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.2.1.4
PDU phase current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.2.1.8
Real power for phase in watts
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.12
Apparent power for phase in volt-amps
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.13
Power factor for phase
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.2.1.14
Accumulated energy for phase in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.2.1.15
Phase balance as percent
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.2.1.17
Current crest factor for phase, in hundredths
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.19
Tells if residual current was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.3.2.1.20
.1.3.6.1.4.1.21239.5.2.3.3 · 1 row entry · 11 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduBreakerTable'
PDU breaker information
pduBreakerEntry row .1.3.6.1.4.1.21239.5.2.3.3.1
Entry in the pduBreakerTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.3.1.1
PDU breaker name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.3.1.2
PDU breaker label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.3.1.3
PDU breaker current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.3.1.4
PDU breaker voltage in tenths of a volt. This object may not exist on
all platforms, due to hardware differences.
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.3.1.8
Real power for breaker in watts. This object may not exist on all
platforms, due to hardware differences.
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.3.1.12
Apparent power for breaker in volt-amps. This object may not exist on
all platforms, due to hardware differences.
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.3.1.13
Power factor for breaker. This object may not exist on all platforms,
due to hardware differences.
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.3.1.14
Accumulated energy for breaker in watt-hours. This object may not
exist on all platforms, due to hardware differences.
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.3.1.15
Tells if residual current was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.3.3.1.20
Tells if a loss of load was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.3.3.1.21

pduLineTable

table
.1.3.6.1.4.1.21239.5.2.3.4 · 1 row entry · 4 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduLineTable'
PDU line current information
pduLineEntry row .1.3.6.1.4.1.21239.5.2.3.4.1
Entry in the pduLineTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.4.1.1
PDU line name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.4.1.2
PDU line label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.4.1.3
PDU line current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.4.1.4
.1.3.6.1.4.1.21239.5.2.3.5 · 1 row entry · 13 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduOutletSwitchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduOutletSwitchTable'
Data, config and control for outlets with switching
pduOutletSwitchEntry row .1.3.6.1.4.1.21239.5.2.3.5.1
Entry in the pduOutletSwitchTable table: each entry contains an index
and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.5.1.1
PDU outlet name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.5.1.2
PDU outlet label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.5.1.3
Switch state of the outlet:
1 = Outlet is on
2 = Outlet is off
3 = Outlet is on, but will turn off after a delay
4 = Outlet is off, but will turn on after a delay
5 = Starting reboot cycle, outlet is on, but will go to …
Enumeration
Enumerated Values:
1on
2off
3on2off
4off2on
5rebootOn
6rebootOff
7unavailable
.1.3.6.1.4.1.21239.5.2.3.5.1.4
Tells if the outlet relay has failed. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.3.5.1.5
Used for manual control of the outlet. If the outlet is in manual
mode, this field can be set to one of the following values:
1 = Cancel pending operation
2 = Turn outlet on
3 = After delay (pduOutletSwitchOnDelay), tur…
Enumerationr/w
Enumerated Values:
1cancel
2on
3onAfterDelay
4off
5offAfterDelay
6reboot
7rebootAfterDelay
8none
.1.3.6.1.4.1.21239.5.2.3.5.1.6
Seconds until an outlet state change. The value of
pduOutletSwitchState tells what state the outlet will be set, after
the delay.
Integer32
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.7
Seconds to wait before powering on the outlet, during onAfterDelay(3)
operation. Changing this value has no effect on pending actions.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.8
Seconds to wait before powering off the outlet, during
offAfterDelay(5) operation. Changing this value has no effect on
pending actions.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.9
Seconds to wait before powering off the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.10
Seconds to hold the outlet off, before powering on the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.11
The outlet is set to this state during power-up. The action can be
have one the following values:
1 = Outlet will be turned on
2 = Outlet will stay off
3 = Outlet will be set to last known state
Enumerationr/w
Enumerated Values:
1on
2off
3last
.1.3.6.1.4.1.21239.5.2.3.5.1.12
Seconds to wait before setting the outlet to the
pduOutletSwitchPoaAction state. The delay starts at power-up.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.13
.1.3.6.1.4.1.21239.5.2.3.6 · 1 row entry · 11 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduOutletMeterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduOutletMeterTable'
Metering data for outlets that support this feature
pduOutletMeterEntry row .1.3.6.1.4.1.21239.5.2.3.6.1
Entry in the pduOutletMeterTable table: each entry contains an index
and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.6.1.1
PDU outlet name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.6.1.2
PDU outlet label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.6.1.3
PDU outlet voltage in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.6.1.4
PDU outlet current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.6.1.8
Real power for outlet in watts
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.12
Apparent power for outlet in volt-amps
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.13
Power factor for outlet
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.6.1.14
Accumulated energy for outlet in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.6.1.15
Used to reset energy. If read, the value is none(8). It can be set to
resetEnergy(1), which sets outlet energy to 0
Enumerationr/w
Enumerated Values:
1resetEnergy
8none
.1.3.6.1.4.1.21239.5.2.3.6.1.16
Current crest factor for outlet, in hundredths
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.19
.1.3.6.1.4.1.21239.5.2.3.7 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduResidualCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::pduResidualCurrentTable'
Residual current data for PDUs that support this feature
pduResidualCurrentEntry row .1.3.6.1.4.1.21239.5.2.3.7.1
Entry in the pduResidualCurrentTable table: each entry contains an
index and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.7.1.1
PDU residual current name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.7.1.2
PDU residual current label
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.7.1.3
PDU residual current aggregate value in milliamps
milliampsUnsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.3.7.1.4
PDU residual current DC value in milliamps
milliampsUnsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.3.7.1.5
.1.3.6.1.4.1.21239.5.2.4 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk tempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::tempSensorTable'
Remote Temperature (RT) sensor
tempSensorEntry row .1.3.6.1.4.1.21239.5.2.4.1
Entry in the tempSensorTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.4.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.4.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.4.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.4.1.4
Temperature in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.4.1.5
.1.3.6.1.4.1.21239.5.2.5 · 1 row entry · 8 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk airFlowSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::airFlowSensorTable'
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
airFlowSensorEntry row .1.3.6.1.4.1.21239.5.2.5.1
Entry in the airFlowSensorTable table: each entry contains an index
and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.5.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.5.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.5.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.5.1.4
Temperature reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.5
Airflow reading. Still air will be less than 20, while rushing air
will be around 100.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.6
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.7
Dewpoint reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.8
.1.3.6.1.4.1.21239.5.2.8 · 1 row entry · 14 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk t3hdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::t3hdSensorTable'
Remote Temperature x 3, Humidity and Dewpoint Sensor
t3hdSensorEntry row .1.3.6.1.4.1.21239.5.2.8.1
Entry in the t3hdSensorTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.8.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.8.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.4
Internal label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.5
Internal temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.6
Internal humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.8.1.7
Internal dewpoint in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.8
External A status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.9
External A label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.10
External A temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.11
External B status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.12
External B label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.13
External B temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.14
.1.3.6.1.4.1.21239.5.2.9 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk thdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::thdSensorTable'
Remote Temperature, Humidity, and Dewpoint (THD) Sensor
thdSensorEntry row .1.3.6.1.4.1.21239.5.2.9.1
Entry in the thdSensorTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.9.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.9.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.9.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.9.1.4
Temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.5
Humidity value
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.9.1.6
Dewpoint value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.7
.1.3.6.1.4.1.21239.5.2.11 · 1 row entry · 13 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk a2dSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::a2dSensorTable'
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
a2dSensorEntry row .1.3.6.1.4.1.21239.5.2.11.1
Entry in the a2dSensorTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.11.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.11.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.11.1.4
Analog measurement value, within either a user-defined or preset
range, depending on a2dSensorMode.
Integer32
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.5
For current/voltage modes, the analog value is given as a string. In
binary modes, the value is either a2dSensorLowLabel or
a2dSensorHighLabel, based on a2dSensorValue.
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.6
Binary modes have two states represented by the values 0 (low) or 1
(high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel.
Current and voltage modes provide a scaled value from a2dSensorMin to
a2dSensorMa…
Enumerationr/w
Enumerated Values:
1door
2powerFailure
3flood
4wscLeak
5wscFault
6smoke
7ivsNegGnd
8ivsPosGnd
9customVoltage
10customBinary
11customCurrent
.1.3.6.1.4.1.21239.5.2.11.1.7
The units for the analog value. If a2dSensorMode is customVoltage(9)
or customCurrent(11), then this field has a user-defined value.
Otherwise, the value is fixed, based on mode.
OctetStringr/w
Constraints:
range: 0-7
.1.3.6.1.4.1.21239.5.2.11.1.8
Minimum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.9
Maximum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.10
Label for 0 (low) binary value. This field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.11
Label for 1 (high) binary value. The field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.12
Label for the analog measurement
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.13
.1.3.6.1.4.1.21239.5.2.12 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk humiditySensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::humiditySensorTable'
Remote humidity sensor
humiditySensorEntry row .1.3.6.1.4.1.21239.5.2.12.1
Entry in the humiditySensorTable table: each entry contains an index
and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.12.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.12.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.12.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.12.1.4
Humidity value
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.12.1.5
.1.3.6.1.4.1.21239.5.2.13 · 1 row entry · 10 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk sn2dSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::sn2dSensorTable'
2 Door Switch Sensor (SN-2D)
sn2dSensorEntry row .1.3.6.1.4.1.21239.5.2.13.1
Entry in the sn2dSensorTable table: each entry contains an index and
other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.13.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.13.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.13.1.4
Door switch 1 label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.5
Door switch 1 state:
1 = open
2 = closed
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.21239.5.2.13.1.6
Door switch 1 state given as a string
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.7
Door switch 2 label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.8
Door switch 2 state:
1 = open
2 = closed
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.21239.5.2.13.1.9
Door switch 2 state given as a string
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.10

vrcMainTable

table
.1.3.6.1.4.1.21239.5.2.30.1.1 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcMainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcMainTable'
Table that contains general VRC information
vrcMainEntry row .1.3.6.1.4.1.21239.5.2.30.1.1.1
Entry in the vrcMainTable: each entry represents a VRC device
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.1.1.1
Serial number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.30.1.1.1.2
VRC name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.1.1.3
VRC label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.30.1.1.1.4
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.30.1.1.1.5
.1.3.6.1.4.1.21239.5.2.30.1.2 · 1 row entry · 29 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcMainPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcMainPtTable'
Table that contains general VRC status
vrcMainPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.2.1
Entry in the vrcMainPtTable: each entry contains status data for a VRC
device
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.2.1.1
VRC run state:
1 = on
2 = off
Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.21239.5.2.30.1.2.1.2
Eev opened value (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.2.1.3
Alarm numbers value
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.4
History alarm numbers value
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.5
Hp Abnormal record count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.6
Monitor baud rate:
1 = error
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
Enumeration
Enumerated Values:
1error
2baud1200
3baud2400
4baud4800
5baud9600
6baud19200
.1.3.6.1.4.1.21239.5.2.30.1.2.1.7
Monitor address
Integer32
Constraints:
range: 1-247
.1.3.6.1.4.1.21239.5.2.30.1.2.1.8
Lp status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.9
Filter maintenance reminder status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.10
Cooling flag
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.11
First on flag
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.12
New alarm flag
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.13
Common alarm output state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.14
High water input
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.15
High water alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.16
Water under floor alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.17
Software shutdown status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.18
Remote shutdown status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.19
Remote shutdown flag
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.20
Remote shutdown alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.21
Hmi shutdown flag
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.22
Low pressure alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.23
High pressure alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.24
Low pressure frequently alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.25
High pressure frequently alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.26
Low pressure sensor failure alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.27
High pressure sensor failure alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.28
Eev communication failure alarm status
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.2.1.29
.1.3.6.1.4.1.21239.5.2.30.1.3 · 1 row entry · 35 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcMainCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcMainCfgTable'
Table that contains general VRC configuration
vrcMainCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.3.1
Entry in the vrcMainCfgTable: each entry contains general config
fields for a VRC device
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.3.1.1
Model Selection:
1 = TMM-Local 220V 50/60HZ
2 = TMM-Global 208/230V 50/60HZ
3 = TMM-Global 120V 50/60HZ
4 = SC 220V 50/60HZ
5 = 0U 220V 50/60HZ
6 = SS 208/230V 50/60HZ
7 = SS 120V 50/60HZ
Enumerationr/w
Enumerated Values:
1tmLoc
2r035Ap
3r035Ak
4scLoc
5zeroULoc
6r035Ep
7r035Ek
.1.3.6.1.4.1.21239.5.2.30.1.3.1.2
System time - year
Integer32r/w
Constraints:
range: 2000-2099
.1.3.6.1.4.1.21239.5.2.30.1.3.1.3
System time - month
Integer32r/w
Constraints:
range: 1-12
.1.3.6.1.4.1.21239.5.2.30.1.3.1.4
System time - day
Integer32r/w
Constraints:
range: 1-31
.1.3.6.1.4.1.21239.5.2.30.1.3.1.5
System time - hour
Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.21239.5.2.30.1.3.1.6
System time - minutes
Integer32r/w
Constraints:
range: 0-59
.1.3.6.1.4.1.21239.5.2.30.1.3.1.7
System time - seconds
Integer32r/w
Constraints:
range: 0-59
.1.3.6.1.4.1.21239.5.2.30.1.3.1.8
Min Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.9
Max Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.10
Eev valve close sht in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 0 to 100
Fahrenheit: 0 to 179
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.11
Eev mop pressure setting in tenths of a bar.
decibarsInteger32r/w
Constraints:
range: 0-200
.1.3.6.1.4.1.21239.5.2.30.1.3.1.12
Low pressure dt in seconds
secondsInteger32r/w
Constraints:
range: 30-600
.1.3.6.1.4.1.21239.5.2.30.1.3.1.13
Dead band in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 0 to 20
Fahrenheit: 0 to 35
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.14
On-off switch
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.15
Vacuum state
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.16
Control mode:
1 = supply
2 = return
Enumerationr/w
Enumerated Values:
1supply
2return
.1.3.6.1.4.1.21239.5.2.30.1.3.1.17
Manual run enable
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.18
Remote shutdown input
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.19
Monitor shutdown flag
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.20
First on password value
Integer32r/w
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.3.1.21
Filter maintenance setting
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.22
Time between filter maintenance reminders in days
daysInteger32r/w
Constraints:
range: 30-360
.1.3.6.1.4.1.21239.5.2.30.1.3.1.23
Filter maintenance reminder:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.24
Common alarm output direction
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.3.1.25
Abnormal high pressure alarm value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 300-360
.1.3.6.1.4.1.21239.5.2.30.1.3.1.26
Low pressure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.27
High pressure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.28
Low pressure frequently alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.29
High pressure frequently alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.30
Low pressure sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.31
High pressure sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.32
High water alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.33
Remote shutdown alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.34
Eev communication failure alarm:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.35
.1.3.6.1.4.1.21239.5.2.30.1.4 · 1 row entry · 3 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcOutFanPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcOutFanPtTable'
Table that contains VRC out-fan status
vrcOutFanPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.4.1
Entry in the vrcOutFanPtTable: each entry represents data for a VRC
out-fan
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.4.1.1
Out-fan name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.4.1.2
Fan speed (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.4.1.3
.1.3.6.1.4.1.21239.5.2.30.1.5 · 1 row entry · 6 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcOutFanCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcOutFanCfgTable'
Table used for VRC out-fan configuration
vrcOutFanCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.5.1
Entry in the vrcOutFanCfgTable: each entry contains config fields for
a VRC out-fan
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.1
Out-fan start pressure in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 190-250
.1.3.6.1.4.1.21239.5.2.30.1.5.1.2
Out-fan pressure setting in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 50-80
.1.3.6.1.4.1.21239.5.2.30.1.5.1.3
Min out-fan voltage (percent)
%Integer32r/w
Constraints:
range: 30-50
.1.3.6.1.4.1.21239.5.2.30.1.5.1.4
Max out-fan voltage (percent)
%Integer32r/w
Constraints:
range: 60-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.5
Out-fan speed (percent)
%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.6
.1.3.6.1.4.1.21239.5.2.30.1.6 · 1 row entry · 4 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcInFanPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcInFanPtTable'
Table that contains VRC in-fan status
vrcInFanPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.6.1
Entry in the vrcInFanPtTable: each entry represents data for a VRC in-
fan
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.6.1.1
In-fan name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.6.1.2
In-fan run time in hours
hoursInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.6.1.3
In-fan start/stop count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.6.1.4
.1.3.6.1.4.1.21239.5.2.30.1.7 · 1 row entry · 24 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcInFanCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcInFanCfgTable'
Table used for VRC in-fan configuration
vrcInFanCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.7.1
Entry in the vrcInFanCfgTable: each entry contains config fields for a
VRC in-fan
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.1
In-fan output status
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.7.1.2
In-fan low speed step in tenths of a percent per second
0.1%/sInteger32r/w
Constraints:
range: 1-20
.1.3.6.1.4.1.21239.5.2.30.1.7.1.3
In-fan high speed step in tenths of a percent per second
0.1%/sInteger32r/w
Constraints:
range: 1-50
.1.3.6.1.4.1.21239.5.2.30.1.7.1.4
Min in-fan speed (percent)
%Integer32r/w
Constraints:
range: 30-80
.1.3.6.1.4.1.21239.5.2.30.1.7.1.5
Standard in-fan speed (percent)
%Integer32r/w
Constraints:
range: 80-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.6
Min in-fan cfc (percent)
%Integer32r/w
Constraints:
range: 0-30
.1.3.6.1.4.1.21239.5.2.30.1.7.1.7
Standard in-fan cfc (percent)
%Integer32r/w
Constraints:
range: 85-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.8
In-fan start delay in seconds
secondsInteger32r/w
Constraints:
range: 10-600
.1.3.6.1.4.1.21239.5.2.30.1.7.1.9
In-fan stop delay in seconds
secondsInteger32r/w
Constraints:
range: 10-300
.1.3.6.1.4.1.21239.5.2.30.1.7.1.10
In-fan reduce speed delay in seconds
secondsInteger32r/w
Constraints:
range: 0-300
.1.3.6.1.4.1.21239.5.2.30.1.7.1.11
In-fan jump band 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.12
In-fan jump band 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.13
In-fan jump band 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.14
In-fan jump band 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.15
In-fan jump band 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.16
In-fan jump frequency 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.17
In-fan jump frequency 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.18
In-fan jump frequency 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.19
In-fan jump frequency 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.20
In-fan jump frequency 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.21
In-fan temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32r/w
Constraints:
range: 10-150
.1.3.6.1.4.1.21239.5.2.30.1.7.1.22
In-fan temperature I in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.7.1.23
In-fan temperature D in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.7.1.24
.1.3.6.1.4.1.21239.5.2.30.1.8 · 1 row entry · 23 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcCompPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcCompPtTable'
Table that contains VRC compressor status
vrcCompPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.8.1
Entry in the vrcCompPtTable: each entry represents data for a VRC
compressor
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.8.1.1
Compressor name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.8.1.2
Compressor capacity value (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.8.1.3
Compressor run time in hours
hoursInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.8.1.4
Compressor start/stop count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.8.1.5
Compressor driver fault alarm U00 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.6
Compressor driver fault alarm U01 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.7
Compressor driver fault alarm U02 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.8
Compressor driver fault alarm U03 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.9
Compressor driver fault alarm U04 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.10
Compressor driver fault alarm U05 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.11
Compressor driver fault alarm U06 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.12
Compressor driver fault alarm U07 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.13
Compressor driver fault alarm U08 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.14
Compressor driver fault alarm U09 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.15
Compressor driver fault alarm U10 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.16
Compressor driver fault alarm U11 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.17
Compressor driver fault alarm U12 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.18
Compressor driver fault alarm U13 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.19
Compressor driver fault alarm U14 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.20
Compressor driver fault alarm U15 state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.21
Compressor driver communication failure alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.22
Compressor fault lock alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.8.1.23
.1.3.6.1.4.1.21239.5.2.30.1.9 · 1 row entry · 27 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcCompCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcCompCfgTable'
Table used for VRC compressor configuration
vrcCompCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.9.1
Entry in the vrcCompCfgTable: each entry contains config fields for a
VRC compressor
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.1
Compressor output status
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.9.1.2
Compressor output dead band in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.3
Compressor capacity output (percent)
%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.4
Compressor min capacity (percent)
%Integer32r/w
Constraints:
range: 15-50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.5
Compressor start capacity (percent)
%Integer32r/w
Constraints:
range: 40-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.6
Compressor standard capacity (percent)
%Integer32r/w
Constraints:
range: 80-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.7
Compressor start cfc (percent)
%Integer32r/w
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.8
Compressor stop cfc (percent)
%Integer32r/w
Constraints:
range: -200--50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.9
Compressor min run time in minutes
minutesInteger32r/w
Constraints:
range: 0-30
.1.3.6.1.4.1.21239.5.2.30.1.9.1.10
Compressor min stop time in minutes
minutesInteger32r/w
Constraints:
range: 0-10
.1.3.6.1.4.1.21239.5.2.30.1.9.1.11
Compressor jump band 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.12
Compressor jump band 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.13
Compressor jump band 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.14
Compressor jump band 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.15
Compressor jump band 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.16
Compressor jump frequency 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.17
Compressor jump frequency 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.18
Compressor jump frequency 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.19
Compressor jump frequency 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.20
Compressor jump frequency 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.21
Compressor temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 10 to 150
Fahrenheit: 18 to 269
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.9.1.22
Compressor temperature I in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.9.1.23
Compressor temperature D in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.9.1.24
Compressor driver fault alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.25
Compressor driver communication failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.26
Compressor fault lock alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.27
.1.3.6.1.4.1.21239.5.2.30.1.10 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcReturnPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcReturnPtTable'
Table that contains VRC return status
vrcReturnPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.10.1
Entry in the vrcReturnPtTable: each entry represents return data for a
VRC
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.10.1.1
Return name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.10.1.2
Return temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.10.1.3
Return high temperature alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.10.1.4
Return temperature sensor failure alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.10.1.5
.1.3.6.1.4.1.21239.5.2.30.1.11 · 1 row entry · 9 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcReturnCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcReturnCfgTable'
Table used for VRC return configuration
vrcReturnCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.11.1
Entry in the vrcReturnCfgTable: each entry contains config fields for
VRC return
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.11.1.1
Return oil cycle in tenths of an hour
decihoursInteger32r/w
Constraints:
range: 5-50
.1.3.6.1.4.1.21239.5.2.30.1.11.1.2
Return Oil run capacity (percent)
%Integer32r/w
Constraints:
range: 50-100
.1.3.6.1.4.1.21239.5.2.30.1.11.1.3
Return oil run time in minutes
minutesInteger32r/w
Constraints:
range: 0-10
.1.3.6.1.4.1.21239.5.2.30.1.11.1.4
Return temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit:…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.5
Return temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 250 to 350
Fahrenheit: 770 to 949
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.6
Return high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 300 to 450
Fahrenheit: 8…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.7
Return high temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.11.1.8
Return temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.11.1.9
.1.3.6.1.4.1.21239.5.2.30.1.12 · 1 row entry · 6 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcSupplyPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcSupplyPtTable'
Table that contains VRC supply status
vrcSupplyPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.12.1
Entry in the vrcSupplyPtTable: each entry represents supply data for a
VRC
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.12.1.1
Supply name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.12.1.2
Supply temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.12.1.3
Supply low temperature alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.12.1.4
Supply high temperature alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.12.1.5
Supply temperature sensor failure alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.12.1.6
.1.3.6.1.4.1.21239.5.2.30.1.13 · 1 row entry · 8 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcSupplyCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcSupplyCfgTable'
Table used for VRC supply configuration
vrcSupplyCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.13.1
Entry in the vrcSupplyCfgTable: each entry contains config fields for
a VRC supply
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.13.1.1
Supply temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit:…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.2
Supply temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 130 to 280
Fahrenheit: 554 to 823
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.3
Supply low temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 50 to 200
Fahrenheit: 410…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.4
Supply high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 200 to 350
Fahrenheit: 6…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.5
Supply low temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.6
Supply high temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.7
Supply temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.8
.1.3.6.1.4.1.21239.5.2.30.1.14 · 1 row entry · 9 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcPowerPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcPowerPtTable'
Table that contains VRC power status
vrcPowerPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.14.1
Entry in the vrcPowerPtTable: each entry represents power data for a
VRC
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.14.1.1
Power name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.14.1.2
Power voltage measurement in tenths of a volt
decivoltsInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.14.1.3
Power frequency measurement in tenths of hertz
decihertzInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.14.1.4
Power low voltage alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.14.1.5
Power high voltage alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.14.1.6
Phase power loss alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.14.1.7
Power loss alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.14.1.8
Power frequency error alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.14.1.9
.1.3.6.1.4.1.21239.5.2.30.1.15 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcPowerCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcPowerCfgTable'
Table used for VRC power configuration
vrcPowerCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.15.1
Entry in the vrcPowerCfgTable: each entry contains config fields for
VRC power
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.15.1.1
Power low voltage setting in volts
voltsInteger32r/w
Constraints:
range: 100-230
.1.3.6.1.4.1.21239.5.2.30.1.15.1.2
Power high voltage setting in volts
voltsInteger32r/w
Constraints:
range: 100-300
.1.3.6.1.4.1.21239.5.2.30.1.15.1.3
Power low voltage alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.4
Power high voltage alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.5
Power loss alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.6
Power frequency error alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.7
.1.3.6.1.4.1.21239.5.2.30.1.16 · 1 row entry · 3 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcOutdoorPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcOutdoorPtTable'
Table that contains VRC outdoor status
vrcOutdoorPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.16.1
Entry in the vrcOutdoorPtTable: each entry represents data for a VRC
outdoor
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.16.1.1
Outdoor name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.16.1.2
Outdoor temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.16.1.3
.1.3.6.1.4.1.21239.5.2.30.1.18 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcDischPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcDischPtTable'
Table that contains VRC discharge status
vrcDischPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.18.1
Entry in the vrcDischPtTable: each entry represents discharge data for
a VRC
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.18.1.1
Discharge name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.18.1.2
Discharge temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1560
Fahrenheit: -400 to 3128
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.18.1.3
Discharge air pressure value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 0-460
.1.3.6.1.4.1.21239.5.2.30.1.18.1.4
Discharge high temperature alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.18.1.5
Discharge high temperature frequently alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.18.1.6
Discharge temperature sensor failure alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.18.1.7
.1.3.6.1.4.1.21239.5.2.30.1.19 · 1 row entry · 6 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcDischCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcDischCfgTable'
Table used for VRC discharge configuration
vrcDischCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.19.1
Entry in the vrcDischCfgTable: each entry contains config fields for
VRC discharge
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.19.1.1
Discharge temperature calibration value in tenths of a degree. Units
are given by temperatureUnits field in deviceInfo. The settable range
is determined by the current temperature units.
Celsius: -100 to 100
Fahrenhe…
decidegreesSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.19.1.2
Discharge pressure calibration value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: -100-100
.1.3.6.1.4.1.21239.5.2.30.1.19.1.3
Discharge high temperature alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.4
Discharge high temperature frequenctly alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.5
Discharge temperature sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.6
.1.3.6.1.4.1.21239.5.2.30.1.20 · 1 row entry · 6 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcSuctPtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcSuctPtTable'
Table that contains VRC suction status
vrcSuctPtEntry row .1.3.6.1.4.1.21239.5.2.30.1.20.1
Entry in the vrcSuctPtTable: each entry represents suction data for a
VRC
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.20.1.1
Suction name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.20.1.2
Suction temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.20.1.3
Suction air pressure in tenths of a bar
decibarsInteger32
Constraints:
range: 0-173
.1.3.6.1.4.1.21239.5.2.30.1.20.1.4
Suction super heat temperature in tenths of a degree. Units are given
by temperatureUnits field in deviceInfo. The range is determined by
the current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.20.1.5
Suction temperature sensor failure alarm state
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.21239.5.2.30.1.20.1.6
.1.3.6.1.4.1.21239.5.2.30.1.21 · 1 row entry · 3 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk vrcSuctCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-V5-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-V5-MIB::vrcSuctCfgTable'
Table used for VRC suction configuration
vrcSuctCfgEntry row .1.3.6.1.4.1.21239.5.2.30.1.21.1
Entry in the vrcSuctCfgTable: each entry contains config fields for
VRC suction
Indexes
Column Syntax OID
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.21.1.1
Suction pressure calibration value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: -100-100
.1.3.6.1.4.1.21239.5.2.30.1.21.1.2
Suction temperature sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.21.1.3