pduOutletSwitchControl
VERTIV-V5-MIB ·
.1.3.6.1.4.1.21239.5.2.3.5.1.6
Object
column
r/w
Enumeration
Used for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests.
Context
- MIB
- VERTIV-V5-MIB
- OID
.1.3.6.1.4.1.21239.5.2.3.5.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- pduOutletSwitchEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | cancel |
2 | on |
3 | onAfterDelay |
4 | off |
5 | offAfterDelay |
6 | reboot |
7 | rebootAfterDelay |
8 | none |