vrcReturnCfgHighTempAlarmValue
VERTIV-V5-MIB ·
.1.3.6.1.4.1.21239.5.2.30.1.11.1.7
Object
column
r/w
decidegrees Integer32
Return high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129
Context
- MIB
- VERTIV-V5-MIB
- OID
.1.3.6.1.4.1.21239.5.2.30.1.11.1.7- Type
- column
- Access
- readwrite
- Status
- current
- Units
- decidegrees
- Parent
- vrcReturnCfgEntry
Syntax
decidegrees Integer32
Values & Constraints
No enumerated values or constraints recorded.