LIEBERT-GP-PDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
11
Rows
11
Columns
207

lgpPduTable

table
.1.3.6.1.4.1.476.1.42.3.8.20 · 1 row entry · 11 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduTable'
This table contains a list of PDU entries.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored.  The Network Management System (NMS)
cannot create or delete rows in the table. The rows are created by
the agent based upon the number of PDUs being managed.
Each row in the table represents a PDU in the system.
lgpPduEntry row .1.3.6.1.4.1.476.1.42.3.8.20.1
This entry defines the columns to be populated in the
'lgpPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU identifier that is unique
within the agent.
Column Syntax OID
This is the index that indicates the row of the 'lgpPduTable'.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.20.1.1
This is an internal index representing a unique identifier for
each PDU represented by this agent. The value is assigned
by the agent.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.20.1.5
This is a user assigned label representing the PDU.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.20.1.10
System assigned identifier representing the PDU. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be refer…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.20.1.15
This is a one-based value that indicates the PDU's relative
position within a rack or other enclosing entity.
CountSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.20.1.20
This value represents a bit-field of the various operational
states of the PDU. The value is a logical OR of all of the
following potential states of the PDU. Note the bit-position
is given parenthetically next to the …
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.20.1.25
This is a user assigned Tag for the PDU. This value may be
useful for end-user grouping or asset tracking purposes.
The value for this tag does not need to be unique for this
unit or across other units.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.20.1.35
This is a user assigned Tag for the PDU. This value may be
useful for end-user grouping or asset tracking purposes.
The value for this tag does not need to be unique for this
unit or across other units.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.20.1.40
System assigned serial number for this PDU. This number is
assigned at time of manufacture, is globally unique with respect
to all PDU units.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.20.1.45
Number of receptacle branches (Rb) within this PDU.
CountSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.20.1.50
This is the PDU Software Over Current Protection feature which will
prevent unused receptacles from turning on when the
'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold
is violated. Such receptacles shal…
Enumerationr/w
Enumerated Values:
0disabled
1enable
.1.3.6.1.4.1.476.1.42.3.8.20.1.55
.1.3.6.1.4.1.476.1.42.3.8.30.20 · 1 row entry · 20 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduPsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduPsTable'
This table contains a list of the PDU's power source(s).
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored and the number of
power sources installed for each PDU.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being monitored.  Each row in the table represents a PDU's
Power Source.
lgpPduPsEntry row .1.3.6.1.4.1.476.1.42.3.8.30.20.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduPsTable' (Power Source Table).
This table is indexed by both the 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' a…
Column Syntax OID
This is a unique identifier for the Power Source within a
given PDU. This is one of two indexes used to indicate the row of
the 'lgpPduTable'.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.5
This is a unique entry id representing a given PDU power source
for the PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.10
System assigned identifier for this power source. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be ref…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.15
This is the model name (identifier) of the power supply.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.20
The PDU's power supply physical wiring type.
not-specified
The type has not been specified/configured. The end_user
must configure this object to specify the physical wiring
type.
single-phase-3-wire-L1-N-P…
Enumerationr/w
Enumerated Values:
0not-specified
1single-phase-3-wire-L1-N-PE
2two-phase-3-wire-L1-L2-PE
3three-phase-4-wire-L1-L2-L3-PE
4three-phase-5-wire-L1-L2-L3-N-PE
5two-phase-4-wire-L1-L2-N-PE
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.25
Rated Input Line Voltage for the power source (i.e. this is the
nominal line input voltage; it is NOT a measured voltage).

The value is defined to be the rated line voltage
(either line-to-neutral or line…
VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.30
This is the rated input line current for the module
(it is NOT the measured current).
0.1 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.35
Rated input line frequency for this power source
(i.e. This is the expected line frequency; it is NOT a
measured frequency; it is typically 50 Hz or 60 Hz).
HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.40
Total accumulated energy, measured at the power source input, since
the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall res…
0.1 Kilowatt-HourSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.50
This is a unique serial number of the power supply. This number
is assigned to the power supply at the time of manufacture.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.55
This is the version of the firmware installed on the PDU's
power supply.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.60
Total input power for this power supply. This is the sum of the
power for all phases
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.65
The neutral current measured at the PDU's power source.
0.1 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.70
The threshold at which an over current warning is activated. If the
measured neutral current (lgpPduPsEntryEcNeutral) is above this
percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over neutral c…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.75
The threshold at which an over current alarm is activated. If the
measured neutral current (lgpPduPsEntryEcNeutral) is above this
percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over neutral cur…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.80
The parameter is for setting the maximum acceptable percentage of
'Unbalanced Load' between any two phases. This setting shall
trigger an alarm when the % load between any two phases varies by
a percentage higher than t…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.85
Total Apparent power for this power supply. This is the sum of the
apparent power for all phases
VoltAmpSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.90
Total power factor, which is real power/apparent power for all
phases combined. This is the sum of the real power for all phases
divided by the sum of the apparent power for all phases.
0.01 Power FactorSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.95
The measured residual current.
0.001 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.100
The threshold at which an over current alarm is activated. If the
measured residual current (lgpPduPsEntryEcResidual) is above this
value, an over current alarm is activated. Setting this to 0mA
disables the alarm.
0.001 Amp-AC-RMSSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.105
.1.3.6.1.4.1.476.1.42.3.8.30.40 · 1 row entry · 21 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduPsLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduPsLineTable'
This table contains a list of PDU's power source line/phase
measurements. The table contains zero, one, or many rows, depending
upon the number of PDU's Power Sources being monitored.
The NMS cannot create or delete rows in the table.
The rows are created by the agent based upon the capabilities of the
managed PDU's power supply(s).  Each row in the table represents a
particular phase/line measurement of a power supply for a
given PDU.
lgpPduPsLineEntry row .1.3.6.1.4.1.476.1.42.3.8.30.40.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduPsLineTable'.
The table is index by three indexes which taken together
uniquely identify line/phase information for a given power so…
Column Syntax OID
This is the index that indicates the line/phase of the measurements
in the given row of the 'lgpPduPsLineTable'.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.5
Unique identifier (within a PDU) for the PDU's power source.
The object may not be available in non-modular systems.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.10
The line number (phase) that the measurement represents for all
measurements in a given row of the table. Note that this always
matches the lgpPduPsLineEntryIndex of the same row in the table.
The line/phases are as fo…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.15
Alternating Current RMS Line to Neutral Electrical Potential
measurement.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.1 Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.19
Alternating Current RMS Line to Neutral Electrical Potential
measurement.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.20
Total input line-to-neutral electrical current.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.1 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.21
Total input line-to-neutral electrical current.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.01 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.22
The threshold at which an under current alarm is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an under current…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.35
The threshold at which an over current warning is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over current …
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.36
The threshold at which an over current alarm is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over current al…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.37
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.1 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.38
The percent of current utilization relative to the over current
alarm threshold.
0.1 PercentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.39
Line to Line Electrical Potential.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.60
Line to Line Electrical Potential.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.1 Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.61
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.01 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.62
The line-to-neutral measurement of the Real Power (Watts).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.63
The line-to-line measurement of the Real Power (Watts).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.64
The line-to-neutral measurement of the Apparent Power (VA).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
VoltAmpSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.65
The line-to-line measurement of the Apparent Power (VA).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
VoltAmpSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.66
The line-to-neutral measurement of the Power Factor of the
power source.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.01 Power FactorSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.67
The line-to-line measurement of the Power Factor of the
power source.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table.
0.01 Power FactorSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.68
.1.3.6.1.4.1.476.1.42.3.8.40.20 · 1 row entry · 30 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduRbTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRbTable'
This table contains a list of PDU Receptacle branches.
The table contains zero, one, or many rows, depending
upon the number of PDUs being managed and how many
receptacle branches each PDU has installed.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being managed.  Each row in the table represents a receptacle branch
for a given PDU.  The PDU that a branch is installed
on is indicated by the column lgpPduEntryIndex.  The branch
within the lgpPduEntryIndex PDU is indicated by the column
lgpPduRbEntryIndex.
lgpPduRbEntry row .1.3.6.1.4.1.476.1.42.3.8.40.20.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduRbTable'. The table is indexed
by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The
lgpPduEntryIndex specifies the PDU, de…
Column Syntax OID
This is the index that indicates the row of the
'lgpPduRbTable'
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.1
A unique id representing the receptacle branch within the
collection of branches being monitored by this agent. The
uniqueness of this id is within the PDUs being managed by
a single agent.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.5
A user assigned label representing the receptacle branch.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.8
System assigned identifier for this receptacle branch. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not b…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.20
This is a one-based value that indicates the relative
position of the branch within the PDU.
CountSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.25
A globally unique serial number for this branch. This number
is assigned to the branch at the time of manufacture and can not
be modified. NOTE: Generally only PDUs with replaceable
receptacle branches will have seria…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.30
This is the model designation for this receptacle branch.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.35
This is the firmware version number of the control software
running on the receptacle branch. Only PDUs with
replaceable receptacle branches will typically support this
object.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.40
This is a user assigned Tag for the receptacle branch. This
value may be useful for end-user grouping or asset tracking
purposes. The value for this tag does not need to be unique
for this unit or across other units.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.41
This is a user assigned Tag for the receptacle branch. This
value may be useful for end-user grouping or asset tracking
purposes. The value for this tag does not need to be unique
for this unit or across other units.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.42
This enumeration represents the type of receptacles installed
on this receptacle branch. All receptacles on this branch are
of this type/style.

not-specified
If this value is returned, either the rec…
Enumeration
Enumerated Values:
0not-specified
1nema-5-20R-20-Amp
2iec-C13-sheet-F-10-Amp
3iec-C19-sheet-J-16-Amp
4iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp
5nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp
6nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp
7cee-7-type-E-schuko
8nema-L6-30R-30-Amp
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.45
Receptacle branch capabilities describes what an individual branch
is capable of.

no-optional-capabilities
The branch is unable to report measurements and lacks
control capabilities.
measurement-o…
Enumeration
Enumerated Values:
0not-specified
1no-optional-capabilities
2measurement-only
3measurement-and-control
4control-only
5current-measurement-only
6current-measurement-and-control
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.50
This represents the line source that is supplying power to this
receptacle branch.
not-specified
The line source supplying power to the load for this
receptacle branch has not been specified/configur…
Enumeration
Enumerated Values:
0not-specified
1line-1-neutral
2line-2-neutral
3line-3-neutral
4line-1-line-2
5line-2-line-3
6line-3-line-1
7line-1-line-2-and-line-1-neutral
8line-2-line-3-and-line-2-neutral
9line-3-line-1-and-line-3-neutral
10unknown-line-neutral
11unknown-line-line
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.55
The number of receptacles on this receptacle branch.
CountSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.60
Rated Line Voltage for the receptacle branch and its associated
receptacles (i.e. This is the nominal line voltage that is
available to the connected load; it is NOT a measured voltage.)
VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.70
This is the rated input line current for the module
(it is NOT the measured current).
0.1 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.75
This is the rated electrical frequency for the receptacle branch
and its associated receptacles
HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.80
Total accumulated energy, measured at the receptacle branch input,
since the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shal…
0.1 Kilowatt-HourSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.85
The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
0.1 VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.100
The line-to-neutral measurement of the Real Power (Wattage)
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.115
The line-to-neutral measurement of the Apparent Power (VA)
VoltAmpSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.120
The line-to-neutral measurement of the Power Factor of the
receptacle branches' input.
0.01 Power FactorSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.125
The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared).
0.01 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.130
The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current alarm
is…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.135
The threshold at which an over current warning is activated. If
the measured current (lgpPduRbEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current warning
i…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.140
The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbEntryEcLN) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm
is …
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.145
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.01 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.150
The percent of current utilization relative to the over current
alarm threshold.
0.1 PercentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.160
The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
0.1 VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.170
The configuration parameter to enable or disable the Branch
SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the recepta…
Enumerationr/w
Enumerated Values:
0disable
1enable
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.175

lgpPduRbLineTable

table deprecated
.1.3.6.1.4.1.476.1.42.3.8.40.40 · 1 row entry · 18 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduRbLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRbLineTable'
This table contains a list of PDU receptacle branch line/phase
measurements. The table contains zero, one, or many rows, depending
upon the number of PDUs and the number of receptacle branches
on each PDU that are being monitored.
          
The NMS cannot create or delete rows in the table.
The rows are created by the agent based upon the capabilities of the
PDU(s) being monitored.  Each row in the table represents a
particular phase/line measurement of a PDU Receptacle
Branch.
          
Rows in the table are uniquely identified by three indexes representing
respectively the PDU (lgpPduEntryIndex), the receptacle
branch (lgpPduRbEntryIndex) and the line/phase being
measured (lgpPduRbLineEntryIndex).
lgpPduRbLineEntry row .1.3.6.1.4.1.476.1.42.3.8.40.40.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduRbLineTable'. The table is
indexed by three indexes. The 'lgpPduEntryIndex' references
a PDU in the 'lgpPduTable' to which this re…
Column Syntax OID
This is the index that indicates the row of the
'lgpPduRbLineTable'
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.1
Runtime assigned branch identifier.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.5
The line number or phase that the measurement for this
receptacle branch represents for each measurement in this row of
the table. The phases are as follows:
Line# Description
----- --------------------------------…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.10
The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
0.1 VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.19
The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.20
The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared).
0.1 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.21
The line-to-neutral measurement of the Real Power (Wattage)
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.22
The line-to-neutral measurement of the Apparent Power (VA)
VoltAmpSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.23
The line-to-neutral measurement of the Power Factor of the
receptacle branches' input.
0.01 Power FactorSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.24
The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared).
0.01 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.25
The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbLineEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current alar…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.35
The threshold at which an over current warning is activated. If
the measured current (lgpPduRbLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current warni…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.36
The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLN) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.37
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.01 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.39
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.1 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.40
The percent of current utilization relative to the over current
alarm threshold.
0.1 PercentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.41
The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.60
The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared).
0.1 VoltRMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.40.40.1.61
.1.3.6.1.4.1.476.1.42.3.8.50.20 · 1 row entry · 39 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduRcpTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRcpTable'
This table contains a list of PDU receptacle entries.
The table contains numerous rows representing an individual
receptacle, depending upon the number and configuration of
the PDU(s) being monitored by the agent.
          
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the managed
PDU(s).  Each row in the table represents a receptacle in
the system.
lgpPduRcpEntry row .1.3.6.1.4.1.476.1.42.3.8.50.20.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpTable'. This table is indexed
by three indexes. The 'lgpPduEntryIndex' references a PDU in
the 'lgpPduTable' that a given row in…
Column Syntax OID
This is the index that indicates the receptacle position on the
receptacle branch. This along with the other two indexes on the
lgpPduRcpTable uniquely identify the receptacle in this table.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.1
A runtime assigned receptacle identification number.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.5
User assigned label for this receptacle.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.10
User assigned Tag to assist in identifying or grouping this
receptacle within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.15
User assigned Tag to assist in identifying or grouping this
receptacle within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.20
System assigned identifier representing the receptacle. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not b…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.25
A number representing the position of the receptacle within the
receptacle branch.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.30
The type or form of receptacle. The enumerations are specified
in well-known industry standard terms and abbreviations.
Enumeration
Enumerated Values:
0not-specified
1nema-5-20R-20-Amp
2iec-C13-sheet-F-10-Amp
3iec-C19-sheet-J-16-Amp
7cee-7-type-E-schuko
8nema-L6-30R-30-Amp
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.40
This represents the line source that is supplying power to this
receptacle.
not-specified
The line source supplying power to the load for this
receptacle has not been specified/configured.
line-1-N
Enumeration
Enumerated Values:
0not-specified
1line-1-N
2line-2-N
3line-3-N
4line-1-line-2
5line-2-line-3
6line-3-line-1
7unknown-line-neutral
8unknown-line-line
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.45
Receptacle capabilities describes what an individual receptacle is
capable of.

no-optional-capabilities
The receptacle is unable to report measurements and lacks
control capabilities.
measurement-…
Enumeration
Enumerated Values:
0not-specified
1no-optional-capabilities
2measurement-only
3measurement-and-control
4control-only
5current-measurement-only
6current-measurement-and-control
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.50
Voltage being delivered to the load attached to the receptacle.
Alternating Current RMS Electrical Potential measurement.
Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.55
Voltage being delivered to the load attached to the receptacle.
Alternating Current RMS Electrical Potential measurement.
0.1 Volts-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.56
Current (amperage) being delivered to the load attached to
the receptacle. Electrical Current is measured in
Amperes RMS (Root Mean Squared).
0.1 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.60
Current (amperage) being delivered to the load attached to
the receptacle. Electrical Current is measured in
Amperes RMS (Root Mean Squared).
0.01 Amp-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.61
Real Power (watts) being delivered to the load attached to
the receptacle.
WattSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.65
Apparent Power (volt-amps) being delivered to the load
attached to the receptacle.
Volt-Amp-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.70
Receptacle Power Factor, which is the ratio of real power
to apparent power (i.e. ratio of watts to volts-amps).
.01 Power FactorSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.75
The measured line frequency being delivered to the load
attached to the receptacle.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.80
Total accumulated energy, measured at the module input, since
the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall result in…
0.1 Kilowatt-HourSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.85
The amount of time to wait before power is applied to the
receptacle after a power strip is turned on or rebooted.
This can be used to stagger the powering of multiple
receptacles in order to prevent a large initial cur…
SecondsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.90
unknown
The current power state is unknown.
off
The current power state of the receptacle is OFF.
on
The current power state of the receptacle is ON.
off-pending-on-delay
The current power state of the receptacle is OFF…
Enumeration
Enumerated Values:
0unknown
1off
2on
3off-pending-on-delay
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.95
The 'Power Up State' defines the state to which the receptacle shall return
after a power cycle of the PDU.

on
The receptacle shall be switched to the ON state after the power on delay
timer (lgpPdu…
Enumerationr/w
Enumerated Values:
1on
2off
3last-state
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.96
This object represents the current and persistent (configured)
power state of the receptacle. The receptacle can also be
controlled by writing to this object.
off
The current and persisted (configured) power state …
Enumerationr/w
Enumerated Values:
0off
1on
2cycle-power
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.100
This object represents the locked state of the receptacle.

unknown
The lock state of the receptacle is not known at this time.
locked
If the receptacle is 'locked' then its current persisted
(…
Enumerationr/w
Enumerated Values:
0unknown
1unlocked
2locked
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.105
The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current al…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.150
The threshold at which an over current warning is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current war…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.151
The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm…
PercentSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.152
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.01 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.159
The amount that the current/amperage may increase from its present
value before an over current alarm occurs.
0.1 Amps-AC-RMSSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.160
The percent of current utilization relative to the over current
alarm threshold.
0.1 PercentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.161
Receptacle current crest factor, which is the peak amplitude of the
current waveform divided by the RMS value of the waveform.
0.01SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.162
Blink the receptacle LED. Writing blinkLED(2) will cause the LED
to blink for a predefined duration of time. Reading this object
will always return noAction(1).
Enumerationr/w
Enumerated Values:
1noAction
2blinkLED
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.200
The configuration parameter to enable or disable the Receptacle
SW Over Temperature Protection feature
If the feature is enabled, in case of Over Temperature Alarm condition,
following action will be taken on the recept…
Enumerationr/w
Enumerated Values:
0disable
1enable
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.205
Receptacle Operating Condition - indicates the condition of the receptacle.

The operating condition has the following:

Normal
Normal operation without any alarm or warning.
Alarm
An…
Enumeration
Enumerated Values:
1normalOperation
2normalWithWarning
3normalWithAlarm
4abnormal
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.210
The configuration parameter can be used by the user to mark a receptacle as
critical or non-critical.
Enumerationr/w
Enumerated Values:
0critical
1notCritical
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.215
The 'Post On Delay' is the time interval (in seconds) that the PDU waits after
a command is issued to switch ON a receptacle before applying power to the receptacle

A value of zero implies that there is n…
SecondsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.220
The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after
a command is issued to switch OFF a receptacle before removing power from the receptacle

A value of zero implies that there …
SecondsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.225
This receptacle can be added to a group by writing a corresponding
OID to this column. The OID must be a pointer to the
lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
For example, to add this receptacle to group…
ObjectIdentifierr/w .1.3.6.1.4.1.476.1.42.3.8.50.20.1.230
This receptacle can be removed from a group by writing a corresponding
OID to this column. The OID must be a pointer to the
lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
For example, to remove this receptacle f…
ObjectIdentifierr/w .1.3.6.1.4.1.476.1.42.3.8.50.20.1.235
.1.3.6.1.4.1.476.1.42.3.8.50.30.10 · 1 row entry · 6 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduRcpGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRcpGroupTable'
This table contains a list of the possible receptacle groups
that can be created.  The table contains a fixed number of rows, which
is the maximum number of receptacle groups that can be used.
lgpPduRcpGroupEntry row .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpGroupTable'.
This table is indexed by lgpPduRcpGroupIndex.
Column Syntax OID
This is an index into the table. There will always be 64 rows,
each representing a separate receptacle group.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1
User assigned identifier for this receptacle group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.10
This column will delete the receptacles from the group when written to.
Enumerationr/w
Enumerated Values:
0no-action
1delete-receptacle-group
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.20
This column controls the power to the group of receptacles. The corresponding
operation will be performed on all receptacles that have been added to the group.
Enumerationr/w
Enumerated Values:
0no-action
1off
2on
3cycle-power
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.30
This column controls the locking of the group of receptacles. The corresponding
operation will be performed on all receptacles that have been added to the group.
Enumerationr/w
Enumerated Values:
0no-action
1unlock
2lock
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.40
This column will blink the LED's associated with all receptacles that are part of
the group.
Enumerationr/w
Enumerated Values:
0no-action
1blinkLED
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.50
.1.3.6.1.4.1.476.1.42.3.8.50.30.20 · 1 row entry · 2 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduRcpGroupDisplayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRcpGroupDisplayTable'
This table is used to display which receptacle groups are currently
defined and which receptacles are associated with each group.
The table will have 0 rows when no receptacles have been added to any receptacle
groups.  If a single receptacle has been added to 2 different groups, 
there will be 2 rows in the table.
lgpPduRcpGroupDisplayEntry row .1.3.6.1.4.1.476.1.42.3.8.50.30.20.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpGroupDisplayTable'.
This table is indexed by two indexes.
The 'lgpPduRcpGroupIndex' references a receptacle group in
the 'lgpPdu…
Column Syntax OID
This is an index into the table. There can be zero or more rows
in this table.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.10
This column displays the PDU receptacle list of the specified
receptacle group. The value in this column is a comma delimted string that decribes
the list of receptacles of a PDU that are members of the receptacle …
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.20

lgpPduAuxSensorTable

table deprecated
.1.3.6.1.4.1.476.1.42.3.8.60.10 · 1 row entry · 25 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduAuxSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduAuxSensorTable'
This table contains a list of the PDU's Auxiliary Sensors.
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored and the number of
auxiliary sensors installed for each PDU.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being monitored.  Each row in the table represents an auxiliary
sensor in a PDU.
lgpPduAuxSensorEntry row .1.3.6.1.4.1.476.1.42.3.8.60.10.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxSensorTable'.
This table is indexed by both the 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' and the
'lgpPdu…
Column Syntax OID
This is the index indicating the nth element of the table.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.1
not-specified
The type of sensor is unknown.
temperature
The sensor in this row of the table measures temperature.
humidity
The sensor in this row of the table measures relative humidity.
temperature-and-humidity
The se…
Enumeration
Enumerated Values:
0not-specified
1temperature
2humidity
3temperature-and-humidity
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.5
System assigned auxiliary sensor identification number. The value
assigned is product specific.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.10
Label assigned to the auxiliary sensor at runtime by the system.
The value is independent of any user assigned label or asset tag.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.15
Auxiliary sensor relative position. This is a one-based value
that indicates the sensor's position relative to the sensor string
connector.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.20
User assigned auxiliary sensor label.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.25
User assigned Tag to assist in identifying or grouping this
auxiliary sensor within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.30
User assigned Tag to assist in identifying or grouping this
auxiliary sensor within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.35
The temperature sensor's globally unique serial number assigned at
the time of manufacture.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.40
The humidity sensor's globally unique serial number assigned at
the time of manufacture.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.45
Temperature measured at the temperature sensor reported in
degrees Fahrenheit.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.50
Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.55
Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.60
Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.65
Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.70
Temperature measured at the temperature sensor reported in
degrees Celsius.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.75
Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.80
Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.85
Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.90
Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.95
Relative Humidity measured at the humidity sensor.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.100
Under relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or below this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.105
Over relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or above this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.110
Under relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or below this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.115
Over relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or above this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.10.1.120
.1.3.6.1.4.1.476.1.42.3.8.60.15 · 1 row entry · 33 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduAuxMeasTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduAuxMeasTable'
This table contains a list of the PDU's Auxiliary Sensor Measurements.
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored, the number of auxiliary
sensors installed for each PDU, and the number of measurements within
each sensor. The NMS cannot create or delete rows in the table. The
rows are created by the agent based upon the capabilities of the PDUs
being monitored.  Each row in the table represents an auxiliary
sensor measurement in a PDU.
lgpPduAuxMeasEntry row .1.3.6.1.4.1.476.1.42.3.8.60.15.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxMeasTable'.
This table is indexed by 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' wh…
Column Syntax OID
This is the index indicating the sensor the measurement is accessed
from.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.1
This is the measurement's index identified on the sensor.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.5
not-specified
The type of measurement is unknown.
temperature
The measurement in this row of the table measures temperature.
humidity
The measurement in this row of the table measures relative
humidity.
door-closure
The…
Enumeration
Enumerated Values:
0not-specified
1temperature
2humidity
3door-closure
4contact-closure
5differential-pressure
6leak-detection
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.10
Label assigned to the auxiliary sensor at runtime by the system.
The value is independent of any user assigned label or asset tag.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.15
User assigned auxiliary sensor measurement label.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.20
User assigned Tag to assist in identifying or grouping this
auxiliary sensor measurement within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.25
User assigned Tag to assist in identifying or grouping this
auxiliary sensor measurement within the end-users domain.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.30
The sensor's globally unique serial number assigned at
the time of manufacture.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.35
Temperature measured at the temperature sensor reported in
degrees Fahrenheit.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.40
Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.50
Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.55
Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.60
Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.65
Temperature measured at the temperature sensor reported in
degrees Celsius.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.70
Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.75
Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.80
Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.85
Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.90
Relative Humidity measured at the humidity sensor.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.95
Under relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or below this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.100
Over relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or above this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.105
Under relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or below this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.110
Over relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or above this value.
0.1 percent Relative HumiditySNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.115
The state of a door sensor measurement.
not-specified
The door state is unknown.
open
The door is in the open state.
closed
The door is in the closed state.
Enumeration
Enumerated Values:
0not-specified
1open
2closed
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.120
Configure door state alarms. This object provides the ability to
select when a door closure measurement should cause an alarm.
disabled
The door state will never result in alarm.
alarm-when-open
Acti…
Enumerationr/w
Enumerated Values:
0disabled
1alarm-when-open
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.125
The state of a contact closure sensor measurement.
not-specified
The contact closure state is unknown.
open
The contact closure is in the open state.
closed
The contact closure is in the closed state.
Enumeration
Enumerated Values:
0not-specified
1open
2closed
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.130
Configure contact closure state alarms. This object provides the
ability to select when a contact closure measurement should
activate an alarm.
disabled
The contact closure state will never result in alarm.
Enumerationr/w
Enumerated Values:
0disabled
1alarm-when-open
2alarm-when-closed
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.135
Pressure difference measured at the differential pressure sensor.
0.1 PascalSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.140
Under differential pressure alarm threshold. An alarm is activated
if the differential pressure is equal to or below this value.
0.1 PascalSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.145
Over differential pressure alarm threshold. An alarm is activated
if the differential pressure is equal to or above this value.
0.1 PascalSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.150
Under differential pressure warning threshold. A warning is activated
if the differential pressure is equal to or below this value.
0.1 PascalSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.155
Over differential pressure warning threshold. A warning is activated
if the differential pressure is equal to or above this value.
0.1 PascalSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.160
not-specified
The leak detection state is unknown.
no-leak-detected
No leak has been detected.
leak-detected
A leak has been detected.
leak-detection-pending
Characterization of possible leak is pending further analysis…
Enumeration
Enumerated Values:
0not-specified
1no-leak-detected
2leak-detected
3leak-detection-pending
4cable-fault
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.165
.1.3.6.1.4.1.476.1.42.3.8.60.20 · 1 row entry · 2 columns
Uses the liebert variant from /opt/observium/mibs/liebert.
Command help
Walk lgpPduAuxMeasOrderTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduAuxMeasOrderTable'
This table contains a list of the PDU's Auxiliary Sensors
and their respective 'location' in the lgpPduAuxMeasTable table.
This table contains 1 row, for potential sensor for each PDU.
The rows in this table are created by the agent based on the maximum
number of sensor's supported for each PDU.
          
Each row in the table represents an auxiliary sensor, identified by its
factory assigned serial number and its placement in the lgpPduAuxMeasTable.
If all serial numbers in this table are empty strings then the
location of the sensors in the lgpPduAuxMeasTable will default to the
agent's default placement algorithm.  If sensors in the
lgpPduAuxMeasTable and are not represented by an entry in this table then
the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable,
and other display mediums, will be determined by the agent, but in no
case will an unrepresented sensor occupy a position reserved for a sensor
present in this table.  Those unrepresented sensor's display location is
not guaranteed to be consistent across reboots or rediscovery actions
on the sensor bus.  Only sensors represented in this table are guarantted
consistent placement as specified by their index entries (position) in
this table.
          
Note that it is possible to have entries in this table representing sensors
that may not exist on the given PDU at runtime. These allocated by not present
sensors will reduce the total number of sensors that can be displayed for
the given PDU.
lgpPduAuxMeasOrderEntry row .1.3.6.1.4.1.476.1.42.3.8.60.20.1
This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxMeasOrderTable'.
This table is indexed by 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSen…
Column Syntax OID
Index representing the position within the sensor string on the given PDU
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.476.1.42.3.8.60.20.1.5
The sensor's globally unique serial number assigned at
the time of manufacture. The sensor represented by this
serial number will be, if discovered, by the agent placed
in the lgpPduAuxMeasTable at the location specifi…
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.476.1.42.3.8.60.20.1.15