lgpPduRbEntryEnergyAccum

LIEBERT-GP-PDU-MIB · .1.3.6.1.4.1.476.1.42.3.8.40.20.1.85

Object

column r/w 0.1 Kilowatt-HourSNMPv2-SMIUnsigned32
Total accumulated energy, measured at the receptacle branch input,
since the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall result in a write error and the
total energy value remains unchanged.
              
If the energy has not been reset and has not wrapped, then this
is the total energy since installation.
              
This value persists across boot events.
              
NOTE: Resetting this value does not reset the values for the
individual receptacles.

Context

MIB
LIEBERT-GP-PDU-MIB
OID
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.85
Type
column
Access
readwrite
Status
current
Units
0.1 Kilowatt-Hour
Parent
lgpPduRbEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRbEntryEnergyAccum'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-PDU-MIB::lgpPduRbEntryEnergyAccum.<lgpPduEntryIndex>.<lgpPduRbEntryIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'LIEBERT-GP-PDU-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'LIEBERT-GP-PDU-MIB::lgpPduRbEntryEnergyAccum'

Syntax

0.1 Kilowatt-HourSNMPv2-SMIUnsigned32
Source
SNMPv2-SMIUnsigned32
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295