CYCLADES-ACS5K-PM-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
8
Rows
8
Columns
96
cyPMTable
table.1.3.6.1.4.1.2925.8.5.2
·
1 row entry
·
6 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMTable'
Allows to read information about each connected PM
Information about the connected PM
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The number of the serial port when the PM is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.2.1.1 |
|
Number of outlets.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.2.1.2 |
|
Total number of PM unists that are accessed by this
serial port. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.2.1.3 |
|
Current reading for the PM.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.2.1.4 |
|
The software version of the PM.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.2.1.5 |
|
A character string for the user to send commands to
PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on , or cycled or locked or unlocked as a group. The command… |
OctetStringr/w Constraints: range: 1-100 |
.1.3.6.1.4.1.2925.8.5.2.1.7 |
cyPMUnitTable
table.1.3.6.1.4.1.2925.8.5.3
·
1 row entry
·
13 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMUnitTable'
Allow operations on specific PM unit connected
Allow operations on outlet
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The number of the PM unit in the daisy-chained mode.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.3.1.1 |
||||
|
The software version of this PM unit.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.3.1.2 |
||||
|
Number of outlets of this PM unit.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.3 |
||||
|
Number of the first outlet of this PM unit.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.4 |
||||
|
Current of this PM unit in AMP.
The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.5 |
||||
|
Maximum current of this PM unit in AMP.
The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the maximum current is 0.5 AMP.) |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.6 |
||||
|
Sequence interval delay.
Valid values are 2 to 15 (seconds). |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.9 |
||||
|
Number of seconds that a socket stays off
before turning it back on. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.10 |
||||
|
PDU identification.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.3.1.11 |
||||
|
Number of phases of this PDU unit.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.3.1.12 |
||||
|
Number of banks of this PDU unit.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.13 |
||||
|
Nominal Voltage configured for this PDU unit, when it does not have voltage sensor
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.14 |
||||
|
Power Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.3.1.15 |
cyOutletTable
table.1.3.6.1.4.1.2925.8.5.4
·
1 row entry
·
11 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyOutletTable'
Allow operations on outlet
Allow operations on outlet
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
The outlet number on the PM. Zero is ALL outlets.
|
IF-MIBInterfaceIndexOrZero Type Constraints: range: 0..2147483647Description: This textual convention is an extension of the InterfaceIndex convention. The latter defines a greater than zero value used to identify an interface or interface sub-layer in the managed system. This extension permits… |
.1.3.6.1.4.1.2925.8.5.4.1.1 |
||||||||
|
The name given to a particular outlet Maximum size is 8 characters.
|
OctetStringr/w Constraints: range: 1-8 |
.1.3.6.1.4.1.2925.8.5.4.1.2 |
||||||||
|
Alias of the Server connected to this outlet .
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.4.1.3 |
||||||||
|
Getting this object will return the power state of
the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of the outlet. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.4.1.4 |
||||||||
|
Getting this object will return the lock state of
the outlet. Setting this object will change the lock state of the outlet. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.4.1.5 |
||||||||
|
The power unit interval of this outlet in seconds.
The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex. : value is 5, the interval is 0.5 seconds.) |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.4.1.6 |
||||||||
|
Minimum time in seconds an outlet will stay on before
turning it off. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.4.1.7 |
||||||||
|
Minimum time in seconds an outlet will stay off before
turning it on. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.4.1.8 |
||||||||
|
Outlet state after a cold boot. It can be set to on
or off. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.4.1.9 |
||||||||
|
PDU identification.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.4.1.10 |
||||||||
|
The number of the PDU unit in the daisy-chained mode.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.4.1.11 |
cyPMElecPduTable
table.1.3.6.1.4.1.2925.8.5.5
·
1 row entry
·
13 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMElecPduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMElecPduTable'
Allow operations on elecmon element of the PDUs
each entry has the information about the elecmon element of the PDUs.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Serial Port number where the PDU is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.5.1.1 |
||||
|
The number of the PDU unit in the daisy-chained mode
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.5.1.2 |
||||
|
Actual value of current in the element (A x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.3 |
||||
|
Maximum detected value of current in the element (A x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.4 |
||||
|
Actual value of power in the element (W x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.5 |
||||
|
Maximum value of power in the element (W x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.6 |
||||
|
Actual value of voltage in the element (V).When element
does not have voltage sensor, it returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.7 |
||||
|
Maximum value of voltage in the element (V). When element
does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.8 |
||||
|
Actual value of power factor in the element (Pf x 10).
When element does not have power factor sensor, returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.9 |
||||
|
Maximum value of power factor in the element (Pf x 10).
When element does not have power factor sensor, returns 0. Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.5.1.10 |
||||
|
This PDU unit's Power sensor type.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.5.1.11 |
||||
|
This PDU unit's has voltage sensor type.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.5.1.12 |
||||
|
This PDU unit's Power Factor sensor type.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.5.1.13 |
cyPMElecPhaseTable
table.1.3.6.1.4.1.2925.8.5.6
·
1 row entry
·
15 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMElecPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMElecPhaseTable'
Allow operations on elecmon element for phases
each entry has the information about the elecmon for phase.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Serial Port number where the PDU is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.6.1.1 |
||||
|
The number of the PDU unit in the daisy-chained mode
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.6.1.2 |
||||
|
index of the phase in the PDU. Index can be 1,2 or 3.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.6.1.3 |
||||
|
Sys-name of the phase.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.6.1.4 |
||||
|
Actual value of current in the phase (A x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.5 |
||||
|
Maximum detected value of current in the phase (A x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.6 |
||||
|
Actual value of power in the phase (W x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.7 |
||||
|
Maximum value of power in the phase (W x 10).Write operation
accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.8 |
||||
|
Actual value of voltage in the phase (V).When phase does
not have voltage sensor, it returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.9 |
||||
|
Maximum value of voltage in the phase (V). When phase does
not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.10 |
||||
|
Actual value of power factor in the phase (Pf x 10). When
phase does not have power factor sensor, returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.11 |
||||
|
Maximum value of power factor in the phase (Pf x 10). When
phase does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.6.1.12 |
||||
|
The type of Power sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.6.1.13 |
||||
|
The type of Voltage sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.6.1.14 |
||||
|
The type of Power Factor sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.6.1.15 |
cyPMElecBankTable
table.1.3.6.1.4.1.2925.8.5.7
·
1 row entry
·
15 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMElecBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMElecBankTable'
Allow operations on elecmon element for banks
each entry has the information about the elecmon for Bank.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Serial Port number where the PDU is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.7.1.1 |
||||
|
The number of the PDU unit in the daisy-chained mode
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.7.1.2 |
||||
|
index of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.7.1.3 |
||||
|
Sys-name of the Bank.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.7.1.4 |
||||
|
Actual value of current in the Bank (A x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.5 |
||||
|
Maximum detected value of current in the Bank (A x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.6 |
||||
|
Actual value of power in the Bank (W x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.7 |
||||
|
Maximum value of power in the Bank (W x 10).Write operation
accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.8 |
||||
|
Actual value of voltage in the Bank (V).When Bank does
not have voltage sensor, it returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.9 |
||||
|
Maximum value of voltage in the Bank (V). When Bank does
not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.10 |
||||
|
Actual value of power factor in the Bank (Pf x 10). When
Bank does not have power factor sensor, returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.11 |
||||
|
Maximum value of power factor in the Bank (Pf x 10). When
Bank does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.7.1.12 |
||||
|
The type of Power sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.7.1.13 |
||||
|
The type of Voltage sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.7.1.14 |
||||
|
The type of Power Factor sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.7.1.15 |
cyPMElecOutletTable
table.1.3.6.1.4.1.2925.8.5.8
·
1 row entry
·
15 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMElecOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMElecOutletTable'
Allow operations on elecmon element for outlets
each entry has the information about the elecmon for Outlet.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Serial Port number where the PDU is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.8.1.1 |
||||
|
The number of the PDU unit in the daisy-chained mode
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.8.1.2 |
||||
|
outlet number in the PDU
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.8.1.3 |
||||
|
name of the Outlet.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.8.1.4 |
||||
|
Actual value of current in the Outlet (A x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.5 |
||||
|
Maximum detected value of current in the Outlet (A x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.6 |
||||
|
Actual value of power in the Outlet (W x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.7 |
||||
|
Maximum value of power in the Outlet (W x 10).Write operation
accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.8 |
||||
|
Actual value of voltage in the Outlet (V).When Outlet does
not have voltage sensor, it returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.9 |
||||
|
Maximum value of voltage in the Outlet (V). When Outlet does
not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.10 |
||||
|
Actual value of power factor in the Outlet (Pf x 10). When
Outlet does not have power factor sensor, returns 0. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.11 |
||||
|
Maximum value of power factor in the Outlet (Pf x 10). When
Outlet does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.8.1.12 |
||||
|
The type of Power sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.8.1.13 |
||||
|
The type of Voltage sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.8.1.14 |
||||
|
The type of Power Factor sensor for this elecmon
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.8.1.15 |
cyPMEnvMonTable
table.1.3.6.1.4.1.2925.8.5.9
·
1 row entry
·
8 columns
Uses the vertiv variant from
Command help
/opt/observium/mibs/vertiv.
Walk cyPMEnvMonTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CYCLADES-ACS5K-PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CYCLADES-ACS5K-PM-MIB::cyPMEnvMonTable'
Allow operations on environmental monitors
each entry has the information about the environmental monitors.
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Serial Port number where the PDU is connected.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.9.1.1 |
||||||||||||||||||||
|
The number of the PDU unit in the daisy-chained mode
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.9.1.2 |
||||||||||||||||||||
|
index of the environmental monitor in the PDU.
|
IF-MIBInterfaceIndex Type Constraints: range: 1..2147483647Description: A unique value, greater than zero, for each interface or interface sub-layer in the managed system. It is recommended that values are assigned contiguously starting from 1. The value for each interface sub-layer must … |
.1.3.6.1.4.1.2925.8.5.9.1.3 |
||||||||||||||||||||
|
Name of the environmental monitor.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.2925.8.5.9.1.4 |
||||||||||||||||||||
|
The type of environmental monitor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.9.1.5 |
||||||||||||||||||||
|
The status of Dry-Contact/Water-level/Smoke/Motion monitors.
Dry-Contact sensor: Opened(1), closed(2). Water level: Normal (1), Triggered(2). Smoke sensor: not-detected(1), detected(2). Motion sensor: not-detected(1… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2925.8.5.9.1.6 |
||||||||||||||||||||
|
Actual value of Temperature/Humidity/Air-flow monitors (x 10).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.9.1.7 |
||||||||||||||||||||
|
Maximum detected value of Temperature/Humidity/Air-flow monitor (x 10).
Write operation accepts only 0 for reset action. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2925.8.5.9.1.8 |