tlpCoolingFanSpeed
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.2
Object
column
r/w
Enumeration
Specifies the actual speed of the evaporator fan. Setting the fan speed to auto(6) will enable tlpCoolingAutoFanSpeed; however, on most units getting the fan speed will return the actual fan speed regardless whether auto fan speed is enabled or disabled. The value auto(6) is returned only on units that do not report the actual fan speed when auto fan speed is enabled. Not all values are supported on all cooling units. Invalid values will return an appropriate error when accessed. If not supported, this value will always return ERROR_NO_SUCH_NAME
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.2- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- tlpCoolingConfigEntry
- Table
- tlpCoolingConfigTable
- Siblings
- 24
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | off |
1 | low |
2 | mediumLow |
3 | medium |
4 | mediumHigh |
5 | high |
6 | auto |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpCoolingAutoStart Specifies if the unit should start automatically on power up.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.1 |
| tlpCoolingOffOnInputContact Indicates if the unit should stop cooling when input contact is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.10 |
| tlpCoolingOffOnLeak Indicates if the unit should stop cooling when leak input is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.11 |
| tlpCoolingWaterLeakContactType The water leak contact type. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.12 |
| tlpCoolingAirFilterInterval The number of weeks before the air filter needs to be changed.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | weeks SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.13 |
| tlpCoolingAirFilterAlarm When enabled, an alarm should occur when the maximum number of air filter run hours
has been exceeded. If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | hours Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.14 |
| tlpCoolingMaxAirFilterRunHours The maximum interval for air filter run hours before warning is annunciated.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | hours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.15 |
| tlpCoolingStartTimer The unit will start operate after the specified timer elapsed. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | minutes SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.16 |
| tlpCoolingStopTimer The unit will switch to standby mode after the specified timer elapsed. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | minutes SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.17 |
| tlpCoolingEnergyMode This option enables or disables the energy saving mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.18 |
| tlpCoolingDefrostMode This option enables or disables the defrost mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.19 |
| tlpCoolingRemoteTemperatureSensor This option enables or disables the remote temperature sensor.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.20 |
| tlpCoolingDehumidifyingMode This option enables or disables the dehumidifying mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.21 |
| tlpCoolingFanAlwaysOn This option enables or disables the fan always on.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.22 |
| tlpCoolingQuietMode This option enables or disables the quiet mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.23 |
| tlpCoolingHotGasBypass This option enables or disables the hot gas bypass.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.24 |
| tlpCoolingAutoFanSpeed This option enables or disables the auto fan speed.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.25 |
| tlpCoolingControlType Specifies which temperature is used as a control point. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.3 |
| tlpCoolingDisplayUnits Specifies whether displays output values in Metric or English formats. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.4 |
| tlpCoolingBeepOnKey Specifies whether a beep is emitted when a key is pressed on the unit's display panel. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.5 |
| tlpCoolingInputContactType The input contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.6 |
| tlpCoolingOutputContactType The output contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.7 |
| tlpCoolingOutputRelaySource The alarm level that causes the output relay to activate. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.8 |
| tlpCoolingOutputRelayDefault Type of contact to make when output relay is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.5.5.1.1.9 |