tlpAtsDeviceMainLoadCommand
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.3
Object
column
r/w
Enumeration
Reading this value will always return 0. Setting this value to turnOff(1) will turn off the main output of the ups. Setting this value to turnOn(2) will turn on the main output of the ups. Setting this value to cycle(3) will turn off the main output, then turn it back on.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- tlpAtsDeviceEntry
- Table
- tlpAtsDeviceTable
- Siblings
- 11
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | idle |
1 | turnOff |
2 | turnOn |
3 | cycle |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpAtsDeviceMainLoadState The current state of the main output of the device. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.1 |
| tlpAtsDeviceAggregatePowerFactor The aggregate power factor of all phases. | column | 0.1 Watts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.10 |
| tlpAtsDeviceOutputCurrentPrecision Output current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin
and tlpAtsOutputCurrentMax. These values are all reported in hundredths
(0.01A), which accommodates all m… | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.11 |
| tlpAtsDeviceGeneralFault Indicates whether or not the ats is in a system fault condition. When the
ats is in such a fault condition, the condition can be cleared with
tlpAtsControlResetGeneralFault. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.12 |
| tlpAtsDeviceMainLoadControllable Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.2 |
| tlpAtsDevicePowerOnDelay The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0. Fo… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.4 |
| tlpAtsDeviceTotalInputPowerRating The total input power rating of all phases on the device. This
value may not be supported on all models. If not supported, this
value will always return ERROR_NO_SUCH_NAME. | column | Watts SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.5 |
| tlpAtsDeviceTemperatureC The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | degrees Celsius SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.6 |
| tlpAtsDeviceTemperatureF The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME. | column | degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.7 |
| tlpAtsDevicePhaseImbalance The percentage of imbalance of the three phases. This value is in
the range from 0% imbalance to 100% imbalance. The lower the value,
the better balanced the phases are. If all lo… | column | percent Integer32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.8 |
| tlpAtsDeviceOutputPowerTotal The AC output total power for all circuits. | column | Watts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.2.1.1.9 |