tlpAtsConfigHighVoltageReset

TRIPPLITE-PRODUCTS · .1.3.6.1.4.1.850.1.1.3.4.5.5.1.2

Object

column r/w 0.1 Volts SNMPv2-SMIUnsigned32
If an input connection is disconnected due to over-voltage, the line voltage
on the input source has to fall below this value before the unit re-connects
the AC input connection for the input source. tlpAtsConfigHighVoltageReset is the
same value for both input sources on some units. On such units, changing this
value on one source will change the value on the other source. The maximum value
allowed is dictated by tlpAtsConfigHighVoltageTransfer. On units where this is
the same value for both sources, the minimum value allowed is dictated by the
greater of tlpAtsConfigTransferReset.1 and tlpAtsConfigTransferReset.2. On units
where the value is distinct for each source, the minimum value allowed is
dictated solely by this source's tlpAtsConfigTransferReset. If not supported,
this value will return ERROR_NO_SUCH_NAME.

Context

MIB
TRIPPLITE-PRODUCTS
OID
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.2
Type
column
Access
readwrite
Status
current
Units
0.1 Volts
Parent
tlpAtsConfigVoltageRangeEntry
Table
tlpAtsConfigVoltageRangeTable
Siblings
6

Syntax

0.1 Volts SNMPv2-SMIUnsigned32
Source
SNMPv2-SMIUnsigned32
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295

Related Objects

Sibling Objects