tlpAtsConfigVoltageRangeTable

TRIPPLITE-PRODUCTS · .1.3.6.1.4.1.850.1.1.3.4.5.5

Object

table
The voltage range options in this table is intended to configure the
operating voltages of an ats. This is a sparse dependent table, and will
contain some subset of devices that are atss. All voltage points defined
in this table are listed in a specific order from high to low. All voltage
points must satisfy the conditions and ranges defined for each point. Any
point violating any of the relative limits will be rejected.
          
For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset
be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1%
of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset
(tlpAtsConfigSource2TransferReset) be set higher than
tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no
less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet).
          
*The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound.
The lower limit of line voltage is tlpAtsInputBadTransferVoltageLowerBound. All
minimum and maximum limits for each voltage point are all exclusive unless
indicated otherwise.