tlpAtsConfigBrownoutSet
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.4
Object
This value dictates the voltage level below which the input source goes into a brown out condition. The maximum value allowed is dictated by tlpAtsConfigTransferReset. The minimum value allowed is dictated by tlpAtsConfigTransferSet. If not supported, this value will return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.4- Type
- column
- Access
- readwrite
- Status
- current
- Units
- 0.1 Volts
- Parent
- tlpAtsConfigVoltageRangeEntry
- Table
- tlpAtsConfigVoltageRangeTable
- Siblings
- 6
Syntax
0.1 Volts SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpAtsConfigHighVoltageTransfer The maximum line voltage allowed on the input source before the unit
disconnects the AC input connection. tlpAtsConfigHighVoltageTransfer is the
same value for both input sources … | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.1 |
| tlpAtsConfigHighVoltageReset If an input connection is disconnected due to over-voltage, the line voltage
on the input source has to fall below this value before the unit re-connects
the AC input connection f… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.2 |
| tlpAtsConfigTransferReset If input source voltage level is above this value, a unit connected to
this other input source will transition to this input source (if it is the
preferred source). The maximum va… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.3 |
| tlpAtsConfigTransferSet If input source voltage level falls below this value, a unit connected to
this input source will transition to other input source (if it is in fair
condition as denoted by tlpAtsC… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.5 |
| tlpAtsConfigLowVoltageReset If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. t… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.6 |
| tlpAtsConfigLowVoltageTransfer The minimum line voltage allowed before the unit disconnects the AC input
connection. tlpAtsConfigLowVoltageTransfer is the same value for both input
sources. As such, changing th… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.5.1.7 |