genEquipmentControl

SCTE-HMS-GEN-MIB · .1.3.6.1.4.1.5591.1.6.2.1.22

Object

column optional r/w Enumeration
When written, the appropriate corresponding command action
is sent to the generator.
              
1 = End generator test
2 = Start generator test
3 = Reset latched generator alarms which 
may be preventing a generator start
              
This object is intentionally simplistic to allow for maximum
flexibility.   It IS assumed that the generator has
sufficient intelligence to prevent an overcrank condition.
              
Example 1: From a single SET and corresponding single
'start' command,  the generator may automatically attempt
starting 'n' times before giving up.
              
Example 2: The transponder may be simple and send only the
single 'start' command, and the EMS/end user is responsible
for making 'n' attempts (by performing additional SETs to
this object.)
              
The choice between the methods depends on the specific
application and vendor equipment.

Context

MIB
SCTE-HMS-GEN-MIB
OID
.1.3.6.1.4.1.5591.1.6.2.1.22
Type
column
Access
readwrite
Status
optional
Parent
genDeviceEntry
Table
genDeviceTable
Siblings
28

Syntax

Enumeration

Values & Constraints

Enumerated Values
1stopGenerator
2startGenerator
3resetLatchedAlarms

Related Objects