temperatureCompensationAllowed
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.20.7
Object
scalar
CanStart
Indicates if Temperature Compensation is allowed to start or not. Temperature compensation cannot start if there are no rectifiers with AC power, or if the temperature sensor has failed.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.20.7- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- temperatureCompensation
- Siblings
- 7
Syntax
CanStart
- Source
- CanStart
- Base type
Enumeration
Values & Constraints
Type Values
190 | started |
191 | canStart |
192 | busy |
193 | disabled |
194 | alarmsActive |
195 | sensorFailed |
196 | batteryNotCharged |
197 | noRectifiersNorSolarAvailable |
198 | rectifierOvsd |
199 | noBatteryConfigured |
200 | loadCurrentTooLow |
201 | acFailed |
202 | manualStop |
203 | batteryNotDischarged |
204 | acStateUnavailable |
205 | systemOverloaded |
206 | noPeakLoadReduction |
207 | inLockout |
208 | rectifiersFailed |
209 | rectifiersCommsLost |
210 | systemInOverload |
211 | batteryFuseFail |
212 | batteryTestFail |
213 | bAcFailed |
214 | bAcStateUnavailable |
215 | bNoBatteryConfigured |
216 | bSensorFailed |
217 | bNoRectifiersNorSolarAvailable |
218 | bRectifiersFailed |
219 | bRectifiersCommsLost |
220 | bSystemInOverload |
221 | bBatteryFuseFail |
222 | bBusy |
223 | bBatteryTestFail |
224 | bSystemOverloaded |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| temperatureCompensationState The state of the Temperature Compensation process. To be active, it must be enabled, and the temperature sensor must be working. | scalar | TcState | .1.3.6.1.4.1.1918.2.14.10.70.20.10 |
| temperatureCompensationSlope Bus voltage adjustment rate. Use the value specified by the battery manufacturer. | scalar | 0.01 mV/°C/Cell Float | .1.3.6.1.4.1.1918.2.14.10.70.20.20 |
| temperatureCompensationReferenceTemperature The temperature where no voltage adjustment is applied. Use the value specified by the battery manufacturer. | scalar | 0.1 °C Float | .1.3.6.1.4.1.1918.2.14.10.70.20.30 |
| temperatureCompensationUpperLimit No additional voltage adjustment is made above this temperature. | scalar | 0.1 °C Float | .1.3.6.1.4.1.1918.2.14.10.70.20.40 |
| enableTemperatureCompensation When enabled, the battery charge voltage is automatically adjusted based on temperature. This is recommended by battery manufacturers to optimize battery life. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.20.5 |
| temperatureCompensationLowerLimit No additional voltage adjustment is made below this temperature. | scalar | 0.1 °C Float | .1.3.6.1.4.1.1918.2.14.10.70.20.50 |
| temperatureCompensationOffsetVoltage The adjustment to the bus voltage being applied due to the Temperature Compensation. Offset is zero when the battery temperature equals the reference temperature. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.20.60 |