inDischargeAlarmCondition
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.110.15.200
Object
scalar
r/w
InDischargeAlarmCondition
This specifies if AC present is required for In Discharge alarm to be active.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.110.15.200- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- alarmConfiguration
- Siblings
- 21
Syntax
InDischargeAlarmCondition
- Source
- InDischargeAlarmCondition
- Base type
Enumeration
Values & Constraints
Type Values
0 | always |
1 | onlyWhileAcPresent |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| enableAudibleAlarmIndication Enable/disable audible alarm indication. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.110.15.10 |
| batteryTemperatureHighThreshold Battery Temperature High alarm is activated if the battery temperature is above this value. | scalar | °C Signed8 | .1.3.6.1.4.1.1918.2.14.10.110.15.130 |
| batteryTemperatureLowThreshold Battery Temperature Low alarm is activated if the battery temperature is below this value. | scalar | °C Signed8 | .1.3.6.1.4.1.1918.2.14.10.110.15.140 |
| systemOverloadType The controller can detect a system overload either based on a simple load threshold or based on a redundancy calculation taking into account individual rectifier capacities. | scalar | OverloadAlarmType | .1.3.6.1.4.1.1918.2.14.10.110.15.170 |
| systemOverloadTypeB The controller can detect a system overload either based on a simple load threshold or based on a redundancy calculation taking into account individual rectifier capacities. | scalar | OverloadAlarmType | .1.3.6.1.4.1.1918.2.14.10.110.15.171 |
| systemOverloadRecognitionPeriod The System Overload alarm activates if the condition (see System Overload Type) has been continuously true for this time. It is normally set to several hours so that the alarm doe… | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.110.15.180 |
| systemOverloadThreshold The System Overload alarm activates if the load is above this threshold continuously for the System Overload Recognition Period. Measured as a percentage of total rectifier capaci… | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.110.15.190 |
| systemOverloadThresholdB The System Overload alarm activates if the load is above this threshold continuously for the System Overload Recognition Period. Measured as a percentage of total rectifier capaci… | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.110.15.191 |
| alarmRecognitionPeriod An alarm condition must be continuously active for this period before an alarm is generated. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.110.15.20 |
| batteryCurrentSensorFailRecognitionPeriod If the battery current sensor continuously does not report a valid current for this time, the battery current sensor will be considered failed. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.110.15.220 |
| lowRectifierCapacityRedundancy Redundancy capacity is a percentage of useable rectifier capacity. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.110.15.240 |
| lowRectifierCapacityAlarmThreshold Percentage of Low-Rectifier-Capacity to trigger the Low-Rectifier-Capacity alarm. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.110.15.250 |
| lowRectifierCapacityRecognitionPeriod The Low-Rectifier-Capacity-Alarm activates if the condition has been continuously true for this time. | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.110.15.252 |
| rectifierCapacityBalance The proportion of capacity available to the A side of an A+B system. i.e. 100% means the B side is off. | scalar | % Percentile8Nan | .1.3.6.1.4.1.1918.2.14.10.110.15.260 |
| acFailRecognitionPeriod An AC fail condition must be continuously active for this period before an AC Fail alarm is generated. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.110.15.30 |
| enableHighFloatTracking The alarm thresholds will be increased when the operating voltage is raised by a voltage control function. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.110.15.40 |
| highFloatThreshold High Float alarm is activated if the bus voltage is above this value. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.110.15.50 |
| enableLowFloatTracking The alarm thresholds will be reduced when the operating voltage is lowered by a voltage control function. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.110.15.60 |
| lowFloatThreshold Low Float alarm is activated when the bus voltage is below this value. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.110.15.70 |
| highLoadThreshold High Load alarm is activated if the bus voltage is above this value. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.110.15.80 |
| lowLoadThreshold The Low Load alarm is activated if the bus voltage is below this value. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.110.15.90 |