bclState
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.50.10
Object
scalar
BclState
The state of the Battery Current Limit process.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.50.10- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- batteryCurrentLimit
- Siblings
- 4
Syntax
BclState
- Source
- BclState
- Base type
Enumeration
Values & Constraints
Type Values
110 | disabled |
111 | inoperative |
112 | active |
113 | inactive |
114 | lostControl |
115 | inDeadband |
116 | pending |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| bclLimit BCL maintains the battery current below this value, which is a percentage of the installed C10 Battery Capacity. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.50.30 |
| bclOffsetVoltage The bus voltage adjustment made by Battery Current Limit is applied to the Operating Voltage to produce the Target Voltage. Target Voltage is used as the input to the AVC function. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.50.40 |
| enableBatteryCurrentLimit Protects the batteries from excessive charge current. BCL varies the system voltage in order to maintain battery charge current below the BCL Limit value. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.50.5 |
| bclEngineRunLimit The Battery Current Limit setting when the Engine Run State is 'Running'. BCL maintains the battery current below this value when the Engine Run State is 'Running'. This limit is … | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.50.50 |