batteryTestLockoutRemaining
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.70.8
Object
scalar
s TimeIntervalInSeconds
How much longer the Battery Test is locked-out. Battery Tests cannot be started within 48 hours of an AC failure. If an immediate test is required, set Battery test Interval to zero (this disables the 48 hour lockout).
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.70.8- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- s
- Parent
- batteryTest
- Siblings
- 15
Syntax
s TimeIntervalInSeconds
- Source
- TimeIntervalInSeconds
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| batteryTestState The state of the Battery Test process. | scalar | BatteryTestState | .1.3.6.1.4.1.1918.2.14.10.70.70.10 |
| startBatteryTest This command attempts to start the Battery Test process. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.100 |
| stopBatteryTest This command stops the Battery Test process if it is currently active. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.110 |
| allowBatteryTestDuringLockout Allow immediate battery test without AC fail lockout for the next 1 hour. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.130 |
| bBatteryTestOffsetVoltage The adjustment to the bus voltage being applied due to the Battery Test. While a Battery Test is running, the rectifiers are turned down to force the battery to carry the load. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.140 |
| batteryTestFirstDateTime The date and time that the first Battery Test will occur. Subsequent tests will occur at every Battery Test Interval after that. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.70.15 |
| batteryTestInterval The time between scheduled Battery Tests. The interval period begins at the start of a Battery Test. Zero disables scheduled Battery Tests. Zero also disables the 48 hour lockout … | scalar | d TimeIntervalInDays | .1.3.6.1.4.1.1918.2.14.10.70.70.17 |
| nextBatteryTestStartTime The start time of the next scheduled Battery Test. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.70.20 |
| enableBatteryTest Periodically tests the condition of the battery by reducing the rectifier voltage and allowing the batteries to discharge into the normal load. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.70.3 |
| batteryTestDuration The maximum time a Battery Test process will be active. The Battery Test will pass if the bus voltage remains above the Battery Test Termination Voltage for the duration of the te… | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.70.30 |
| preventBatteryTest Battery test can be prevented by Battery-Fuse-Fail. | scalar | PreventBatteryTest | .1.3.6.1.4.1.1918.2.14.10.70.70.4 |
| batteryTestRemainingTime The time to the end of the currently active Battery Test. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.70.40 |
| batteryTestTerminationVoltage If the bus voltages drops below this value during a Battery Test, then the test fails. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.50 |
| batteryTestOffsetVoltage The adjustment to the bus voltage being applied due to the Battery Test. While a Battery Test is running, the rectifiers are turned down to force the battery to carry the load. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.60 |
| batteryTestStartAllowed Indicates if a Battery Test is allowed to start. Battery Tests cannot start within 48 hours of an AC failure, if there are no rectifiers, if Equalize or Fast Charge is active, if … | scalar | CanStart | .1.3.6.1.4.1.1918.2.14.10.70.70.7 |