batteryTest
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.70
Object
node
No description available.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.70- Type
- node
- Status
- current
- Parent
- controlFunctions
- Siblings
- 13
- Children
- 16
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| voltageControl | node | - | .1.3.6.1.4.1.1918.2.14.10.70.10 |
| temperatureCompensation | node | - | .1.3.6.1.4.1.1918.2.14.10.70.20 |
| resetAhDischarged This command resets controller battery state information (Amp hours discharged) and reverts all control process states to Inactive. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.25 |
| ahDischargedFloatResetRate Once the battery has returned to float the Ah discharged figure is adjust towards zero by this factor multiplied by Battery-State-Threshold. In Solar applications where the amount… | scalar | 0.1 Float | .1.3.6.1.4.1.1918.2.14.10.70.27 |
| equalize | node | - | .1.3.6.1.4.1.1918.2.14.10.70.30 |
| fastCharge | node | - | .1.3.6.1.4.1.1918.2.14.10.70.40 |
| controlState Indicates the state of control process, e.g. Equalize, Fast Charge or Normal. | scalar | ControlState | .1.3.6.1.4.1.1918.2.14.10.70.5 |
| batteryCurrentLimit | node | - | .1.3.6.1.4.1.1918.2.14.10.70.50 |
| lvd | node | - | .1.3.6.1.4.1.1918.2.14.10.70.75 |
| generatorControl | node | - | .1.3.6.1.4.1.1918.2.14.10.70.80 |
| peakLoadReduction | node | - | .1.3.6.1.4.1.1918.2.14.10.70.85 |
| energyMeters | node | - | .1.3.6.1.4.1.1918.2.14.10.70.87 |
| fanController | node | - | .1.3.6.1.4.1.1918.2.14.10.70.88 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| batteryTestState The state of the Battery Test process. | scalar | BatteryTestState | .1.3.6.1.4.1.1918.2.14.10.70.70.10 |
| startBatteryTest This command attempts to start the Battery Test process. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.100 |
| stopBatteryTest This command stops the Battery Test process if it is currently active. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.110 |
| allowBatteryTestDuringLockout Allow immediate battery test without AC fail lockout for the next 1 hour. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.70.130 |
| bBatteryTestOffsetVoltage The adjustment to the bus voltage being applied due to the Battery Test. While a Battery Test is running, the rectifiers are turned down to force the battery to carry the load. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.140 |
| batteryTestFirstDateTime The date and time that the first Battery Test will occur. Subsequent tests will occur at every Battery Test Interval after that. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.70.15 |
| batteryTestInterval The time between scheduled Battery Tests. The interval period begins at the start of a Battery Test. Zero disables scheduled Battery Tests. Zero also disables the 48 hour lockout … | scalar | d TimeIntervalInDays | .1.3.6.1.4.1.1918.2.14.10.70.70.17 |
| nextBatteryTestStartTime The start time of the next scheduled Battery Test. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.70.20 |
| enableBatteryTest Periodically tests the condition of the battery by reducing the rectifier voltage and allowing the batteries to discharge into the normal load. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.70.3 |
| batteryTestDuration The maximum time a Battery Test process will be active. The Battery Test will pass if the bus voltage remains above the Battery Test Termination Voltage for the duration of the te… | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.70.30 |
| preventBatteryTest Battery test can be prevented by Battery-Fuse-Fail. | scalar | PreventBatteryTest | .1.3.6.1.4.1.1918.2.14.10.70.70.4 |
| batteryTestRemainingTime The time to the end of the currently active Battery Test. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.70.40 |
| batteryTestTerminationVoltage If the bus voltages drops below this value during a Battery Test, then the test fails. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.50 |
| batteryTestOffsetVoltage The adjustment to the bus voltage being applied due to the Battery Test. While a Battery Test is running, the rectifiers are turned down to force the battery to carry the load. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.70.60 |
| batteryTestStartAllowed Indicates if a Battery Test is allowed to start. Battery Tests cannot start within 48 hours of an AC failure, if there are no rectifiers, if Equalize or Fast Charge is active, if … | scalar | CanStart | .1.3.6.1.4.1.1918.2.14.10.70.70.7 |
| batteryTestLockoutRemaining How much longer the Battery Test is locked-out. Battery Tests cannot be started within 48 hours of an AC failure. If an immediate test is required, set Battery test Interval to ze… | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.70.8 |