upsAdvTestCalibrationResults
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.7.2.6
Object
scalar
mandatory
Enumeration
The results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidCalibration(2) indicates last calibration did
not take place since the battery capacity was below
100%.
Value calibrationInProgress(3) means a calibration
is occurring now.
Value refused(4) means the test was refused, it did not take place.
Value aborted(5) indicates the test started but either someone cancelled it or
the system encountered an error.
Value pending(6) the test will commence shortly.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.7.2.6- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsAdvTest
- Siblings
- 15
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | ok |
2 | invalidCalibration |
3 | calibrationInProgress |
4 | refused |
5 | aborted |
6 | pending |
7 | unknown |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvTestDiagnosticSchedule mandatory The UPS system's automatic battery test schedule. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.1 |
| upsAdvTestBatteryInterval mandatory The UPS system's automatic battery test period. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.10 |
| upsAdvTestCalibrationLastSuccessfulDate mandatory The latest date when the UPS performed a successful runtime calibration test.
The format is YYYY-MM-DD | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.11 |
| upsAdvTestBatteryLastSuccessfulDate mandatory The latest date when the UPS performed a successful battery diagnostic test (battery monitoring test).
The format is YYYY-MM-DD | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.12 |
| upsAdvTestBatteryLastDate optional The latest date when the UPS performed a battery diagnostic test (battery monitoring test),
regardless of the test result.The format is YYYY-MM-DD.
If not defined, return 2000-01-… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.13 |
| upsAdvTestBatteryProcessStatus mandatory The results of the latest battery diagnostic test (battery monitoring test).
ok(1) indicates a successful completion of the test.
preconditionNotMeet(2) indicates that the test di… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.14 |
| upsAdvTestBatteryConditionStatus mandatory Result of the latest successful test
1 = unknown
2 = battery OK
3 = battery capacity decreased
4 = battery defect
5 = indicate that no battery is present (no battery, battery brea… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.15 |
| upsAdvTestDiagnosticsBatteryInterval mandatory The battery test is a diagnostic test (also referred to as battery monitoring test).
The test will be performed on the day stated in upsAdvTestDiagnosticDay
and at the time stated… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.16 |
| upsAdvTestDiagnostics mandatory Setting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The v… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.2 |
| upsAdvTestDiagnosticsResults mandatory The results of the last UPS diagnostics test performed. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.3 |
| upsAdvTestLastDiagnosticsDate mandatory The date the last UPS diagnostics test was performed in
mm/dd/yy format. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.4 |
| upsAdvTestRuntimeCalibration mandatory Setting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100%.
The test runs until capa… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.5 |
| upsAdvTestCalibrationDate mandatory The date the last UPS runtime calibration was
performed in mm/dd/yy format. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.7 |
| upsAdvTestDiagnosticTime mandatory The time of the day to perform automatic battery test.
Expressed in 24 hour notation - hh:mm. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.8 |
| upsAdvTestDiagnosticDay mandatory The day of the week to perform automatic battery test. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.9 |