upsAdvTest
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.7.2
Object
node
No description available.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.7.2- Type
- node
- Parent
- upsTest
- Siblings
- 1
- Children
- 16
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBasicTest | node | - | .1.3.6.1.4.1.318.1.1.1.7.1 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvTestDiagnosticSchedule mandatory The UPS system's automatic battery test schedule. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.1 |
| upsAdvTestBatteryInterval mandatory The UPS system's automatic battery test period. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.10 |
| upsAdvTestCalibrationLastSuccessfulDate mandatory The latest date when the UPS performed a successful runtime calibration test.
The format is YYYY-MM-DD | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.11 |
| upsAdvTestBatteryLastSuccessfulDate mandatory The latest date when the UPS performed a successful battery diagnostic test (battery monitoring test).
The format is YYYY-MM-DD | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.12 |
| upsAdvTestBatteryLastDate optional The latest date when the UPS performed a battery diagnostic test (battery monitoring test),
regardless of the test result.The format is YYYY-MM-DD.
If not defined, return 2000-01-… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.13 |
| upsAdvTestBatteryProcessStatus mandatory The results of the latest battery diagnostic test (battery monitoring test).
ok(1) indicates a successful completion of the test.
preconditionNotMeet(2) indicates that the test di… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.14 |
| upsAdvTestBatteryConditionStatus mandatory Result of the latest successful test
1 = unknown
2 = battery OK
3 = battery capacity decreased
4 = battery defect
5 = indicate that no battery is present (no battery, battery brea… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.15 |
| upsAdvTestDiagnosticsBatteryInterval mandatory The battery test is a diagnostic test (also referred to as battery monitoring test).
The test will be performed on the day stated in upsAdvTestDiagnosticDay
and at the time stated… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.16 |
| upsAdvTestDiagnostics mandatory Setting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The v… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.2 |
| upsAdvTestDiagnosticsResults mandatory The results of the last UPS diagnostics test performed. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.3 |
| upsAdvTestLastDiagnosticsDate mandatory The date the last UPS diagnostics test was performed in
mm/dd/yy format. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.4 |
| upsAdvTestRuntimeCalibration mandatory Setting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100%.
The test runs until capa… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.5 |
| upsAdvTestCalibrationResults mandatory The results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidCalibration(2) indicates last calibration did
n… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.6 |
| upsAdvTestCalibrationDate mandatory The date the last UPS runtime calibration was
performed in mm/dd/yy format. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.7 |
| upsAdvTestDiagnosticTime mandatory The time of the day to perform automatic battery test.
Expressed in 24 hour notation - hh:mm. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.7.2.8 |
| upsAdvTestDiagnosticDay mandatory The day of the week to perform automatic battery test. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.7.2.9 |