upsAdvTestBatteryProcessStatus

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.7.2.14

Object

scalar mandatory Enumeration
The results of the latest battery diagnostic test (battery monitoring test).
ok(1) indicates a successful completion of the test.
preconditionNotMeet(2) indicates that the test did not start, due to low capacity or low load.
batteryTestInProgress(3) indicates that a test is in progress.
refused(4) indicates that the test was refused and did not take place.
aborted(5) indicates that the test started but it was either cancelled or the system encountered an error.
pending(6) the test will commence shortly.
noBatteryPresent(8) indicates that no battery is present (no battery, battery breaker open, etc.) to perform the battery diagnostic test.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.7.2.14
Type
scalar
Access
readonly
Status
mandatory
Parent
upsAdvTest
Siblings
15

Syntax

Enumeration

Values & Constraints

Enumerated Values
1ok
2preconditionNotMeet
3batteryTestInProgress
4refused
5aborted
6pending
7unknown
8noBatteryPresent

Related Objects

Sibling Objects