dm3ConfigConvFailSafe
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.7.2.4.2.1.3
Object
scalar
mandatory
r/w
Integer32
Converter Fail Safe point. This OID represents the value sent to converter controllers
to use in the event of communications loss with the Master Controller or Master Controller
board failure.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.7.2.4.2.1.3- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- dm3ConfigConvThresh
- Siblings
- 6
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dm3ConfigConvHighVoltThresh mandatory Converter high voltage threshold. If converter voltage exceeds threshold
a converter high voltage alarm will occur.
Values are represented in thousandths of Volts (mV)… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.1 |
| dm3ConfigConvLowVoltThresh mandatory Converter low voltage threshold. If converter voltage exceeds threshold
a converter low voltage alarm will occur.
Values are represented in thousandths of Volts (mV).
… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.2 |
| dm3ConfigConvSetPoint mandatory Converter Set point. This OID represents the initial set point used in the
voltage control loop.
Units are thousandths of Volts (mV).
Attempts to set the value above o… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.4 |
| dm3ConfigConvFailMax mandatory Converter Fail Maximum limit. This OID represents the value sent to the converter
controllers to define the maximum set point allowed.
Units are thousandths of Volts (… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.5 |
| dm3ConfigConvFailMin mandatory Converter Fail Minimum limit. This OID represents the value sent to the converter
controllers to define the minimum set point allowed.
Units are thousandths of Volts (… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.6 |
| dm3ConfigConvFailComm mandatory Converter Communication Fail timeout. This OID represents the time interval in which there is no
communication between the converter and the master controller at which the conver… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.4.2.1.7 |