dm3ConfigBattHighTempThresh
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.7.2.3.9
Object
scalar
mandatory
r/w
Integer32
Battery high temperature threshold. If system battery temperature exceeds threshold
a battery high temperature alarm will occur.
Values are represented in thousandths of a degree.
Units are displayed in the scale shown in
the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.7.2.3.9- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- dm3ConfigBattery
- Siblings
- 18
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dm3ConfigBattFloatVolt mandatory Battery Float Voltage. This setting controls the power plant voltage.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.1 |
| dm3ConfigBattHighTempAlarm mandatory For the Battery High Temperature Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.10 |
| dm3ConfigBattLowTempThresh mandatory Battery low temperature threshold. If system battery temperature is under threshold
a battery low temperature alarm will occur.
Values are represented in thousandths o… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.11 |
| dm3ConfigBattLowTempAlarm mandatory For the Battery Low Temperature Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be a… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.12 |
| dm3ConfigBattAmpHour mandatory Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.13 |
| dm3ConfigCompMethod mandatory This OID is used to configure and get the state of the battery
temperature compensation.
Setting this OID to tempcompOn (1) will enable/turn on the battery temperature … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.14 |
| dm3ConfigCompTempCoeff mandatory Compensation Temperature Coefficient. (uV/degC/cell).
Units are presented in microvolts.
Attempts to set the value above or below the acceptable range of the powerplant… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.15 |
| dm3ConfigHighKneeTemp mandatory High Knee for temperature compensation: Compensation temperature coefficient
becomes 0mV/degC/cell.
Values are represented in thousandths of degrees Celsius.
Attempts … | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.16 |
| dm3ConfigLowKneeTemp mandatory Low Knee for temperature compensation: Compensation temperature coefficient
becomes 0mV/degC/cell.
Values are represented in thousandths of degrees Celsius.
Attempts t… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.17 |
| dm3ConfigBattHwCurrentAlarm mandatory For the Battery Current Hardware Alarm (indicating current is outside realistic
limits, or a possible measurement fault;
Setting this OID to alarmIgnore (1) results in the alarm c… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.18 |
| dm3ConfigBattHwTempAlarm mandatory For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic
limits, or a possible measurement fault;
Setting this OID to alarmIgnore (1) results in the… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.19 |
| dm3ConfigBattMaxRecharge mandatory Battery Maximum Recharge Rate. This setting controls the battery max
recharge rate. The value is based on C/20 for 240 AHr battery string.
Values are represented in t… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.2 |
| dm3ConfigBattDischargeThresh mandatory Battery discharge threshold. If battery output current exceeds threshold
a battery discharge alarm will occur.
Values are represented in thousandths of Amps (mA).
Atte… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.3 |
| dm3ConfigBattDischargeAlarm mandatory For the Battery Discharge Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activat… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.4 |
| dm3ConfigBattHighVoltThresh mandatory Battery high voltage threshold. If system battery voltage exceeds threshold
a battery high voltage alarm will occur.
Values are represented in thousandths of Volts (mV… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.5 |
| dm3ConfigBattHighVoltAlarm mandatory For the Battery High Voltage Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be acti… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.6 |
| dm3ConfigBattLowVoltThresh mandatory Battery low voltage threshold. If system battery voltage is under threshold
a battery low voltage alarm will occur.
Values are represented in thousandths of Volts (mV)… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.3.7 |
| dm3ConfigBattLowVoltAlarm mandatory For the Battery Low Voltage Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activ… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.3.8 |