airFMSysHumSetpoint
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.6.3
Object
scalar
mandatory
r/w
Integer32
The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpoint. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.