airFMSysHumDeadband
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.6.4
Object
scalar
mandatory
r/w
Integer32
The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.4.6.4- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMSysHumidify
- Siblings
- 6
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airFMSysHumState mandatory Set the mode to enabled or disabled. Disabled modes
will not operate, and you cannot make changes to their
settings while they are disabled.
A value of notApplicable indicates tha… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.6.1 |
| airFMSysHumEssFunction mandatory Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notA… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.6.2 |
| airFMSysHumSetpoint mandatory The target value for the selected control sensor air
for this mode. It must be at least 1.0 % RH below
the dehumidification setpoint. Measured in tenths of
percent relative humid… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.6.3 |
| airFMSysHumCtrlSetting mandatory Set the method to control the humidity in the room.
The two methods are Relative Humidity (RH) or Dew
Point of the selected control sensor air. The dew
point method helps correct … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.6.5 |
| airFMSysActualHumCtrl mandatory The humidity control method the system is using.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.6.6 |
| airFMSysHumSensBand mandatory The percentage of relative humidity below the
setpoint at which the humidifier will output at 100%
of capacity. Measured in percent relative humidity.
A value of -2147483648 indi… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.6.7 |