rPDU2OutletMeteredStatusIndex
PowerNet-Inova ·
.1.3.6.1.4.1.63131.1.1.26.9.4.3.1.1
Object
column
mandatory
Integer32
The index to the Rack PDU metered status table entry
Context
- MIB
- PowerNet-Inova
- OID
.1.3.6.1.4.1.63131.1.1.26.9.4.3.1.1- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2OutletMeteredStatusEntry
- Table
- rPDU2OutletMeteredStatusTable
- Siblings
- 15
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2OutletMeteredStatusPeakPowerStartTime mandatory Indicates the start date and time that this metered
outlet began recording peak power observations | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.10 |
| rPDU2OutletMeteredStatusEnergy mandatory A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.11 |
| rPDU2OutletMeteredStatusReceptacleType mandatory Indicates receptacle type for the outlet. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.12 |
| rPDU2OutletMeteredStatusExternalLink mandatory Each RPDU outlet can have its own external web URL link.
This can be configured in the rPDU2OutletMeteredConfigExternalLink OID.
When this link is clicked in the web interface,… | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.13 |
| rPDU2OutletMeteredStatusPowerFactor mandatory The power factor of the Rack PDU outlet in hundredths. Models that do not support this feature
will respond to this OID with a value of -1. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.14 |
| rPDU2OutletMeteredStatusApparentPower mandatory The apparent power consumption of the Rack PDU outlet load in hundredths of kiloVoltAmps (kVA).
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.15 |
| rPDU2OutletMeteredStatusVoltage mandatory Indicates the Voltage, in Volts, of the Rack PDU outlet being queried.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.16 |
| rPDU2OutletMeteredStatusModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.2 |
| rPDU2OutletMeteredStatusName mandatory The user-defined metered outlet ID string | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.3 |
| rPDU2OutletMeteredStatusNumber mandatory The numeric metered outlet ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.4 |
| rPDU2OutletMeteredStatusState mandatory Indicates the present load status of the Rack
PDU metered outlet being queried | column | Enumeration | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.5 |
| rPDU2OutletMeteredStatusCurrent mandatory Indicates the current draw, in tenths
of Amps, of the load on the Rack PDU
outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.6 |
| rPDU2OutletMeteredStatusPower mandatory Indicates the power draw of the load
on the Rack PDU outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.7 |
| rPDU2OutletMeteredStatusPeakPower mandatory Indicates the peak power load draw
on the Rack PDU outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.8 |
| rPDU2OutletMeteredStatusPeakPowerTimestamp mandatory Indicates the date and time that this metered
outlet's peak power consumption occurred | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.9 |