rPDU2OutletMeteredStatusApparentPower
PowerNet-Inova ·
.1.3.6.1.4.1.63131.1.1.26.9.4.3.1.15
Object
column
mandatory
Integer32
The apparent power consumption of the Rack PDU outlet load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with a value of -1.
Context
- MIB
- PowerNet-Inova
- OID
.1.3.6.1.4.1.63131.1.1.26.9.4.3.1.15- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2OutletMeteredStatusEntry
- Table
- rPDU2OutletMeteredStatusTable
- Siblings
- 15
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2OutletMeteredStatusIndex mandatory The index to the Rack PDU metered status table
entry | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.1 |
| rPDU2OutletMeteredStatusPeakPowerStartTime mandatory Indicates the start date and time that this metered
outlet began recording peak power observations | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.10 |
| rPDU2OutletMeteredStatusEnergy mandatory A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.11 |
| rPDU2OutletMeteredStatusReceptacleType mandatory Indicates receptacle type for the outlet. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.12 |
| rPDU2OutletMeteredStatusExternalLink mandatory Each RPDU outlet can have its own external web URL link.
This can be configured in the rPDU2OutletMeteredConfigExternalLink OID.
When this link is clicked in the web interface,… | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.13 |
| rPDU2OutletMeteredStatusPowerFactor mandatory The power factor of the Rack PDU outlet in hundredths. Models that do not support this feature
will respond to this OID with a value of -1. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.14 |
| rPDU2OutletMeteredStatusVoltage mandatory Indicates the Voltage, in Volts, of the Rack PDU outlet being queried.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.16 |
| rPDU2OutletMeteredStatusModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.2 |
| rPDU2OutletMeteredStatusName mandatory The user-defined metered outlet ID string | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.3 |
| rPDU2OutletMeteredStatusNumber mandatory The numeric metered outlet ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.4 |
| rPDU2OutletMeteredStatusState mandatory Indicates the present load status of the Rack
PDU metered outlet being queried | column | Enumeration | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.5 |
| rPDU2OutletMeteredStatusCurrent mandatory Indicates the current draw, in tenths
of Amps, of the load on the Rack PDU
outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.6 |
| rPDU2OutletMeteredStatusPower mandatory Indicates the power draw of the load
on the Rack PDU outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.7 |
| rPDU2OutletMeteredStatusPeakPower mandatory Indicates the peak power load draw
on the Rack PDU outlet being queried | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.8 |
| rPDU2OutletMeteredStatusPeakPowerTimestamp mandatory Indicates the date and time that this metered
outlet's peak power consumption occurred | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.9.4.3.1.9 |