pdug5InputPhaseEntry
PANDUIT-MIB ·
.1.3.6.1.4.1.19536.10.1.2.2.1
Object
row
The input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or 3.
Context
- MIB
- PANDUIT-MIB
- OID
.1.3.6.1.4.1.19536.10.1.2.2.1- Type
- row
- Status
- current
- Parent
- pdug5InputPhaseTable
- Table
- pdug5InputPhaseTable
- Children
- 43
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdug5InputPhaseIndex Index for the pdug5InputEntry table. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.1 |
| pdug5InputPhaseCurrentRating Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are 0.01 amps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.10 |
| pdug5InputPhaseCurrent An input current measurement value. Units are 0.01 amps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.11 |
| pdug5InputPhaseCurrentThStatus Status of the measured input current relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.12 |
| pdug5InputPhaseCurrentThLowerWarning Lower warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.13 |
| pdug5InputPhaseCurrentThLowerCritical Lower critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.14 |
| pdug5InputPhaseCurrentThUpperWarning Upper warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.15 |
| pdug5InputPhaseCurrentThUpperCritical Upper critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.16 |
| pdug5InputPhaseCurrentPercentLoad Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not avail… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.17 |
| pdug5InputPhasePowerMeasType Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.18 |
| pdug5InputPhasePowerVA An input VA value. Units are VA. A negative value indicates
that this object is not available. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.19 |
| pdug5InputPhaseVoltageMeasType Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phas… | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.2 |
| pdug5InputPhasePowerWatts An input Watts value. Units are Watts. A negative value indicates
that this object is not available. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.20 |
| pdug5InputPhasePowerWattHour A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well
A negative… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.21 |
| pdug5InputPhasePowerWattHourTimer Timestamp of when input Watt-hours (inputWh) was last reset. | column | OctetString | .1.3.6.1.4.1.19536.10.1.2.2.1.22 |
| pdug5InputPhasePowerFactor An input PF value. Units are in hundredths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned
as 92. A negative value indicates that this ob… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.23 |
| pdug5InputPhasePowerVAR An input VAR value. Units are VAR. A negative value indicates
that this object is not available. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.24 |
| pdug5InputPhaseVoltageThResetThld The Reset threshold is the number of volts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are 0.1 volts. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.25 |
| pdug5InputPhaseVoltageThChangeDelay The number of consecutive sample that the condition is present before
an alarm is raised. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.26 |
| pdug5InputPhaseVoltageThCtrl Input phase voltage alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
b… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.27 |
| pdug5InputPhaseCurrentThResetThld The Reset threshold is the number of amps the reading needs to fall below
the threshold setting for the condition to be cleared. Units are 0.01 amps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.28 |
| pdug5InputPhaseCurrentThChangeDelay The number of consecutive sample that the condition is present before
an alarm is raised. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.29 |
| pdug5InputPhaseVoltage An input voltage measurement value. Values is in 0.1 V. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.3 |
| pdug5InputPhaseCurrentThCtrl Input phase current alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
b… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.30 |
| pdug5InputPowerThresholdThLowerWarning Lower warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.31 |
| pdug5InputPowerThresholdThLowerCritical Lower critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.32 |
| pdug5InputPowerThresholdThUpperWarning Upper warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.33 |
| pdug5InputPowerThresholdThUpperCritical Upper critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.34 |
| pdug5InputPowerThresholdThResetThld The Reset threshold is the number of watts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are watts. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.35 |
| pdug5InputPowerThresholdThChangeDelay The number of consecutive sample that the condition is present before
an alarm is raised. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.36 |
| pdug5InputPowerThresholdThCtrl Power alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low war… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.37 |
| pdug5InputEnergyThresholdThUpperWarning Upper warning Energy threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.38 |
| pdug5InputEnergyThresholdThUpperCritical Upper critical Energy threshold. Units are in Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.39 |
| pdug5InputPhaseVoltageThStatus Status of the measured input voltage relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.4 |
| pdug5InputEnergyThresholdThResetThld The Reset threshold is the number of watts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are watts. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.40 |
| pdug5InputEnergyThresholdThChangeDelay The number of consecutive sample that the condition is present before
an alarm is raised. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.41 |
| pdug5InputEnergyThresholdThCtrl Energy alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low wa… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.2.1.42 |
| pdug5InputPhasePowerThStatus Status of the measured input current relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.43 |
| pdug5InputPhaseVoltageThLowerWarning Lower warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.5 |
| pdug5InputPhaseVoltageThLowerCritical Lower critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.6 |
| pdug5InputPhaseVoltageThUpperWarning Upper warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.7 |
| pdug5InputPhaseVoltageThUpperCritical Upper critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.8 |
| pdug5InputPhaseCurrentMeasType Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.9 |