lgpPwrBatteryLastCommissionTime

LIEBERT-GP-POWER-MIB · .1.3.6.1.4.1.476.1.42.3.5.1.24

Object

scalar r/w seconds SNMPv2-SMIUnsigned32
The date and time when the battery system was put into service.
This information persists across system reboot events. It is the
responsibility of Service to reset this date/time when the batteries
are replaced. The date and time are determined in seconds since the 
epoch on January 1, 1970.

Context

MIB
LIEBERT-GP-POWER-MIB
OID
.1.3.6.1.4.1.476.1.42.3.5.1.24
Type
scalar
Access
readwrite
Status
current
Units
seconds
Parent
lgpPwrBattery
Siblings
26

Syntax

seconds SNMPv2-SMIUnsigned32
Source
SNMPv2-SMIUnsigned32
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295

Related Objects

Sibling Objects