slcDevRPMShutdownOrder

LANTRONIX-SLC-MIB · .1.3.6.1.4.1.244.1.1.4.7.1.1.21

Object

column Integer32
If a UPS reaches a 'low battery' state and its
slcDevRPMOnLowBattery setting is shutdownAllUPS, this
indicates the order in which this RPM will be shutdown as
all UPSes are shutdown.  All UPSes with a shutdown order of 
'1' will be shutdown first, followed by all UPSes with a 
shutdown order of '2', etc. Shutdown orders are in the range 
of 1 to 49, with 50 being reserved for UPSes that provide 
power to the SLC - they will always be shutdown last. 
A value of 0 indicates that this UPS will not be shutdown. 
Applies to UPS devices only.

Context

MIB
LANTRONIX-SLC-MIB
OID
.1.3.6.1.4.1.244.1.1.4.7.1.1.21
Type
column
Access
readonly
Status
current
Parent
slcDevRPMCfgEntry
Table
slcDevRPMCfgTable
Siblings
27

Syntax

Integer32

Values & Constraints

Object Constraints
range: 0-50

Related Objects

Sibling Objects