upsWellKnownAlarms
GEPARALLELUPS-MIB ·
.1.3.6.1.4.1.818.1.1.10.6.3
Object
node
No description available.
Context
- MIB
- GEPARALLELUPS-MIB
- OID
.1.3.6.1.4.1.818.1.1.10.6.3- Type
- node
- Parent
- upsAlarm
- Siblings
- 3
- Children
- 31
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAlarmsPresent The present number of active alarm conditions.(*) | scalar | SNMPv2-SMIGauge32 | .1.3.6.1.4.1.818.1.1.10.6.1 |
| upsAlarmTable A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at… | table | - | .1.3.6.1.4.1.818.1.1.10.6.2 |
| upsAlarmMaskA Specifies which alarm can be handled by the UPS.
The 'Mask' parameter is a Long Integer32. The meaning
of every bit is the same as for the 'upsAlarmGroupA'
command. A bit having v… | scalar | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.818.1.1.10.6.4 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAlarmBatteryBad One or more batteries have been determined to require
replacement.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.1 |
| upsAlarmBypassBad The Bypass is out of tolerance.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.10 |
| upsAlarmOutputOffAsRequested The UPS has shutdown as requested, i.e., the output
is off.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.11 |
| upsAlarmUpsOffAsRequested The entire UPS has shutdown as commanded.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.12 |
| upsAlarmChargerFailed An uncorrected problem has been detected within the
UPS charger subsystem.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.13 |
| upsAlarmUpsOutputOff The output of the UPS is in the off state.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.14 |
| upsAlarmUpsSystemOff The UPS system is in the off state.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.15 |
| upsAlarmFanFailure The failure of one or more fans in the UPS has been
detected.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.16 |
| upsAlarmFuseFailure The failure of one or more fuses has been detected.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.17 |
| upsAlarmGeneralFault A general fault in the UPS has been detected.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.18 |
| upsAlarmDiagnosticTestFailed The result of the last diagnostic test indicates a
failure.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.19 |
| upsAlarmOnBattery The UPS is drawing power from the batteries.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.2 |
| upsAlarmCommunicationsLost A problem has been encountered in the communications
between the agent and the UPS.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.20 |
| upsAlarmAwaitingPower The UPS output is off and the UPS is awaiting the
return of input power.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.21 |
| upsAlarmShutdownPending A upsShutdownAfterDelay countdown is underway.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.22 |
| upsAlarmShutdownImminent The UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.23 |
| upsAlarmTestInProgress A test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the … | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.24 |
| upsAlarmReceptacleOff The receptacle are switch off | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.25 |
| upsAlarmHighSpeedBusFailure A problem on the High Speed Bus communication is detected | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.26 |
| upsAlarmHighSpeedBusJACRCFailure A CRC problem on the Highspeed Bus JA is detected. | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.27 |
| upsAlarmConnectivityBusFailure A problem on the Connectivity Bus communication is detected | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.28 |
| upsAlarmHighSpeedBusJBCRCFailure A CRC problem on the Highspeed Bus JB is detected. | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.29 |
| upsAlarmLowBattery The remaining battery run-time is less than or equal
to upsConfigLowBattTime.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.3 |
| upsAlarmCurrentSharing The System detects an high current sharing on the parallel system | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.30 |
| upsAlarmDCRipple The System detects an high ripple voltage on one DC link | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.31 |
| upsAlarmDepletedBattery The UPS will be unable to sustain the present load
when and if the utility power is lost.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.4 |
| upsAlarmTempBad A temperature is out of tolerance.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.5 |
| upsAlarmInputBad An input condition is out of tolerance.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.6 |
| upsAlarmOutputBad An output condition (other than OutputOverload) is
out of tolerance.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.7 |
| upsAlarmOutputOverload The output load exceeds the UPS output capacity.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.8 |
| upsAlarmOnBypass The Bypass is presently engaged on the UPS.(*) | node | - | .1.3.6.1.4.1.818.1.1.10.6.3.9 |