WebGraph-Thermo-Hygrometer-US-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
8
Rows
8
Columns
66
.1.3.6.1.4.1.5040.1.2.42.1.2 · 1 row entry · 1 columns
List of sensors.
wtWebGraphThermoHygroSensorEntry entry .1.3.6.1.4.1.5040.1.2.42.1.2.1
List of sensor numbers.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroSensorNo mandatory
Sensor number.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.5040.1.2.42.1.2.1.1
.1.3.6.1.4.1.5040.1.2.42.1.3 · 1 row entry · 1 columns
List of measurement values corresponding to the channel numbers.
wtWebGraphThermoHygroTempValueEntry entry .1.3.6.1.4.1.5040.1.2.42.1.3.1
Measurement values of the sensors.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroTempValue mandatory
Measurement value of the sensor, ASCII, 5 characters in length.
OctetString
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.42.1.3.1.1
.1.3.6.1.4.1.5040.1.2.42.1.4 · 1 row entry · 1 columns
List of binary measurement values corresponding to the channel numbers.
wtWebGraphThermoHygroBinaryTempValueEntry entry .1.3.6.1.4.1.5040.1.2.42.1.4.1
Binary measurement values of the sensors.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroBinaryTempValue mandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an
invalid measured value.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.42.1.4.1.1
.1.3.6.1.4.1.5040.1.2.42.1.8 · 1 row entry · 1 columns
List of measurement values corresponding to the channel numbers.
wtWebGraphThermoHygroTempValuePktEntry entry .1.3.6.1.4.1.5040.1.2.42.1.8.1
Measurement values of the sensors.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroTempValuePkt mandatory
Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point.
OctetString
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.42.1.8.1.1
.1.3.6.1.4.1.5040.1.2.42.3.1.5.2 · 1 row entry · 1 columns
List of alarm indices.
wtWebGraphThermoHygroAlarmIfEntry entry .1.3.6.1.4.1.5040.1.2.42.3.1.5.2.1
Numbers of the alarms.
Indexes
wtWebGraphThermoHygroAlarmNo
Column Syntax OID
wtWebGraphThermoHygroAlarmNo mandatory
Alarm number.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5040.1.2.42.3.1.5.2.1.1
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3 · 1 row entry · 52 columns
List of settings depending on the alarm number.
wtWebGraphThermoHygroAlarmEntry entry .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1
Alarm parameters of the individual alarms.
Indexes
wtWebGraphThermoHygroAlarmNo
Column Syntax OID
wtWebGraphThermoHygroAlarmTrigger mandatory
Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart

Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.1
wtWebGraphThermoHygroAlarmMin mandatory
Minimum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.2
wtWebGraphThermoHygroAlarmMax mandatory
Maximum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.3
wtWebGraphThermoHygroAlarmHysteresis mandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.4
wtWebGraphThermoHygroAlarmDelay mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes).
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.5
wtWebGraphThermoHygroAlarmInterval mandatory
Send interval for alarm messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.6
wtWebGraphThermoHygroAlarmEnable mandatory
Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.7
wtWebGraphThermoHygroAlarmEMailAddr mandatory
E-Mail address for sending the alarm mail to.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.8
wtWebGraphThermoHygroAlarmMailSubject mandatory
Subject line for alarm mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.9
wtWebGraphThermoHygroAlarmMailText mandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.10
wtWebGraphThermoHygroAlarmManagerIP mandatory
Name or IP address of the SNMP Manager which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.11
wtWebGraphThermoHygroAlarmTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.12
wtWebGraphThermoHygroAlarmMailOptions mandatory
Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.13
wtWebGraphThermoHygroAlarmTcpIpAddr mandatory
Name or IP address of the TCP server which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.14
wtWebGraphThermoHygroAlarmTcpPort mandatory
Port number of the TCP server which accepts the trap.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.15
wtWebGraphThermoHygroAlarmTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.16
wtWebGraphThermoHygroAlarmClearMailSubject mandatory
Subject line for alarm clear mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.17
wtWebGraphThermoHygroAlarmClearMailText mandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.18
wtWebGraphThermoHygroAlarmClearTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.19
wtWebGraphThermoHygroAlarmClearTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.20
wtWebGraphThermoHygroAlarmDeltaTemp mandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.21
wtWebGraphThermoHygroAlarmRHMin mandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.22
wtWebGraphThermoHygroAlarmRHMax mandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.23
wtWebGraphThermoHygroAlarmRHHysteresis mandatory
Hysterese rel. Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.24
wtWebGraphThermoHygroAlarmAHMin mandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.25
wtWebGraphThermoHygroAlarmAHMax mandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.26
wtWebGraphThermoHygroAlarmSyslogIpAddr mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.27
wtWebGraphThermoHygroAlarmSyslogPort mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.28
wtWebGraphThermoHygroAlarmSyslogText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.29
wtWebGraphThermoHygroAlarmSyslogClearText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.30
wtWebGraphThermoHygroAlarmFtpDataPort mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.31
wtWebGraphThermoHygroAlarmFtpFileName mandatory
Name of the file including path informations.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.32
wtWebGraphThermoHygroAlarmFtpText mandatory
Message text to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.33
wtWebGraphThermoHygroAlarmFtpClearText mandatory
Alarm clear message to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.34
wtWebGraphThermoHygroAlarmFtpOption mandatory
Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file

Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STOR…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.35
wtWebGraphThermoHygroAlarmTimerCron mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separatley.
1: Minutes Rang…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.36
wtWebGraphThermoHygroAlarmName mandatory
Alert name
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.39
wtWebGraphThermoHygroAlarmActive mandatory
Alert active
1 = ON
0 = OFF
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.40
wtWebGraphThermoHygroAlarmHttpReqAuthEnable mandatory
Binary coded options, select only one option at the same time:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : HHTP Request Authentication enable
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.61
wtWebGraphThermoHygroAlarmHttpReqAuthUser mandatory
HTTP Request: User
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.62
wtWebGraphThermoHygroAlarmHttpReqAuthPassword mandatory
HTTP Request: Password
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.63
wtWebGraphThermoHygroAlarmHttpReqSetUrl mandatory
HTTP Request: Set URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.64
wtWebGraphThermoHygroAlarmHttpReqClearUrl mandatory
HTTP Request: Clear URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.65
wtWebGraphThermoHygroAlarmHttpReqServerPort mandatory
HTTP Request: Server Port
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.66
wtWebGraphThermoHygroAlarmMqttTopicPath mandatory
MQTT Publish: Topic path
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.67
wtWebGraphThermoHygroAlarmMqttTopicSetTopic mandatory
MQTT Publish: Topic SET message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.68
wtWebGraphThermoHygroAlarmMqttTopicClear mandatory
MQTT Publish: Topic CLEAR message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.69
wtWebGraphThermoHygroAlarmSensorLostSelection mandatory
Binary coded options:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 2-7: unused
Bit 1 : Sensor 1
Bit 0 : Sensor 0
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.70
wtWebGraphThermoHygroAlarmLimitWindow mandatory
If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE
the alarm is generated when the measured value is lower than the mini…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.71
wtWebGraphThermoHygroAlarmSnmpManagerPort mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.76
wtWebGraphThermoHygroAlarmMqttQoS mandatory
Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: QoS 0
Bit 1: QoS 1
Bit 2: QoS 2
Bit 3-7:unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.77
wtWebGraphThermoHygroAlarmMqttRetain mandatory
Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : retain enable
Bit 1-7 : unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.78
.1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3 · 1 row entry · 2 columns
List of sensor colors for the praphical presentation.
wtWebGraphThermoHygroSensorColorEntry entry .1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1
Numbers of the sensors.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroGraphicsSensorColor mandatory
Color of the sensors at the praphical presention.
OctetStringr/w
Constraints:
range: 3-3
.1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.1
wtWebGraphThermoHygroGraphicsSelectScale mandatory
Assignes one of 4 scales to a sensor:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Use Scale 1
Bit 1 : Use Scale 2
Bit 2-7: unused
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.2
.1.3.6.1.4.1.5040.1.2.42.3.2.1 · 1 row entry · 7 columns
List of settings depending on the sensor number.
wtWebGraphThermoHygroPortEntry entry .1.3.6.1.4.1.5040.1.2.42.3.2.1.1
Sensor parameters for the individual sensors.
Indexes
wtWebGraphThermoHygroSensorNo
Column Syntax OID
wtWebGraphThermoHygroPortName mandatory
Name of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.1
wtWebGraphThermoHygroPortText mandatory
Description of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.2
wtWebGraphThermoHygroPortOffset1 mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.3
wtWebGraphThermoHygroPortTemperature1 mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.4
wtWebGraphThermoHygroPortOffset2 mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.5
wtWebGraphThermoHygroPortTemperature2 mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.6
wtWebGraphThermoHygroPortComment mandatory
Offset calibration: informations of date, name of operator, reference devices.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.7