wtWebGraphThermoHygroAlarmMqttTopicSetTopic
WebGraph-Thermo-Hygrometer-US-MIB ·
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.68
Object
column
mandatory
r/w
OctetString
MQTT Publish: Topic SET message
Context
- MIB
- WebGraph-Thermo-Hygrometer-US-MIB
- OID
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.68- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebGraphThermoHygroAlarmEntry
- Table
- wtWebGraphThermoHygroAlarmTable
- Siblings
- 51
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wtWebGraphThermoHygroAlarmTrigger mandatory Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Senso… | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.1 |
| wtWebGraphThermoHygroAlarmMailText mandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.10 |
| wtWebGraphThermoHygroAlarmManagerIP mandatory Name or IP address of the SNMP Manager which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.11 |
| wtWebGraphThermoHygroAlarmTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.12 |
| wtWebGraphThermoHygroAlarmMailOptions mandatory Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.13 |
| wtWebGraphThermoHygroAlarmTcpIpAddr mandatory Name or IP address of the TCP server which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.14 |
| wtWebGraphThermoHygroAlarmTcpPort mandatory Port number of the TCP server which accepts the trap. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.15 |
| wtWebGraphThermoHygroAlarmTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.16 |
| wtWebGraphThermoHygroAlarmClearMailSubject mandatory Subject line for alarm clear mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.17 |
| wtWebGraphThermoHygroAlarmClearMailText mandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.18 |
| wtWebGraphThermoHygroAlarmClearTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.19 |
| wtWebGraphThermoHygroAlarmMin mandatory Minimum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.2 |
| wtWebGraphThermoHygroAlarmClearTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.20 |
| wtWebGraphThermoHygroAlarmDeltaTemp mandatory Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.21 |
| wtWebGraphThermoHygroAlarmRHMin mandatory Minimum rel. Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.22 |
| wtWebGraphThermoHygroAlarmRHMax mandatory Maximum rel.Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.23 |
| wtWebGraphThermoHygroAlarmRHHysteresis mandatory Hysterese rel. Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.24 |
| wtWebGraphThermoHygroAlarmAHMin mandatory Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.25 |
| wtWebGraphThermoHygroAlarmAHMax mandatory Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.26 |
| wtWebGraphThermoHygroAlarmSyslogIpAddr mandatory IP address of the syslog server to which the Webio device should send syslog messages. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.27 |
| wtWebGraphThermoHygroAlarmSyslogPort mandatory Port number of the syslog server to which the Webio device should send syslog messages. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.28 |
| wtWebGraphThermoHygroAlarmSyslogText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.29 |
| wtWebGraphThermoHygroAlarmMax mandatory Maximum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.3 |
| wtWebGraphThermoHygroAlarmSyslogClearText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.30 |
| wtWebGraphThermoHygroAlarmFtpDataPort mandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.31 |
| wtWebGraphThermoHygroAlarmFtpFileName mandatory Name of the file including path informations. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.32 |
| wtWebGraphThermoHygroAlarmFtpText mandatory Message text to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.33 |
| wtWebGraphThermoHygroAlarmFtpClearText mandatory Alarm clear message to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.34 |
| wtWebGraphThermoHygroAlarmFtpOption mandatory Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
… | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.35 |
| wtWebGraphThermoHygroAlarmTimerCron mandatory This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are… | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.36 |
| wtWebGraphThermoHygroAlarmName mandatory Alert name | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.39 |
| wtWebGraphThermoHygroAlarmHysteresis mandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.4 |
| wtWebGraphThermoHygroAlarmActive mandatory Alert active
1 = ON
0 = OFF | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.40 |
| wtWebGraphThermoHygroAlarmDelay mandatory Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.5 |
| wtWebGraphThermoHygroAlarmInterval mandatory Send interval for alarm messages. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.6 |
| wtWebGraphThermoHygroAlarmHttpReqAuthEnable mandatory Binary coded options, select only one option at the same time:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : HHTP Request Authentication enable | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.61 |
| wtWebGraphThermoHygroAlarmHttpReqAuthUser mandatory HTTP Request: User | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.62 |
| wtWebGraphThermoHygroAlarmHttpReqAuthPassword mandatory HTTP Request: Password | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.63 |
| wtWebGraphThermoHygroAlarmHttpReqSetUrl mandatory HTTP Request: Set URL | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.64 |
| wtWebGraphThermoHygroAlarmHttpReqClearUrl mandatory HTTP Request: Clear URL | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.65 |
| wtWebGraphThermoHygroAlarmHttpReqServerPort mandatory HTTP Request: Server Port | column | Integer32 | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.66 |
| wtWebGraphThermoHygroAlarmMqttTopicPath mandatory MQTT Publish: Topic path | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.67 |
| wtWebGraphThermoHygroAlarmMqttTopicClear mandatory MQTT Publish: Topic CLEAR message | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.69 |
| wtWebGraphThermoHygroAlarmEnable mandatory Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.7 |
| wtWebGraphThermoHygroAlarmSensorLostSelection mandatory Binary coded options:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 2-7: unused
Bit 1 : Sensor 1
Bit 0 : Sensor 0 | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.70 |
| wtWebGraphThermoHygroAlarmLimitWindow mandatory If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE
the alarm is generated when t… | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.71 |
| wtWebGraphThermoHygroAlarmSnmpManagerPort mandatory Port number of the SNMP Manager to which the Webio device should send SNMP traps. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.76 |
| wtWebGraphThermoHygroAlarmMqttQoS mandatory Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: QoS 0
Bit 1: QoS 1
Bit 2: QoS 2
Bit 3-7:unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.77 |
| wtWebGraphThermoHygroAlarmMqttRetain mandatory Binary coded value:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : retain enable
Bit 1-7 : unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.78 |
| wtWebGraphThermoHygroAlarmEMailAddr mandatory E-Mail address for sending the alarm mail to. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.8 |
| wtWebGraphThermoHygroAlarmMailSubject mandatory Subject line for alarm mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.9 |