WebGraph-OLD-Thermo-Hygrometer-US-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
7
Rows
7
Columns
49
.1.3.6.1.4.1.5040.1.2.9.1.2 · 1 row entry · 1 columns
List of sensors.
wtWebGraphThermHygroSensorEntry entry .1.3.6.1.4.1.5040.1.2.9.1.2.1
List of sensor numbers.
Indexes
wtWebGraphThermHygroSensorNo
Column Syntax OID
wtWebGraphThermHygroSensorNo mandatory
Sensor number.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.5040.1.2.9.1.2.1.1
.1.3.6.1.4.1.5040.1.2.9.1.3 · 1 row entry · 1 columns
List of measurement values corresponding to the channel numbers.
wtWebGraphThermHygroTempValueEntry entry .1.3.6.1.4.1.5040.1.2.9.1.3.1
Measurement values of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
Column Syntax OID
wtWebGraphThermHygroTempValue mandatory
Measurement value of the sensor, ASCII, 5 characters in length.
OctetString
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.9.1.3.1.1
.1.3.6.1.4.1.5040.1.2.9.1.4 · 1 row entry · 1 columns
List of binary measurement values corresponding to the channel numbers.
wtWebGraphThermHygroBinaryTempValueEntry entry .1.3.6.1.4.1.5040.1.2.9.1.4.1
Binary measurement values of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
Column Syntax OID
wtWebGraphThermHygroBinaryTempValue mandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an
invalid measured value.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.9.1.4.1.1
.1.3.6.1.4.1.5040.1.2.9.3.1.4.4 · 1 row entry · 1 columns
List of sensor colors for the praphical presentation.
wtWebGraphThermHygroSensorColorEntry entry .1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1
Index numbers of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
Column Syntax OID
wtWebGraphThermHygroSensorColor mandatory
Color of the sensors at the praphical presention.
OctetStringr/w
Constraints:
range: 3-3
.1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1.1
.1.3.6.1.4.1.5040.1.2.9.3.1.5.2 · 1 row entry · 1 columns
List of alarm indices.
wtWebGraphThermHygroAlarmIfEntry entry .1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1
Numbers of the alarms.
Indexes
wtWebGraphThermHygroAlarmNo
Column Syntax OID
wtWebGraphThermHygroAlarmNo mandatory
Alarm number.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1.1
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3 · 1 row entry · 36 columns
List of settings depending on the alarm number.
wtWebGraphThermHygroAlarmEntry entry .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1
Alarm parameters of the individual alarms.
Indexes
wtWebGraphThermHygroAlarmNo
Column Syntax OID
wtWebGraphThermHygroAlarmTrigger mandatory
Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart

Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1
wtWebGraphThermHygroAlarmMin mandatory
Minimum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2
wtWebGraphThermHygroAlarmMax mandatory
Maximum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3
wtWebGraphThermHygroAlarmHysteresis mandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4
wtWebGraphThermHygroAlarmDelay mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes).
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5
wtWebGraphThermHygroAlarmInterval mandatory
Send interval for alarm messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6
wtWebGraphThermHygroAlarmEnable mandatory
Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7
wtWebGraphThermHygroAlarmEMailAddr mandatory
E-Mail address for sending the alarm mail to.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8
wtWebGraphThermHygroAlarmMailSubject mandatory
Subject line for alarm mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9
wtWebGraphThermHygroAlarmMailText mandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10
wtWebGraphThermHygroAlarmManagerIP mandatory
Name or IP address of the SNMP Manager which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11
wtWebGraphThermHygroAlarmTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12
wtWebGraphThermHygroAlarmMailOptions mandatory
Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13
wtWebGraphThermHygroAlarmTcpIpAddr mandatory
Name or IP address of the TCP server which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14
wtWebGraphThermHygroAlarmTcpPort mandatory
Port number of the TCP server which accepts the trap.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15
wtWebGraphThermHygroAlarmTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16
wtWebGraphThermHygroAlarmClearMailSubject mandatory
Subject line for alarm clear mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17
wtWebGraphThermHygroAlarmClearMailText mandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18
wtWebGraphThermHygroAlarmClearTrapText mandatory
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19
wtWebGraphThermHygroAlarmClearTcpText mandatory
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20
wtWebGraphThermHygroAlarmDeltaTemp mandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21
wtWebGraphThermHygroAlarmRHMin mandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22
wtWebGraphThermHygroAlarmRHMax mandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23
wtWebGraphThermHygroAlarmRHHysteresis mandatory
Hysterese rel. Humidity in percent with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24
wtWebGraphThermHygroAlarmAHMin mandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25
wtWebGraphThermHygroAlarmAHMax mandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26
wtWebGraphThermHygroAlarmSyslogIpAddr mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27
wtWebGraphThermHygroAlarmSyslogPort mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28
wtWebGraphThermHygroAlarmSyslogText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29
wtWebGraphThermHygroAlarmSyslogClearText mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30
wtWebGraphThermHygroAlarmFtpDataPort mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31
wtWebGraphThermHygroAlarmFtpFileName mandatory
Name of the file including path informations.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32
wtWebGraphThermHygroAlarmFtpText mandatory
Message text to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33
wtWebGraphThermHygroAlarmFtpClearText mandatory
Alarm clear message to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34
wtWebGraphThermHygroAlarmFtpOptions mandatory
Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file

Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STOR…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35
wtWebGraphThermHygroAlarmTimerCron mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separatley.
1: Minutes Rang…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36
.1.3.6.1.4.1.5040.1.2.9.3.2.1 · 1 row entry · 8 columns
List of settings depending on the sensor number.
wtWebGraphThermHygroPortEntry entry .1.3.6.1.4.1.5040.1.2.9.3.2.1.1
Sensor parameters for the individual sensors.
Indexes
wtWebGraphThermHygroSensorNo
Column Syntax OID
wtWebGraphThermHygroPortName mandatory
Name of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.1
wtWebGraphThermHygroPortText mandatory
Description of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.2
wtWebGraphThermHygroPortOffset1 mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.3
wtWebGraphThermHygroPortTemperature1 mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.4
wtWebGraphThermHygroPortOffset2 mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.5
wtWebGraphThermHygroPortTemperature2 mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.6
wtWebGraphThermHygroPortComment mandatory
Offset calibration: informations of date, name of operator, reference devices.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.7
wtWebGraphThermHygroPortSensorSelect mandatory
Binary coded options for sensor 1:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : PT100
Bit 1 : PT1000 (default)
Bit 2-7: unused

Binary coded options for sensor 2:
Octet 1: unuse…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.9.3.2.1.1.8