WebGraph-OLD-Thermo-Hygrometer-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
49
.1.3.6.1.4.1.5040.1.2.9.1.2
·
1 row entry
·
1 columns
List of sensors.
List of sensor numbers.
Indexes
wtWebGraphThermHygroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroSensorNo
mandatory
Sensor number.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.9.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.9.1.3
·
1 row entry
·
1 columns
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroTempValue
mandatory
Measurement value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.9.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.9.1.4
·
1 row entry
·
1 columns
List of binary measurement values corresponding to the channel numbers.
Binary measurement values of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroBinaryTempValue
mandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an invalid measured value. |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.9.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.9.3.1.4.4
·
1 row entry
·
1 columns
List of sensor colors for the praphical presentation.
Index numbers of the sensors.
Indexes
wtWebGraphThermHygroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroSensorColor
mandatory
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1.1 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
wtWebGraphThermHygroAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroAlarmNo
mandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3
·
1 row entry
·
36 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
wtWebGraphThermHygroAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroAlarmTrigger
mandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1 |
|
wtWebGraphThermHygroAlarmMin
mandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2 |
|
wtWebGraphThermHygroAlarmMax
mandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3 |
|
wtWebGraphThermHygroAlarmHysteresis
mandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 |
|
wtWebGraphThermHygroAlarmDelay
mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5 |
|
wtWebGraphThermHygroAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6 |
|
wtWebGraphThermHygroAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7 |
|
wtWebGraphThermHygroAlarmEMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8 |
|
wtWebGraphThermHygroAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9 |
|
wtWebGraphThermHygroAlarmMailText
mandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10 |
|
wtWebGraphThermHygroAlarmManagerIP
mandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11 |
|
wtWebGraphThermHygroAlarmTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12 |
|
wtWebGraphThermHygroAlarmMailOptions
mandatory
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13 |
|
wtWebGraphThermHygroAlarmTcpIpAddr
mandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14 |
|
wtWebGraphThermHygroAlarmTcpPort
mandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15 |
|
wtWebGraphThermHygroAlarmTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16 |
|
wtWebGraphThermHygroAlarmClearMailSubject
mandatory
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17 |
|
wtWebGraphThermHygroAlarmClearMailText
mandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18 |
|
wtWebGraphThermHygroAlarmClearTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19 |
|
wtWebGraphThermHygroAlarmClearTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20 |
|
wtWebGraphThermHygroAlarmDeltaTemp
mandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21 |
|
wtWebGraphThermHygroAlarmRHMin
mandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22 |
|
wtWebGraphThermHygroAlarmRHMax
mandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23 |
|
wtWebGraphThermHygroAlarmRHHysteresis
mandatory
Hysterese rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24 |
|
wtWebGraphThermHygroAlarmAHMin
mandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25 |
|
wtWebGraphThermHygroAlarmAHMax
mandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26 |
|
wtWebGraphThermHygroAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
RFC1155-SMIIpAddressr/w Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27 |
|
wtWebGraphThermHygroAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28 |
|
wtWebGraphThermHygroAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29 |
|
wtWebGraphThermHygroAlarmSyslogClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30 |
|
wtWebGraphThermHygroAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31 |
|
wtWebGraphThermHygroAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32 |
|
wtWebGraphThermHygroAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33 |
|
wtWebGraphThermHygroAlarmFtpClearText
mandatory
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34 |
|
wtWebGraphThermHygroAlarmFtpOptions
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35 |
|
wtWebGraphThermHygroAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36 |
.1.3.6.1.4.1.5040.1.2.9.3.2.1
·
1 row entry
·
8 columns
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
wtWebGraphThermHygroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermHygroPortName
mandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.1 |
|
wtWebGraphThermHygroPortText
mandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.2 |
|
wtWebGraphThermHygroPortOffset1
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.3 |
|
wtWebGraphThermHygroPortTemperature1
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.4 |
|
wtWebGraphThermHygroPortOffset2
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.5 |
|
wtWebGraphThermHygroPortTemperature2
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.6 |
|
wtWebGraphThermHygroPortComment
mandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.7 |
|
wtWebGraphThermHygroPortSensorSelect
mandatory
Binary coded options for sensor 1:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : PT100 Bit 1 : PT1000 (default) Bit 2-7: unused Binary coded options for sensor 2: Octet 1: unuse… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.9.3.2.1.1.8 |