wtWebGraphThermHygroAlarmSyslogPort
WebGraph-OLD-Thermo-Hygrometer-US-MIB ·
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28
Object
column
mandatory
r/w
Integer32
Port number of the syslog server to which the Webio device should send syslog messages.
Context
- MIB
- WebGraph-OLD-Thermo-Hygrometer-US-MIB
- OID
.1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebGraphThermHygroAlarmEntry
- Table
- wtWebGraphThermHygroAlarmTable
- Siblings
- 35
Syntax
Integer32
Values & Constraints
Object Constraints
range: 1-65535
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wtWebGraphThermHygroAlarmTrigger mandatory Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Senso… | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1 |
| wtWebGraphThermHygroAlarmMailText mandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10 |
| wtWebGraphThermHygroAlarmManagerIP mandatory Name or IP address of the SNMP Manager which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11 |
| wtWebGraphThermHygroAlarmTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12 |
| wtWebGraphThermHygroAlarmMailOptions mandatory Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13 |
| wtWebGraphThermHygroAlarmTcpIpAddr mandatory Name or IP address of the TCP server which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14 |
| wtWebGraphThermHygroAlarmTcpPort mandatory Port number of the TCP server which accepts the trap. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15 |
| wtWebGraphThermHygroAlarmTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16 |
| wtWebGraphThermHygroAlarmClearMailSubject mandatory Subject line for alarm clear mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17 |
| wtWebGraphThermHygroAlarmClearMailText mandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18 |
| wtWebGraphThermHygroAlarmClearTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19 |
| wtWebGraphThermHygroAlarmMin mandatory Minimum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2 |
| wtWebGraphThermHygroAlarmClearTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20 |
| wtWebGraphThermHygroAlarmDeltaTemp mandatory Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21 |
| wtWebGraphThermHygroAlarmRHMin mandatory Minimum rel. Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22 |
| wtWebGraphThermHygroAlarmRHMax mandatory Maximum rel.Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23 |
| wtWebGraphThermHygroAlarmRHHysteresis mandatory Hysterese rel. Humidity in percent with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24 |
| wtWebGraphThermHygroAlarmAHMin mandatory Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25 |
| wtWebGraphThermHygroAlarmAHMax mandatory Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26 |
| wtWebGraphThermHygroAlarmSyslogIpAddr mandatory IP address of the syslog server to which the Webio device should send syslog messages. | column | RFC1155-SMIIpAddress | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27 |
| wtWebGraphThermHygroAlarmSyslogText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29 |
| wtWebGraphThermHygroAlarmMax mandatory Maximum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3 |
| wtWebGraphThermHygroAlarmSyslogClearText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30 |
| wtWebGraphThermHygroAlarmFtpDataPort mandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31 |
| wtWebGraphThermHygroAlarmFtpFileName mandatory Name of the file including path informations. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32 |
| wtWebGraphThermHygroAlarmFtpText mandatory Message text to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33 |
| wtWebGraphThermHygroAlarmFtpClearText mandatory Alarm clear message to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34 |
| wtWebGraphThermHygroAlarmFtpOptions mandatory Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
… | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35 |
| wtWebGraphThermHygroAlarmTimerCron mandatory This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are… | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36 |
| wtWebGraphThermHygroAlarmHysteresis mandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 |
| wtWebGraphThermHygroAlarmDelay mandatory Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5 |
| wtWebGraphThermHygroAlarmInterval mandatory Send interval for alarm messages. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6 |
| wtWebGraphThermHygroAlarmEnable mandatory Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7 |
| wtWebGraphThermHygroAlarmEMailAddr mandatory E-Mail address for sending the alarm mail to. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8 |
| wtWebGraphThermHygroAlarmMailSubject mandatory Subject line for alarm mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9 |