.1.3.6.1.4.1.1718.4.1.2.2 · 1 row entry · 19 columns
Unit configuration table.
st4UnitConfigEntry entry .1.3.6.1.4.1.1718.4.1.2.2.1
Configuration objects for a particular unit.
Indexes
st4UnitIndex
Column Syntax OID
st4UnitIndex
Unit index. A=1, B=2, C=3, D=4, E=5, F=6.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.1718.4.1.2.2.1.1
st4UnitID
The internal ID of the unit. Format=A.
OctetString
Constraints:
range: 1-1
.1.3.6.1.4.1.1718.4.1.2.2.1.2
st4UnitName
The name of the unit.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.3
st4UnitProductSN
The product serial number of the unit.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.4
st4UnitModel
The model of the unit.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.5
st4UnitAssetTag
The asset tag of the unit.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.6
st4UnitType
The type of the unit.
Enumeration
Enumerated Values:
0primary
1link
2controller
3emcu
.1.3.6.1.4.1.1718.4.1.2.2.1.7
st4UnitCapabilities
The capabilities of the unit.
Bits
Enumerated Values:
0dc
1phase3
2wye
3delta
.1.3.6.1.4.1.1718.4.1.2.2.1.8
st4UnitProductMfrDate
The product manufacture date in YYYY-MM-DD (ISO 8601 format) of
the unit.
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.1718.4.1.2.2.1.9
st4UnitDisplayOrientation
The orientation of all displays in the unit.
Enumerationr/w
Enumerated Values:
0normal
1inverted
2auto
.1.3.6.1.4.1.1718.4.1.2.2.1.20
st4UnitOutletSequenceOrder
The sequencing order of all outlets in the unit.
Enumerationr/w
Enumerated Values:
0normal
1reversed
.1.3.6.1.4.1.1718.4.1.2.2.1.21
st4UnitOutletDisplayOrder
The display order in the user interfaces of all outlets in the
unit.
Enumerationr/w
Enumerated Values:
0normal
1reversed
.1.3.6.1.4.1.1718.4.1.2.2.1.22
st4UnitInputCordCount
The number of power input cords into the unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.30
st4UnitTempSensorCount
The number of external temperature sensors supported by the unit.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.2.2.1.31
st4UnitHumidSensorCount
The number of external humidity sensors supported by the unit.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.2.2.1.32
st4UnitWaterSensorCount
The number of external water sensors supported by the unit.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.2.2.1.33
st4UnitCcSensorCount
The number of external contact closure sensors supported by the
unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.34
st4UnitAdcSensorCount
The number of analog-to-digital converter sensors supported by the
unit.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.2.2.1.35
st4UnitFanSensorCount
The number of fan sensors supported by the unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.36
.1.3.6.1.4.1.1718.4.1.2.3 · 1 row entry · 1 columns
Unit monitor table.
st4UnitMonitorEntry entry .1.3.6.1.4.1.1718.4.1.2.3.1
Objects to monitor for a particular unit.
Indexes
st4UnitIndex
Column Syntax OID
st4UnitStatus
The status of the unit.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.2.3.1.1
.1.3.6.1.4.1.1718.4.1.2.4 · 1 row entry · 1 columns
Unit event configuration table.
st4UnitEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.2.4.1
Event configuration objects for a particular unit.
Indexes
st4UnitIndex
Column Syntax OID
st4UnitNotifications
The notification methods enabled for unit events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.2.4.1.1
.1.3.6.1.4.1.1718.4.1.3.2 · 1 row entry · 16 columns
Input cord configuration table.
st4InputCordConfigEntry entry .1.3.6.1.4.1.1718.4.1.3.2.1
Configuration objects for a particular input cord.
Indexes
st4UnitIndex st4InputCordIndex
Column Syntax OID
st4InputCordIndex
Input cord index. A=1, B=2, C=3, D=4.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.1718.4.1.3.2.1.1
st4InputCordID
The internal ID of the input cord. Format=AA.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.3.2.1.2
st4InputCordName
The name of the input cord.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.3.2.1.3
st4InputCordInletType
The type of plug on the input cord, or socket for the input cord.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.3.2.1.6
st4InputCordNominalVoltage
The user-configured nominal voltage of the input cord in tenth
Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.3.2.1.7
st4InputCordNominalVoltageMin
The factory-set minimum allowed for the user-configured nominal
voltage of the input cord in Volts.
VoltsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.8
st4InputCordNominalVoltageMax
The factory-set maximum allowed for the user-configured nominal
voltage of the input cord in Volts.
VoltsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.9
st4InputCordCurrentCapacity
The user-configured current capacity of the input cord in Amps.
AmpsInteger32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.10
st4InputCordCurrentCapacityMax
The factory-set maximum allowed for the user-configured current
capacity of the input cord in Amps.
AmpsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.11
st4InputCordPowerCapacity
The power capacity of the input cord in Volt-Amps. For DC
products, this is identical to power capacity in Watts.
Volt-AmpsInteger32
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.2.1.12
st4InputCordNominalPowerFactor
The user-configured estimated nominal power factor of the input
cord in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.2.1.13
st4InputCordLineCount
The number of current-carrying lines in the input cord.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.3.2.1.20
st4InputCordPhaseCount
The number of active phases from the lines in the input cord.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.1718.4.1.3.2.1.21
st4InputCordOcpCount
The number of over-current protectors downstream from the input
cord.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.3.2.1.22
st4InputCordBranchCount
The number of branches downstream from the input cord.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.3.2.1.23
st4InputCordOutletCount
The number of outlets powered from the input cord.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.3.2.1.24
.1.3.6.1.4.1.1718.4.1.3.3 · 1 row entry · 13 columns
Input cord monitor table.
st4InputCordMonitorEntry entry .1.3.6.1.4.1.1718.4.1.3.3.1
Objects to monitor for a particular input cord.
Indexes
st4UnitIndex st4InputCordIndex
Column Syntax OID
st4InputCordState
The on/off state of the input cord.
DeviceState
Textual Convention: DeviceState Enumeration
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.3.3.1.1
st4InputCordStatus
The status of the input cord.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.2
st4InputCordActivePower
The measured active power of the input cord in Watts.
WattsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.4.1.3.3.1.3
st4InputCordActivePowerStatus
The status of the measured active power of the input cord.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.4
st4InputCordApparentPower
The measured apparent power of the input cord in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.4.1.3.3.1.5
st4InputCordApparentPowerStatus
The status of the measured apparent power of the input cord.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.6
st4InputCordPowerUtilized
The amount of the input cord power capacity used in tenth percent.
For AC products, this is the ratio of the apparent power to the
power capacity. For DC products, this is the ratio of the active
power to the power cap…
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.3.3.1.7
st4InputCordPowerFactor
The measured power factor of the input cord in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.3.3.1.8
st4InputCordPowerFactorStatus
The status of the measured power factor of the input cord.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.9
st4InputCordEnergy
The total energy consumption of loads through the input cord in
tenth Kilowatt-Hours.
tenth Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.3.3.1.10
st4InputCordFrequency
The frequency of the input cord voltage in tenth Hertz.
tenth HertzInteger32
Constraints:
range: -1-1000
.1.3.6.1.4.1.1718.4.1.3.3.1.11
st4InputCordOutOfBalance
The current imbalance on the lines of the input cord in tenth
percent.
tenth percentInteger32
Constraints:
range: -1-2000
.1.3.6.1.4.1.1718.4.1.3.3.1.12
st4InputCordOutOfBalanceStatus
The status of the current imbalance on the lines of the input
cord.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.13
.1.3.6.1.4.1.1718.4.1.3.4 · 1 row entry · 13 columns
Input cord event configuration table.
st4InputCordEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.3.4.1
Event configuration objects for a particular input cord.
Indexes
st4UnitIndex st4InputCordIndex
Column Syntax OID
st4InputCordNotifications
The notification methods enabled for input cord events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.3.4.1.1
st4InputCordActivePowerLowAlarm
The active power low alarm threshold of the input cord in Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.2
st4InputCordActivePowerLowWarning
The active power low warning threshold of the input cord in
Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.3
st4InputCordActivePowerHighWarning
The active power high warning threshold of the input cord in
Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.4
st4InputCordActivePowerHighAlarm
The active power high alarm threshold of the input cord in Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.5
st4InputCordApparentPowerLowAlarm
The apparent power low alarm threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.6
st4InputCordApparentPowerLowWarning
The apparent power low warning threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.7
st4InputCordApparentPowerHighWarning
The apparent power high warning threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.8
st4InputCordApparentPowerHighAlarm
The apparent power high alarm threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.9
st4InputCordPowerFactorLowAlarm
The power factor low alarm threshold of the input cord in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.10
st4InputCordPowerFactorLowWarning
The power factor low warning threshold of the input cord in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.11
st4InputCordOutOfBalanceHighWarning
The 3 phase out-of-balance high warning threshold of the input
cord in percent.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.12
st4InputCordOutOfBalanceHighAlarm
The 3 phase out-of-balance high alarm threshold of the input cord
in percent.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.13
.1.3.6.1.4.1.1718.4.1.4.2 · 1 row entry · 4 columns
Line configuration table.
st4LineConfigEntry entry .1.3.6.1.4.1.1718.4.1.4.2.1
Configuration objects for a particular line.
Indexes
st4UnitIndex st4InputCordIndex st4LineIndex
Column Syntax OID
st4LineIndex
Line index. L1=1, L2=2, L3=3, N=4.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.1718.4.1.4.2.1.1
st4LineID
The internal ID of the line. Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.4.2.1.2
st4LineLabel
The system label assigned to the line for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.4.2.1.4
st4LineCurrentCapacity
The current capacity of the line in Amps.
AmpsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.4.2.1.6
.1.3.6.1.4.1.1718.4.1.4.3 · 1 row entry · 5 columns
Line monitor table.
st4LineMonitorEntry entry .1.3.6.1.4.1.1718.4.1.4.3.1
Objects to monitor for a particular line.
Indexes
st4UnitIndex st4InputCordIndex st4LineIndex
Column Syntax OID
st4LineState
The on/off state of the line.
DeviceState
Textual Convention: DeviceState Enumeration
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.4.3.1.1
st4LineStatus
The status of the line.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.4.3.1.2
st4LineCurrent
The measured current on the line in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-60000
.1.3.6.1.4.1.1718.4.1.4.3.1.3
st4LineCurrentStatus
The status of the measured current on the line.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.4.3.1.4
st4LineCurrentUtilized
The amount of the line current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.4.3.1.5
.1.3.6.1.4.1.1718.4.1.4.4 · 1 row entry · 5 columns
Line event configuration table.
st4LineEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.4.4.1
Event configuration objects for a particular line.
Indexes
st4UnitIndex st4InputCordIndex st4LineIndex
Column Syntax OID
st4LineNotifications
The notification methods enabled for line events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.4.4.1.1
st4LineCurrentLowAlarm
The current low alarm threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.2
st4LineCurrentLowWarning
The current low warning threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.3
st4LineCurrentHighWarning
The current high warning threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.4
st4LineCurrentHighAlarm
The current high alarm threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.5
.1.3.6.1.4.1.1718.4.1.5.2 · 1 row entry · 6 columns
Phase configuration table.
st4PhaseConfigEntry entry .1.3.6.1.4.1.1718.4.1.5.2.1
Configuration objects for a particular phase.
Indexes
st4UnitIndex st4InputCordIndex st4PhaseIndex
Column Syntax OID
st4PhaseIndex
Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3;
Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase:
L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2,
L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.1718.4.1.5.2.1.1
st4PhaseID
The internal ID of the phase. Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.5.2.1.2
st4PhaseLabel
The system label assigned to the phase for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.5.2.1.4
st4PhaseNominalVoltage
The nominal voltage of the phase in tenth Volts.
tenth VoltsInteger32
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.2.1.6
st4PhaseBranchCount
The number of branches downstream from the phase.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.5.2.1.20
st4PhaseOutletCount
The number of outlets powered from the phase.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.5.2.1.21
.1.3.6.1.4.1.1718.4.1.5.3 · 1 row entry · 13 columns
Phase monitor table.
st4PhaseMonitorEntry entry .1.3.6.1.4.1.1718.4.1.5.3.1
Objects to monitor for a particular phase.
Indexes
st4UnitIndex st4InputCordIndex st4PhaseIndex
Column Syntax OID
st4PhaseState
The on/off state of the phase.
DeviceState
Textual Convention: DeviceState Enumeration
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.5.3.1.1
st4PhaseStatus
The status of the phase.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.2
st4PhaseVoltage
The measured voltage on the phase in tenth Volts.
tenth VoltsInteger32
Constraints:
range: -1-6000
.1.3.6.1.4.1.1718.4.1.5.3.1.3
st4PhaseVoltageStatus
The status of the measured voltage on the phase.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.4
st4PhaseVoltageDeviation
The deviation from the nominal voltage on the phase in tenth
percent.
tenth percentInteger32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.1718.4.1.5.3.1.5
st4PhaseCurrent
The measured current on the phase in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-30000
.1.3.6.1.4.1.1718.4.1.5.3.1.6
st4PhaseCurrentCrestFactor
The measured crest factor of the current waveform on the phase in
tenths.
tenthsInteger32
Constraints:
range: -1-250
.1.3.6.1.4.1.1718.4.1.5.3.1.7
st4PhaseActivePower
The measured active power on the phase in Watts.
WattsInteger32
Constraints:
range: -1-25000
.1.3.6.1.4.1.1718.4.1.5.3.1.8
st4PhaseApparentPower
The measured apparent power on the phase in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-25000
.1.3.6.1.4.1.1718.4.1.5.3.1.9
st4PhasePowerFactor
The measured power factor on the phase in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.5.3.1.10
st4PhasePowerFactorStatus
The status of the measured power factor on the phase.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.11
st4PhaseReactance
The status of the measured reactance of the phase.
Enumeration
Enumerated Values:
0unknown
1capacitive
2inductive
3resistive
.1.3.6.1.4.1.1718.4.1.5.3.1.12
st4PhaseEnergy
The total energy consumption of loads through the phase in tenth
Kilowatt-Hours.
tenth Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.5.3.1.13
.1.3.6.1.4.1.1718.4.1.5.4 · 1 row entry · 7 columns
Phase event configuration table.
st4PhaseEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.5.4.1
Event configuration objects for a particular phase.
Indexes
st4UnitIndex st4InputCordIndex st4PhaseIndex
Column Syntax OID
st4PhaseNotifications
The notification methods enabled for phase events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.5.4.1.1
st4PhaseVoltageLowAlarm
The current low alarm threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.2
st4PhaseVoltageLowWarning
The current low warning threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.3
st4PhaseVoltageHighWarning
The current high warning threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.4
st4PhaseVoltageHighAlarm
The current high alarm threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.5
st4PhasePowerFactorLowAlarm
The low power factor alarm threshold of the phase in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.5.4.1.6
st4PhasePowerFactorLowWarning
The low power factor warning threshold of the phase in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.5.4.1.7
.1.3.6.1.4.1.1718.4.1.6.2 · 1 row entry · 8 columns
Over-current protector configuration table.
st4OcpConfigEntry entry .1.3.6.1.4.1.1718.4.1.6.2.1
Configuration objects for a particular over-current protector.
Indexes
st4UnitIndex st4InputCordIndex st4OcpIndex
Column Syntax OID
st4OcpIndex
Over-current protector index.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.1718.4.1.6.2.1.1
st4OcpID
The internal ID of the over-current protector. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.6.2.1.2
st4OcpLabel
The system label assigned to the over-current protector for
identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.6.2.1.4
st4OcpType
The type of over-current protector.
Enumeration
Enumerated Values:
0fuse
1breaker
.1.3.6.1.4.1.1718.4.1.6.2.1.6
st4OcpCurrentCapacity
The user-configured current capacity of the over-current protector
in Amps.
AmpsInteger32r/w
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.6.2.1.7
st4OcpCurrentCapacityMax
The factory-set maximum allowed for the user-configured current
capacity of the over-current protector in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.6.2.1.8
st4OcpBranchCount
The number of branches downstream from the over-current
protector.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.6.2.1.20
st4OcpOutletCount
The number of outlets powered from the over-current protector.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.6.2.1.21
.1.3.6.1.4.1.1718.4.1.6.3 · 1 row entry · 1 columns
Over-current protector monitor table.
st4OcpMonitorEntry entry .1.3.6.1.4.1.1718.4.1.6.3.1
Objects to monitor for a particular over-current protector.
Indexes
st4UnitIndex st4InputCordIndex st4OcpIndex
Column Syntax OID
st4OcpStatus
The status of the over-current protector.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.6.3.1.1
.1.3.6.1.4.1.1718.4.1.6.4 · 1 row entry · 1 columns
Over-current protector event configuration table.
st4OcpEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.6.4.1
Event configuration objects for a particular over-current
protector.
Indexes
st4UnitIndex st4InputCordIndex st4OcpIndex
Column Syntax OID
st4OcpNotifications
The notification methods enabled for over-current protector
events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.6.4.1.1
.1.3.6.1.4.1.1718.4.1.7.2 · 1 row entry · 7 columns
Branch configuration table.
st4BranchConfigEntry entry .1.3.6.1.4.1.1718.4.1.7.2.1
Configuration objects for a particular branch.
Indexes
st4UnitIndex st4InputCordIndex st4BranchIndex
Column Syntax OID
st4BranchIndex
Branch index.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.1718.4.1.7.2.1.1
st4BranchID
The internal ID of the branch. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.7.2.1.2
st4BranchLabel
The system label assigned to the branch for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.7.2.1.4
st4BranchCurrentCapacity
The current capacity of the branch in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.7.2.1.6
st4BranchPhaseID
The internal ID of the phase powering this branch.
Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.7.2.1.20
st4BranchOcpID
The internal ID of the over-current protector powering this
outlet. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.7.2.1.21
st4BranchOutletCount
The number of outlets powered from the branch.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.7.2.1.30
.1.3.6.1.4.1.1718.4.1.7.3 · 1 row entry · 5 columns
Branch monitor table.
st4BranchMonitorEntry entry .1.3.6.1.4.1.1718.4.1.7.3.1
Objects to monitor for a particular branch.
Indexes
st4UnitIndex st4InputCordIndex st4BranchIndex
Column Syntax OID
st4BranchState
The on/off state of the branch.
DeviceState
Textual Convention: DeviceState Enumeration
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.7.3.1.1
st4BranchStatus
The status of the branch.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.7.3.1.2
st4BranchCurrent
The measured current on the branch in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-12500
.1.3.6.1.4.1.1718.4.1.7.3.1.3
st4BranchCurrentStatus
The status of the measured current on the branch.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.7.3.1.4
st4BranchCurrentUtilized
The amount of the branch current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.7.3.1.5
.1.3.6.1.4.1.1718.4.1.7.4 · 1 row entry · 5 columns
Branch event configuration table.
st4BranchEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.7.4.1
Event configuration objects for a particular branch.
Indexes
st4UnitIndex st4InputCordIndex st4BranchIndex
Column Syntax OID
st4BranchNotifications
The notification methods enabled for branch events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.7.4.1.1
st4BranchCurrentLowAlarm
The current low alarm threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.2
st4BranchCurrentLowWarning
The current low warning threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.3
st4BranchCurrentHighWarning
The current high warning threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.4
st4BranchCurrentHighAlarm
The current high alarm threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.5
.1.3.6.1.4.1.1718.4.1.8.2 · 1 row entry · 13 columns
Outlet configuration table.
st4OutletConfigEntry entry .1.3.6.1.4.1.1718.4.1.8.2.1
Configuration objects for a particular outlet.
Indexes
st4UnitIndex st4InputCordIndex st4OutletIndex
Column Syntax OID
st4OutletIndex
Outlet index.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.1718.4.1.8.2.1.1
st4OutletID
The internal ID of the outlet. Format=AAN[N[N]].
OctetString
Constraints:
range: 3-5
.1.3.6.1.4.1.1718.4.1.8.2.1.2
st4OutletName
The name of the outlet.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.8.2.1.3
st4OutletCapabilities
The capabilities of the outlet.
Bits
Enumerated Values:
0switched
1pops
.1.3.6.1.4.1.1718.4.1.8.2.1.5
st4OutletSocketType
The socket type of the outlet.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.8.2.1.6
st4OutletCurrentCapacity
The current capacity of the outlet in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.8.2.1.7
st4OutletPowerCapacity
The power capacity of the outlet in Volt-Amps. For DC products,
this is identical to power capacity in Watts.
Volt-AmpsInteger32
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.2.1.8
st4OutletSocketAdapter
The manually-selected or automatically-detected socket adapter
of the outlet.
Enumerationr/w
Enumerated Values:
0none
1c13
2c19
.1.3.6.1.4.1.1718.4.1.8.2.1.9
st4OutletWakeupState
The wakeup state of the outlet.
Enumerationr/w
Enumerated Values:
0on
1off
2last
.1.3.6.1.4.1.1718.4.1.8.2.1.20
st4OutletPostOnDelay
The post-on delay of the outlet in seconds.
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.1718.4.1.8.2.1.21
st4OutletPhaseID
The internal ID of the phase powering this outlet.
Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.8.2.1.30
st4OutletOcpID
The internal ID of the over-current protector powering this
outlet. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.8.2.1.31
st4OutletBranchID
The internal ID of the branch powering this outlet.
Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.8.2.1.32
.1.3.6.1.4.1.1718.4.1.8.3 · 1 row entry · 14 columns
Outlet monitor table.
st4OutletMonitorEntry entry .1.3.6.1.4.1.1718.4.1.8.3.1
Objects to monitor for a particular outlet.
Indexes
st4UnitIndex st4InputCordIndex st4OutletIndex
Column Syntax OID
st4OutletState
The on/off state of the outlet.
DeviceState
Textual Convention: DeviceState Enumeration
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.8.3.1.1
st4OutletStatus
The status of the outlet.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.2
st4OutletCurrent
The measured current on the outlet in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-12500
.1.3.6.1.4.1.1718.4.1.8.3.1.3
st4OutletCurrentStatus
The status of the measured current on the outlet.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.4
st4OutletCurrentUtilized
The amount of the outlet current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.8.3.1.5
st4OutletVoltage
The measured voltage of the outlet in tenth Volts.
tenth VoltsInteger32
Constraints:
range: -1-6000
.1.3.6.1.4.1.1718.4.1.8.3.1.6
st4OutletActivePower
The measured active power of the outlet in Watts.
WattsInteger32
Constraints:
range: -1-10000
.1.3.6.1.4.1.1718.4.1.8.3.1.7
st4OutletActivePowerStatus
The status of the measured active power of the outlet.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.8
st4OutletApparentPower
The measured apparent power of the outlet in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-10000
.1.3.6.1.4.1.1718.4.1.8.3.1.9
st4OutletPowerFactor
The measured power factor of the outlet in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.8.3.1.10
st4OutletPowerFactorStatus
The status of the measured power factor of the outlet.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.11
st4OutletCurrentCrestFactor
The measured crest factor of the outlet in tenths.
tenthsInteger32
Constraints:
range: -1-250
.1.3.6.1.4.1.1718.4.1.8.3.1.12
st4OutletReactance
The status of the measured reactance of the outlet.
Enumeration
Enumerated Values:
0unknown
1capacitive
2inductive
3resistive
.1.3.6.1.4.1.1718.4.1.8.3.1.13
st4OutletEnergy
The total energy consumption of the device plugged into the outlet
in Watt-Hours.
Watt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.8.3.1.14
.1.3.6.1.4.1.1718.4.1.8.4 · 1 row entry · 11 columns
Outlet event configuration table.
st4OutletEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.8.4.1
Event configuration objects for a particular outlet.
Indexes
st4UnitIndex st4InputCordIndex st4OutletIndex
Column Syntax OID
st4OutletNotifications
The notification methods enabled for outlet events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.8.4.1.1
st4OutletCurrentLowAlarm
The current low alarm threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.2
st4OutletCurrentLowWarning
The current low warning threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.3
st4OutletCurrentHighWarning
The current high warning threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.4
st4OutletCurrentHighAlarm
The current high alarm threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.5
st4OutletActivePowerLowAlarm
The active power low alarm threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.6
st4OutletActivePowerLowWarning
The active power low warning threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.7
st4OutletActivePowerHighWarning
The active power high warning threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.8
st4OutletActivePowerHighAlarm
The active power high alarm threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.9
st4OutletPowerFactorLowAlarm
The low power factor alarm threshold of the outlet in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.8.4.1.10
st4OutletPowerFactorLowWarning
The low power factor warning threshold of the outlet in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.8.4.1.11
.1.3.6.1.4.1.1718.4.1.8.5 · 1 row entry · 2 columns
Outlet control table.
st4OutletControlEntry entry .1.3.6.1.4.1.1718.4.1.8.5.1
Objects for control of a particular outlet.
Indexes
st4UnitIndex st4InputCordIndex st4OutletIndex
Column Syntax OID
st4OutletControlState
The control state of the outlet.
Enumeration
Enumerated Values:
0notSet
1fixedOn
2idleOff
3idleOn
4wakeOff
5wakeOn
6ocpOff
7ocpOn
8pendOn
9pendOff
10off
11on
12reboot
13shutdown
14lockedOff
15lockedOn
16eventOff
17eventOn
18eventReboot
19eventShutdown
.1.3.6.1.4.1.1718.4.1.8.5.1.1
st4OutletControlAction
An action to change the control state of the outlet, or to queue
an action.
Enumerationr/w
Enumerated Values:
0none
1on
2off
3reboot
4queueOn
5queueOff
6queueReboot
.1.3.6.1.4.1.1718.4.1.8.5.1.2
.1.3.6.1.4.1.1718.4.1.9.2 · 1 row entry · 5 columns
Temperature sensor configuration table.
st4TempSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.9.2.1
Configuration objects for a particular temperature sensor.
Indexes
st4UnitIndex st4TempSensorIndex
Column Syntax OID
st4TempSensorIndex
Temperature sensor index.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.9.2.1.1
st4TempSensorID
The internal ID of the temperature sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.9.2.1.2
st4TempSensorName
The name of the temperature sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.9.2.1.3
st4TempSensorValueMin
The minimum temperature limit of the sensor in degrees, using the
scale selected by st4TempSensorScale.
degreesInteger32
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.2.1.4
st4TempSensorValueMax
The maximum temperature limit of the sensor in degrees, using the
scale selected by st4TempSensorScale.
degreesInteger32
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.2.1.5
.1.3.6.1.4.1.1718.4.1.9.3 · 1 row entry · 2 columns
Temperature sensor monitor table.
st4TempSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.9.3.1
Objects to monitor for a particular temperature sensor.
Indexes
st4UnitIndex st4TempSensorIndex
Column Syntax OID
st4TempSensorValue
The measured temperature on the sensor in tenth degrees using the
scale selected by st4TempSensorScale. -410 means the temperature
reading is invalid.
tenth degreesInteger32
Constraints:
range: -410-2540
.1.3.6.1.4.1.1718.4.1.9.3.1.1
st4TempSensorStatus
The status of the temperature sensor.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.9.3.1.2
.1.3.6.1.4.1.1718.4.1.9.4 · 1 row entry · 5 columns
Temperature sensor event configuration table.
st4TempSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.9.4.1
Event configuration objects for a particular temperature sensor.
Indexes
st4UnitIndex st4TempSensorIndex
Column Syntax OID
st4TempSensorNotifications
The notification methods enabled for temperature sensor events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.9.4.1.1
st4TempSensorLowAlarm
The low alarm threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.2
st4TempSensorLowWarning
The low warning threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.3
st4TempSensorHighWarning
The high warning threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.4
st4TempSensorHighAlarm
The high alarm threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.5
.1.3.6.1.4.1.1718.4.1.10.2 · 1 row entry · 3 columns
Humidity sensor configuration table.
st4HumidSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.10.2.1
Configuration objects for a particular humidity sensor.
Indexes
st4UnitIndex st4HumidSensorIndex
Column Syntax OID
st4HumidSensorIndex
Humidity sensor index.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.10.2.1.1
st4HumidSensorID
The internal ID of the humidity sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.10.2.1.2
st4HumidSensorName
The name of the humidity sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.10.2.1.3
.1.3.6.1.4.1.1718.4.1.10.3 · 1 row entry · 2 columns
Humidity sensor monitor table.
st4HumidSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.10.3.1
Objects to monitor for a particular humidity sensor.
Indexes
st4UnitIndex st4HumidSensorIndex
Column Syntax OID
st4HumidSensorValue
The measured humidity on the sensor in percentage relative
humidity.
percentage relative humidityInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.10.3.1.1
st4HumidSensorStatus
The status of the humidity sensor.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.10.3.1.2
.1.3.6.1.4.1.1718.4.1.10.4 · 1 row entry · 5 columns
Humidity sensor event configuration table.
st4HumidSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.10.4.1
Event configuration objects for a particular humidity sensor.
Indexes
st4UnitIndex st4HumidSensorIndex
Column Syntax OID
st4HumidSensorNotifications
The notification methods enabled for humidity sensor events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.10.4.1.1
st4HumidSensorLowAlarm
The low alarm threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.2
st4HumidSensorLowWarning
The low warning threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.3
st4HumidSensorHighWarning
The high warning threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.4
st4HumidSensorHighAlarm
The high alarm threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.5
.1.3.6.1.4.1.1718.4.1.11.2 · 1 row entry · 3 columns
Water sensor configuration table.
st4WaterSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.11.2.1
Configuration objects for a particular water sensor.
Indexes
st4UnitIndex st4WaterSensorIndex
Column Syntax OID
st4WaterSensorIndex
Water sensor index.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.11.2.1.1
st4WaterSensorID
The internal ID of the water sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.11.2.1.2
st4WaterSensorName
The name of the water sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.11.2.1.3
.1.3.6.1.4.1.1718.4.1.11.3 · 1 row entry · 1 columns
Water sensor monitor table.
st4WaterSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.11.3.1
Objects to monitor for a particular water sensor.
Indexes
st4UnitIndex st4WaterSensorIndex
Column Syntax OID
st4WaterSensorStatus
The status of the water sensor.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.11.3.1.1
.1.3.6.1.4.1.1718.4.1.11.4 · 1 row entry · 1 columns
Water sensor event configuration table.
st4WaterSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.11.4.1
Event configuration objects for a particular water sensor.
Indexes
st4UnitIndex st4WaterSensorIndex
Column Syntax OID
st4WaterSensorNotifications
The notification methods enabled for water sensor events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.11.4.1.1
.1.3.6.1.4.1.1718.4.1.12.2 · 1 row entry · 3 columns
Contact closure sensor configuration table.
st4CcSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.12.2.1
Configuration objects for a particular contact closure sensor.
Indexes
st4UnitIndex st4CcSensorIndex
Column Syntax OID
st4CcSensorIndex
Contact closure sensor index.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.12.2.1.1
st4CcSensorID
The internal ID of the contact closure sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.12.2.1.2
st4CcSensorName
The name of the contact closure sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.12.2.1.3
.1.3.6.1.4.1.1718.4.1.12.3 · 1 row entry · 1 columns
Contact closure sensor monitor table.
st4CcSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.12.3.1
Objects to monitor for a particular contact closure sensor.
Indexes
st4UnitIndex st4CcSensorIndex
Column Syntax OID
st4CcSensorStatus
The status of the contact closure.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.12.3.1.1
.1.3.6.1.4.1.1718.4.1.12.4 · 1 row entry · 1 columns
Contact closure sensor event configuration table.
st4CcSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.12.4.1
Event configuration objects for a particular contact closure
sensor.
Indexes
st4UnitIndex st4CcSensorIndex
Column Syntax OID
st4CcSensorNotifications
The notification methods enabled for contact closure sensor
events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.12.4.1.1
.1.3.6.1.4.1.1718.4.1.13.2 · 1 row entry · 3 columns
Analog-to-digital converter sensor configuration table.
st4AdcSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.13.2.1
Configuration objects for a particular analog-to-digital
converter sensor.
Indexes
st4UnitIndex st4AdcSensorIndex
Column Syntax OID
st4AdcSensorIndex
Analog-to-digital converter sensor index.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.13.2.1.1
st4AdcSensorID
The internal ID of the analog-to-digital converter sensor.
Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.13.2.1.2
st4AdcSensorName
The name of the analog-to-digital converter sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.13.2.1.3
.1.3.6.1.4.1.1718.4.1.13.3 · 1 row entry · 2 columns
Analog-to-digital converter sensor monitor table.
st4AdcSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.13.3.1
Objects to monitor for a particular analog-to-digital converter
sensor.
Indexes
st4UnitIndex st4AdcSensorIndex
Column Syntax OID
st4AdcSensorValue
The 8-bit value from the analog-to-digital converter sensor.
Integer32
Constraints:
range: -1-255
.1.3.6.1.4.1.1718.4.1.13.3.1.1
st4AdcSensorStatus
The status of the analog-to-digital converter sensor.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.13.3.1.2
.1.3.6.1.4.1.1718.4.1.13.4 · 1 row entry · 5 columns
Analog-to-digital converter sensor event configuration table.
st4AdcSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.13.4.1
Event configuration objects for a particular
analog-to-digital converter sensor.
Indexes
st4UnitIndex st4AdcSensorIndex
Column Syntax OID
st4AdcSensorNotifications
The notification methods enabled for analog-to-digital converter
sensor events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.13.4.1.1
st4AdcSensorLowAlarm
The 8-bit value for the low alarm threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.2
st4AdcSensorLowWarning
The 8-bit value for the low warning threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.3
st4AdcSensorHighWarning
The 8-bit value for the high warning threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.4
st4AdcSensorHighAlarm
The 8-bit value for the high alarm threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.5
.1.3.6.1.4.1.1718.4.1.14.2 · 1 row entry · 3 columns
Fan sensor configuration table.
st4FanSensorConfigEntry entry .1.3.6.1.4.1.1718.4.1.14.2.1
Configuration objects for a particular fan sensor.
Indexes
st4UnitIndex st4FanSensorIndex
Column Syntax OID
st4FanSensorIndex
Fan sensor index.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.14.2.1.1
st4FanSensorID
The internal ID of the fan sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.14.2.1.2
st4FanSensorName
The name of the fan sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.14.2.1.3
.1.3.6.1.4.1.1718.4.1.14.3 · 1 row entry · 2 columns
Fan sensor monitor table.
st4FanSensorMonitorEntry entry .1.3.6.1.4.1.1718.4.1.14.3.1
Objects to monitor for a particular fan sensor.
Indexes
st4UnitIndex st4FanSensorIndex
Column Syntax OID
st4FanSensorValue
The measured fan speed of the sensor in rotations per minute.
rotations per minuteInteger32
Constraints:
range: -1-15300
.1.3.6.1.4.1.1718.4.1.14.3.1.1
st4FanSensorStatus
The status of the fan sensor.
DeviceStatus
Textual Convention: DeviceStatus Enumeration
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.14.3.1.2
.1.3.6.1.4.1.1718.4.1.14.4 · 1 row entry · 5 columns
Fan sensor event configuration table.
st4FanSensorEventConfigEntry entry .1.3.6.1.4.1.1718.4.1.14.4.1
Event configuration objects for a particular fan sensor.
Indexes
st4UnitIndex st4FanSensorIndex
Column Syntax OID
st4FanSensorNotifications
The notification methods enabled for fan sensor events.
EventNotificationMethodsr/w
Textual Convention: EventNotificationMethods Bits
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.14.4.1.1
st4FanSensorLowAlarm
The low alarm threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.2
st4FanSensorLowWarning
The low warning threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.3
st4FanSensorHighWarning
The high warning threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.4
st4FanSensorHighAlarm
The high alarm threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.5